NTU method

The NTU method, or Number of Transfer Units method, is a dimensionless analytical technique employed in to assess the performance of heat exchangers by relating the device's size, fluid properties, and flow arrangement to its thermal effectiveness. Developed in the mid-20th century, it provides a standardized framework for predicting rates without requiring iterative calculations of differences, making it particularly useful for complex flow configurations such as counterflow, parallel flow, and crossflow. Central to the NTU method is the concept of effectiveness (ε), defined as the of the actual rate (Q) to the maximum possible rate (Q_max) under ideal conditions, where Q_max = C_min (T_{h,in} - T_{c,in}) and C_min is the smaller of the two fluid rates (ṁ c_p). The number of transfer units (NTU) quantifies the heat exchanger's capacity for , calculated as NTU = UA / C_min, with U as the overall and A as the surface area; higher NTU values indicate greater potential for . Additionally, the capacity ratio (C_r), given by C_r = C_min / C_max, accounts for the relative capacities of the fluids, influencing the -NTU through specific analytical expressions or charts derived for different exchanger geometries. Unlike the log mean temperature difference (LMTD) method, which relies on arithmetic temperature profiles and can be cumbersome for preliminary or non-standard flows, the NTU method offers direct correlations between ε, NTU, and C_r, enabling rapid evaluation and optimization in applications ranging from HVAC systems to power plant condensers. This approach, pioneered by W. M. Kays and A. L. London in their seminal work on compact exchangers, remains a cornerstone of thermal due to its versatility and accuracy across a wide range of operating conditions.

Fundamentals of the NTU Method

Heat Exchanger Effectiveness

The effectiveness of a , denoted as ε, is defined as the ratio of the actual rate Q to the maximum possible rate Q_max that could occur under ideal conditions for the given inlet temperatures and fluid properties. This dimensionless parameter provides a direct measure of the device's thermal performance, ranging from 0 (no ) to 1 (perfect ). The actual heat transfer rate Q can be expressed through the energy balance for each fluid stream. For the hot fluid, Q = C_h (T_{h,in} - T_{h,out}), where C_h is the heat capacity rate of the hot fluid (defined as \dot{m}h c{p,h}), T_{h,in} is the inlet temperature, and T_{h,out} is the outlet temperature. Similarly, for the cold fluid, Q = C_c (T_{c,out} - T_{c,in}), with C_c = \dot{m}c c{p,c}, T_{c,out} the outlet temperature, and T_{c,in} the inlet temperature. These equations ensure conservation of energy, equating the heat lost by the hot fluid to the heat gained by the cold fluid. The maximum possible heat transfer rate Q_max is limited by the fluid with the smaller heat capacity rate, C_min = \min(C_h, C_c), as this fluid experiences the largest potential temperature change. Thus, Q_max = C_min (T_{h,in} - T_{c,in}), representing the scenario where the fluid with C_min reaches the inlet temperature of the other fluid in a counterflow arrangement with infinite surface area. This thermodynamic limit establishes the upper bound for ε, independent of the exchanger's specific geometry. By focusing on ε rather than absolute temperatures or rates, the analysis simplifies comparisons across different heat exchanger designs and operating conditions, as ε depends only on the exchanger's intrinsic characteristics and the capacity ratio C_r = C_min / C_max. This approach facilitates performance evaluation without needing outlet temperature measurements, laying the groundwork for relating to parameters like the number of transfer units in design methodologies.

