Static synchronous compensator

A static synchronous compensator (STATCOM) is a shunt-connected, reactive compensation device belonging to the Flexible AC Transmission Systems (FACTS) family, used in electrical power transmission and distribution networks to dynamically provide or absorb reactive power for voltage regulation at the point of connection. It operates as a solid-state, self-commutating voltage source converter (VSC) that emulates an ideal synchronous voltage source, injecting or absorbing reactive current without relying on rotating machinery, thereby enhancing grid stability and power quality under varying load conditions. The primary components of a STATCOM include a multi-level VSC employing insulated-gate bipolar transistors (IGBTs) or gate turn-off thyristors (GTOs) to generate a controllable AC voltage, connected via phase reactors to filter harmonics and a step-up transformer for interfacing with the high-voltage grid. This setup enables rapid response times—typically within one electrical cycle—and maintains reactive power capability even at low system voltages (down to 0.15 per unit), offering superior performance over conventional static VAR compensators (SVC) through reduced size (less than 50% of equivalent SVC footprint), elimination of passive capacitor and reactor banks, and enhanced dynamic control via pulse-width modulation (PWM) techniques. STATCOM technology originated in the early 1980s as part of efforts to improve power system controllability, with the first prototype—a 77 kV, 20 MVA unit—developed in 1980 by Mitsubishi Electric Corporation and Kansai Electric Power Company in Japan. The inaugural operational STATCOM, initially termed an Advanced Static VAR Compensator (ASVC) with a capacity of ±1 Mvar using GTO-based six-pulse bridges, was commissioned in October 1986 by the Electric Power Research Institute (EPRI) and Westinghouse Electric Corporation. Key early demonstrations include a ±80 Mvar installation in Japan in 1991 and a ±100 Mvar unit at the Sullivan Substation in Tennessee in 1995 by EPRI and the Tennessee Valley Authority (TVA), which validated its role in voltage support and oscillation damping. In modern applications, STATCOMs, including those with grid-forming control, are deployed for reactive power compensation, power factor correction, fault ride-through enhancement, and facilitating renewable energy integration by providing synthetic inertia, with notable examples including a ±300 Mvar, 420 kV system commissioned by Amprion in Germany in 2023 and a ±150 Mvar unit by ELES in Slovenia in 2022.

Introduction and Fundamentals

Definition and Role in Power Systems

A static synchronous compensator (STATCOM) is a shunt-connected, static reactive power compensation device that utilizes voltage source converters (VSCs) to dynamically generate or absorb reactive power in alternating current (AC) power systems. As a key member of the Flexible AC Transmission Systems (FACTS) family, the STATCOM operates without rotating parts, relying on power electronics to emulate a synchronous voltage source at the point of connection. This enables precise control of reactive power flow, independent of the system's voltage magnitude and phase angle, distinguishing it from traditional compensators like capacitors or inductors. In power systems, the STATCOM plays a critical role in voltage regulation by injecting or absorbing vars to maintain bus voltages within acceptable limits, thereby improving power factor and reducing losses. It enhances overall grid stability by damping power oscillations and supporting transient stability during faults, allowing for increased power transfer capacity on transmission lines without the need for additional infrastructure. As a FACTS device, the STATCOM facilitates the integration of renewable energy sources by providing dynamic support for voltage fluctuations and low-voltage ride-through capabilities. The STATCOM is typically connected in shunt configuration to the AC bus, either directly for low-voltage applications or through a coupling transformer to interface with high-voltage transmission networks. This transformer, often a step-down type, isolates the VSC from the grid and matches impedance levels, ensuring safe and efficient power exchange. One of the STATCOM's primary advantages is its fast response time, typically achieving full reactive power adjustment within 1-2 cycles of the system frequency, which is essential for real-time grid control. Additionally, it maintains effective operation over a wide voltage range, delivering rated reactive current even at system voltages as low as 0.2 per unit (pu), outperforming conventional static var compensators (SVCs) in weak grid conditions.