Definition of Number of Transfer Units

The number of transfer units (NTU) is a dimensionless that characterizes the size and heat transfer capability of a heat exchanger relative to the fluid streams involved. It serves as a key bridge between the heat exchanger's physical design parameters and its performance metric, the effectiveness ε. NTU is defined as \text{NTU} = \frac{UA}{C_{\min}} where U is the overall heat transfer coefficient, A is the heat transfer surface area, and C_{\min} is the minimum heat capacity rate of the two fluids (C = \dot{m} c_p). This formulation, introduced in seminal work on compact heat exchangers, quantifies the exchanger's thermal conductance relative to the limiting fluid's capacity to absorb or supply heat. Physically, NTU represents the ratio of the thermal resistance associated with the limiting-capacity fluid to the thermal resistance of the itself. The exchanger's resistance is $1/UA, while the fluid's effective resistance is $1/C_{\min}, such that a larger NTU indicates a lower relative resistance in the exchanger, enabling greater potential. The capacity ratio C_r = C_{\min}/C_{\max} (where C_{\max} is the maximum rate) modulates the influence of NTU on performance, as fluids with similar capacities (C_r \approx 1) limit the maximum achievable compared to cases where one fluid dominates (C_r \ll 1). In general, the effectiveness is expressed as \varepsilon = f(\text{NTU}, C_r, \text{flow arrangement}), allowing designers to evaluate exchanger performance without explicit outlet temperature calculations.

ε-NTU Relationships for Heat Transfer

Counterflow and Parallel Flow Configurations

In counterflow heat exchangers, the two fluids flow in opposite directions, maximizing the temperature difference along the exchanger length and thereby enhancing efficiency. This configuration is derived from the general -NTU framework, where ε represents the of actual to the maximum possible under ideal conditions, NTU is the number of transfer units (UA / C_min, with U as the overall , A the surface area, and C_min the minimum rate), and Cr is the (C_min / C_max). The ε-NTU relation for counterflow, assuming constant fluid properties, negligible heat loss to the surroundings, and steady-state operation, is given by \varepsilon = \frac{1 - \exp[-NTU(1 - Cr)]}{1 - Cr \exp[-NTU(1 - Cr)]} for Cr < 1. When Cr = 1 (balanced capacities), the relation simplifies to the limiting case \varepsilon = \frac{NTU}{1 + NTU}. These equations, originally developed in the context of compact heat exchangers, allow direct computation of performance without iterative temperature profile solutions. In parallel flow heat exchangers, both fluids flow in the same direction, resulting in a progressively diminishing temperature difference that limits overall effectiveness compared to counterflow. Under the same assumptions of constant properties, no external heat loss, and steady state, the ε-NTU relation is \varepsilon = \frac{1 - \exp[-NTU(1 + Cr)]}{1 + Cr}. This formulation highlights the inherent constraint of parallel flow, where effectiveness cannot exceed 0.5 for Cr = 1, even as NTU approaches infinity. Graphical representations of ε versus NTU for varying Cr values illustrate the superior performance of counterflow over parallel flow: for any given NTU and Cr, counterflow achieves higher ε, with curves approaching unity at large NTU regardless of Cr, while parallel flow curves asymptote below 1 and are steeper at low NTU but plateau earlier. This difference underscores counterflow's preference in applications requiring high thermal efficiency, such as cryogenic systems, though parallel flow may be simpler in certain layouts.

Crossflow and Shell-and-Tube Configurations

In crossflow heat exchangers, the fluids flow perpendicular to each other, leading to more complex temperature profiles compared to parallel or counterflow arrangements. The ε-NTU relationships for these configurations account for whether the fluids are unmixed (separated by partitions, preventing lateral mixing) or mixed (allowing free lateral mixing). For both fluids unmixed, an approximate analytical expression for effectiveness is given by \epsilon = 1 - \exp\left( \frac{\exp(-C_r \mathrm{NTU}^{0.78}) - 1}{C_r \mathrm{NTU}^{-0.22}} \right), where C_r = C_{\min}/C_{\max} is the capacity ratio. This formula, derived from numerical solutions for compact heat exchangers, provides high accuracy for design purposes and is widely used in applications like air-cooled condensers. For crossflow with one fluid mixed and the other unmixed, the effectiveness depends on which fluid has the minimum capacity rate. When the unmixed fluid has C_{\min}, the relation is \epsilon = \frac{1}{C_r} \left[1 - \exp\left(-C_r \left(1 - \exp(-\mathrm{NTU})\right)\right)\right]. This expression arises from integrating the energy balance assuming plug flow for the unmixed fluid and perfect mixing for the other, commonly applied in scenarios such as finned-tube exchangers where air is unmixed and the tube-side fluid is mixed. If the mixed fluid has C_{\min}, the formula inverts to \epsilon = 1 - \exp\left[ -\frac{1}{C_r} (1 - \exp(-C_r \mathrm{NTU})) \right]. Shell-and-tube heat exchangers, particularly those with one shell pass and an even number of tube passes (e.g., 1-2 TEMA E configuration), have a standard closed-form ε-NTU relation accounting for the mixed crossflow and counterflow elements. For a one-shell-pass exchanger, the effectiveness is \varepsilon = \frac{2}{1 + C_r + \sqrt{1 + C_r^2} \cdot \frac{1 + \exp\left(-\mathrm{NTU} \sqrt{1 + C_r^2}\right)}{1 - \exp\left(-\mathrm{NTU} \sqrt{1 + C_r^2}\right)}}, where C_r = C_{\min}/C_{\max}. This formula, applicable under assumptions of constant properties and steady-state operation, enables direct performance evaluation. Approximations using a correction factor F applied to the counterflow LMTD or ε-NTU baseline are also common, where F < 1 accounts for deviations from ideal counterflow, determined from charts or equations based on temperature effectiveness P = (T_{t,out} - T_{t,in}) / (T_{s,in} - T_{t,in}) and capacity ratio R = C_t / C_s, typically yielding F values between 0.8 and 1.0 for practical ranges. The LMTD method links directly to ε-NTU for validation in crossflow and shell-and-tube exchangers, as both approaches yield equivalent heat transfer rates q = C_{\min} \epsilon (T_{h,in} - T_{c,in}) = U A F \Delta T_{lm,cf} when parameters are consistent. This equivalence allows designers to cross-check results, with ε-NTU preferred for unknown outlet temperatures and LMTD with F for specified temperatures, ensuring accuracy in industrial applications like power plant condensers.

Extensions to Mass Transfer

Gaseous Mass Transfer Applications

The NTU method extends the principles of heat exchanger analysis to gaseous mass transfer processes, such as gas absorption, by drawing an analogy between thermal driving forces (temperature differences) and concentration driving forces (mole fraction or partial pressure differences). This adaptation enables the design and performance evaluation of equipment like packed columns where a solute gas transfers from a carrier gas stream to a liquid absorbent. The core dimensionless parameters—effectiveness and number of transfer units—facilitate predictions without solving complex differential equations, provided equilibrium and operating line relationships are known. In gaseous mass transfer, the number of transfer units is defined as NTU = \frac{K a V}{G}, where K is the overall mass transfer coefficient (mol/(m²·s·Δy)), a is the specific interfacial area (m²/m³), V is the active volume of the transfer zone (m³), and G is the total inert molar gas flow rate (mol/s). This parameter quantifies the available mass transfer area relative to the gas throughput, analogous to UA / (\dot{m} c_p) in . The mass transfer effectiveness, \varepsilon_m, is the ratio of actual solute transferred to the maximum transferable under ideal conditions, often formulated as \varepsilon_m = \frac{y_{in} - y_{out}}{y_{in} - y^*_{in}}, where y denotes gas-phase mole fraction and y^* is the equilibrium mole fraction corresponding to the inlet liquid composition. These definitions assume dilute systems where logarithmic mean driving forces apply. The \varepsilon-NTU relations for mass transfer parallel heat transfer formulations but incorporate a capacity ratio that accounts for phase via Henry's law. For countercurrent gas , the effectiveness is given by \varepsilon = \frac{1 - \exp[-NTU(1 - 1/A)]}{1 - (1/A) \exp[-NTU(1 - 1/A)]}, where A = Q_L / (H \cdot Q_G) is the absorption factor, H is the dimensionless Henry's law constant (y = H x, with y and x mole fractions), and Q_G, Q_L are the inert gas and liquid molar flow rates (mol/s). This relation adjusts for the relative capacities of the phases, with A > 1 favoring high absorption efficiency. For cases where deviates (non-linear), of the operating and equilibrium lines refines NTU calculations. A key application is CO₂ absorption in packed towers using amine solvents like monoethanolamine (MEA) to capture acid gases from flue streams. Here, the equilibrium line follows as y = m x, where m dictates the minimum liquid rate and driving force (y - y^*) along the column; deviations from ideality due to chemical reactions enhance effective capacity. Using the NTU method, designers compute required packing as Z = HTU \cdot NTU, with HTU = G / (K a) typically 0.3–0.5 m for structured packings. For a retrofit treating 500 kg/s (10% CO₂) at a coal plant, NTU ≈7.84 achieves 95% removal with MEA circulation at 142.5 kg/min, equilibrium gas-liquid ratio z=36, and column dimensions of 1.5 m by 3 m , demonstrating scalable efficiency under operating constraints.

Dehumidification and Humidification Processes

In air- systems, the NTU method is adapted for dehumidification processes in cooling s to simultaneously address cooling and removal through moisture condensation, incorporating psychrometric properties such as and . This involves defining separate transfer units for heat (NTU_h) and (NTU_m) to capture the coupled heat and , where NTU_h relates to the transfer coefficient and surface area divided by the minimum rate, while NTU_m is similarly defined using the for . The bypass factor (BF), defined as the fraction of air that does not contact the coil surface effectively, is integrated into coil performance models to adjust for incomplete mixing, with BF = 1 - ε, where ε is the overall ; lower BF values indicate higher coil in dehumidifying moist air streams typical in HVAC applications. The total energy effectiveness for dehumidifying coils is often expressed in terms of enthalpy to account for both sensible and latent effects, given by ε = (h_{in} - h_{out}) / (h_{in} - h_{wb}), where h_{in} and h_{out} are the inlet and outlet air enthalpies, and h_{wb} is the wet-bulb enthalpy representing the coil's apparatus dew point. This formulation allows the NTU method to relate coil performance to the capacity rates of air (C_a = \dot{m}a c{p,a}) and refrigerant or chilled water (C_r), with the overall NTU = UA / C_{min}, where U is the overall heat transfer coefficient adjusted for wet conditions. For air-water systems, the Lewis number (Le = α / D ≈ 1, where α is thermal diffusivity and D is the mass diffusivity of water vapor in air) simplifies the analogy between heat and mass transfer, enabling the use of a single NTU for enthalpy-based calculations when Le is near unity, though models correct for deviations to improve accuracy in predicting outlet conditions like relative humidity and dew point. In humidification processes, such as those in adiabatic saturators or spray towers, the NTU method evaluates the approach to saturation by treating the process as evaporative cooling at constant wet-bulb temperature, where air gains moisture from water sprays or wetted media without external heating. The NTU is defined as NTU = h_g A / (G c_p), with h_g as the gas-side heat transfer coefficient, A the contact area, G the air mass flow rate, and c_p the specific heat of moist air; this quantifies the driving force for mass transfer of water vapor into the airstream. Effectiveness ε approaches 1 for sufficiently long towers or high NTU values (>3-5), achieving near-adiabatic saturation where outlet air enthalpy equals the inlet water wet-bulb enthalpy, as demonstrated in wetted media humidifiers with contact factors exceeding 0.95 under typical HVAC flow rates. This application highlights the NTU method's utility in designing psychrometric processes for air conditioning, ensuring precise control of humidity ratios without excessive energy input.

Key Considerations and Limitations

Role of Specific Heat Capacity Rates

In heat exchanger analysis using the NTU method, the heat capacity rate C for each fluid stream is defined as the product of its mass flow rate \dot{m} and at constant pressure c_p, yielding C = \dot{m} c_p. The minimum heat capacity rate C_{\min} is the smaller of the two fluid streams' capacities, while the capacity ratio C_r = C_{\min}/C_{\max} influences the overall performance. Correctly identifying C_{\min} is essential because it normalizes the number of transfer units as \mathrm{NTU} = UA / C_{\min}, ensuring the effectiveness \epsilon accurately reflects the exchanger's ability to approach the maximum possible . Variable fluid properties, particularly temperature-dependent c_p, can significantly alter C_r and thereby shift the \epsilon-NTU relationships. For gases and liquids with substantial c_p variation, the assumption of constant c_p leads to distortions in predicted , especially in unbalanced flows (C_r < 1) or high-NTU designs. Modern approaches adjust by employing average values like the harmonic mean c_p for balanced counterflow cases, which minimizes deviations, though significant errors can persist in unbalanced, high-NTU scenarios without such corrections. The foundational developments of the NTU method in the 1950s by Kays and London assumed constant c_p to simplify derivations for compact heat exchangers, primarily involving gases like air. Subsequent refinements in the 1980s and beyond incorporated variable properties for more accurate modeling of liquids and cryogenic gases, using numerical methods or mean-property approximations to refine C_{\min} and C_r. Misdefining C_{\min}, such as by erroneously selecting the larger capacity rate, can result in substantial errors in exchanger sizing due to incorrect NTU values and estimates. This is particularly critical in high-performance designs where pinch points from variable c_p amplify discrepancies. Accurate property evaluation at mean temperatures or via iterative methods is thus vital to avoid overdesign.

Multi-Pass and Complex Flow Arrangements

In multi-pass counterflow heat exchangers, such as those with multiple shell passes and an even number of tube passes (e.g., 2-4 or 1-2 configurations), the overall effectiveness \varepsilon is determined by treating the exchanger as a series of single-pass units. The effectiveness of each shell pass, denoted as p, is first calculated using standard \varepsilon-NTU relations for a single counterflow pass based on the NTU and capacity ratio C = C_{\min}/C_{\max} for that pass. The overall effectiveness for n shell passes is then given by \varepsilon = \frac{ \left[ \frac{1 - p C}{1 - p} \right]^{n} - 1 }{ \left[ \frac{1 - p C}{1 - p} \right]^{n} - C }, where p is the single-pass effectiveness. For the special case where C = 1, this simplifies to \varepsilon = n p / [1 + (n-1) p]. The total number of transfer units is the sum of the individual pass NTUs, NTU_{\text{total}} = \sum NTU_i, with each NTU_i = U_i A_i / C_{\min}, assuming uniform distribution across passes unless specified otherwise. This approach allows iterative calculation of outlet temperatures by propagating fluid states through each pass sequentially. For complex flow arrangements, such as plate-fin heat exchangers with flow interruptions or non-ideal mixing, the NTU method employs segmental analysis where the exchanger is divided into smaller elements with local NTU values. Correction factors derived from Tubular Exchanger Manufacturers Association (TEMA) standards adjust for deviations from ideal counterflow in shell-and-tube designs, particularly for multipass configurations like 1-2n or 2-4n passes, by modifying the effective NTU or effectiveness to account for crossflow components and baffle-induced mixing. In plate-fin exchangers with interruptions (e.g., offset strip fins), empirical correlations from experimental data provide segmental NTU corrections, enhancing accuracy for hybrid flows where pure analytical solutions are unavailable. These methods prioritize low-NTU regimes for optimization, as arrangements become less influential at higher NTU. When analytical \varepsilon-NTU relations are unavailable for non-standard geometries, numerical methods integrate the NTU framework with discretization techniques. Finite difference methods solve the governing energy balance equations across segmented control volumes, computing local temperature profiles to derive an overall NTU and effectiveness. For highly irregular flows, computational fluid dynamics (CFD) simulations couple convection-diffusion equations with turbulence models to predict velocity and temperature fields, from which effective UA values are extracted to form NTU = UA / C_{\text{min}}, enabling \varepsilon evaluation via post-processing. These approaches are essential for custom designs like microchannel or interrupted-surface exchangers, where software tools automate the integration. A key limitation in applying the NTU method to multi-pass and complex arrangements is that for NTU > 5, the effectiveness \varepsilon approaches 1 asymptotically, rendering flow arrangement details negligible as the exchanger size dominates performance. Thus, optimization efforts focus on low-NTU regimes (NTU < 2), where configuration impacts \varepsilon significantly, guiding selections for compact or high-recovery applications.

References

  1. [1]
    E-NTU Heat Transfer - MATLAB - MathWorks
    The E-NTU Heat Transfer block models the heat exchange between two general fluids based on the standard Effectiveness-NTU method.Description · Ports · Parameters
  2. [2]
    [PDF] Compact heat exchangers | Semantic Scholar
    Compact heat exchangers · W. Kays, A. London, E. Eckert · Published 1 June 1960 · Engineering, Materials Science · Journal of Applied Mechanics.
  3. [3]
    [PDF] Heat Exchangers - Effectiveness-NTU Method - MSubbu
    Sep 25, 2019 · In order to use this method we need three new definitions: 1. Thermal Capacity Ratio (C):. The thermal capacity of a fluid stream is the ...<|control11|><|separator|>
  4. [4]
    Temperature Effectiveness - an overview | ScienceDirect Topics
    The heat exchanger temperature effectiveness, or simply the effectiveness, ε, is the ratio of actual heat transfer to the maximum possible heat transfer.
  5. [5]
    [PDF] Heat Exchangers: Theory and Selection
    This procedure must be repeated until convergence. A more convenient procedure has been devised, called the Effectiveness-NTU method. To explain this method, a.
  6. [6]
    [PDF] Heat Exchanger Analysis: Design and Performance
    • Here 𝑁𝑇𝑈 (number of transfer units) is a dimensionless parameter given by: ... - Log mean temperature difference. - Effectiveness – NTU method. • Lastly ...
  7. [7]
    [PDF] Heat Exchanger Effectiveness (NTU method)
    Another approach introduce the definition of heat exchanger effectiveness (Є), which is a dimensionless with ranging between 0 to1. Є max q qact. = Where, qmax ...
  8. [8]
    None
    ### Summary of LMTD Correction Factors and ε-NTU Relations
  9. [9]
    KLa Determination Using the Effectiveness-NTU Method - MDPI
    ... NTU method, which is usually applied to heat exchanger design, was adapted to gas–liquid countercurrent absorbers to determine the overall mass transfer ...
  10. [10]
  11. [11]
    Practical effectiveness-NTU model for cooling and dehumidifying ...
    Aug 9, 2025 · As mentioned above, a novel simplified ε-NTU method of counter-flow wet cooling coils based on the enthalpy method is presented by knowing the ...
  12. [12]
    Coils: Engineering Reference — EnergyPlus 8.9 - Big Ladder Software
    ... bypass factor (BF) approach. This approach is analogous to the NTU-effectiveness calculations used for sensible-only heat exchanger calculations, extended ...
  13. [13]
    Practical effectiveness-NTU model for cooling and dehumidifying ...
    May 5, 2016 · Effectiveness-NTU method is considered as a work horse of the simplified approach. ... dehumidification process occurring inside the cooling coil ...
  14. [14]
    [PDF] EXPERIMENTAL AND THEORETICAL STUDY OF ADIABATIC ...
    The results show that humidifier effectiveness can be calculated with an uncertainty of ±2.9% and the average difference between simulated and measured air ...
  15. [15]
    [PDF] experimental and theoretical study of adiabatic humidification in ...
    In this work, effectiveness is estimated for two different adiabatic humidifiers: wetted media and water centrifugal atomizer. The wetted media humidifier ( ...
  16. [16]
  17. [17]
    Thermal Performance of Multipass Parallel and Counter-Cross-Flow ...
    Very accurate results have been obtained over wide ranges of NTU (number of transfer units) and C * (heat capacity rate ratio) values. New effectiveness data ...Introduction · Validation of the Algorithm · Other Geometries and Flow...
  18. [18]
    A comprehensive numerical study on heat transfer and friction ...
    Nov 1, 2024 · Each numerical experiment is carried out by CFD analysis of a periodic fin geometry. ... NTU method assuming uniform heat transfer coefficients.