Basic Operating Principles

The static synchronous compensator (STATCOM) functions by emulating the behavior of a rotating synchronous condenser through the use of a voltage source converter (VSC), which generates a controllable alternating current (AC) voltage behind a coupling reactance. This VSC, typically based on insulated gate bipolar transistors (IGBTs) or similar force-commutated devices, produces a three-phase AC output voltage whose magnitude and phase angle can be precisely adjusted relative to the connected power system bus. Unlike traditional synchronous machines, the STATCOM achieves this electronically without moving parts, enabling rapid response times on the order of milliseconds. The mode of operation—inductive or capacitive—is determined by the differences in magnitude and phase angle between the STATCOM's output voltage (denoted as V_2) and the system bus voltage (denoted as V_1). In capacitive mode, the STATCOM injects reactive power into the system when V_2 > V_1, effectively behaving as a current source leading the bus voltage. Conversely, in inductive mode, it absorbs reactive power when V_2 < V_1, lagging the bus voltage. The coupling reactance between the VSC and the bus facilitates this reactive power exchange without significant active power transfer under steady-state conditions, where the phase angle difference is minimized to near zero except for minor losses. STATCOMs offer a wide dynamic range, capable of operating from full capacitive output (up to +1.0 per unit, pu) to full inductive output (down to -1.0 pu) based on the converter's rated capacity, providing symmetrical reactive power compensation regardless of system voltage variations. This range is particularly advantageous at low voltages, where the device can maintain near-rated capacitive output down to approximately 0.15 pu system voltage. Additionally, STATCOMs feature transient overload capabilities, allowing up to 3.0 pu output for short durations (typically seconds) to support fault ride-through and dynamic stability. To enable coordinated voltage control in multi-device power systems, STATCOMs incorporate a regulation slope, or droop characteristic, typically set between 2% and 10%, which defines the intentional voltage deviation per unit of reactive power output. This droop, represented in the V-I characteristic as a linear slope (e.g., V = V_{\text{ref}} + X_s I_q, where X_s is the slope reactance in pu), prevents hunting between compensators and ensures stable sharing of reactive power load. The slope value is adjustable, with lower percentages (e.g., 2%) providing tighter voltage regulation at the expense of reduced sharing range.

Historical Development

Early Concepts and Precursors

The transmission of electrical energy using alternating current (AC) began at the end of the 19th century, replacing smaller direct current (DC) distribution systems and necessitating solutions for reactive power management to maintain voltage stability and power factor in expanding grids. Early reactive power compensation relied on mechanical and rotating devices, with synchronous condensers emerging as a key solution in the early 20th century; these overexcited synchronous motors, often repurposed from existing generators, provided dynamic reactive power support by absorbing or supplying vars without mechanical load. By the 1920s and 1930s, synchronous condensers were widely installed in high-voltage transmission networks to mitigate voltage fluctuations and enhance system stability, particularly in long-distance lines. The development of static compensation technologies advanced in the early 20th century with the invention of mercury-arc valves by Peter Cooper Hewitt in 1902, which enabled high-power rectification and inversion for industrial applications. These glass-enclosed valves, using mercury vapor conduction, facilitated early converter-based systems for DC power but were adapted for reactive power control in the mid-1960s through DC-controlled reactors, marking the first static compensation devices without rotating parts. Although effective for basic var absorption, mercury-arc systems suffered from slow response times, high maintenance due to bulb fragility, and limited scalability, prompting further innovation in semiconductor-based alternatives. The mid-20th century saw the introduction of thyristor technology, invented in 1957, which revolutionized static compensation by enabling precise control without mechanical switching. Thyristor-controlled reactors (TCRs) and thyristor-switched capacitors (TSCs), first demonstrated in the late 1960s, formed the basis of Static VAR Compensators (SVCs), with the initial commercial TSC installation by ASEA in 1971 and the first full SVC deployed in Nebraska in 1977. These line-commutated devices provided faster reactive power response—on the order of cycles—compared to synchronous condensers, reducing losses and maintenance while supporting voltage regulation in transmission systems. Despite these advances, line-commutated devices like SVCs had inherent limitations that highlighted the need for voltage-sourced alternatives, including dependence on sufficient AC system voltage for thyristor commutation, resulting in reduced reactive power capability below 0.5-0.6 per unit voltage and potential instability in weak grids. Additionally, they generated significant harmonics requiring tuned filters, exhibited a sloped voltage-current characteristic that limited precise control, and lacked the ability to exchange active power or operate independently of grid conditions. These constraints, particularly in dynamic fault scenarios, underscored the transition toward self-commutated converter technologies in the late 20th century.

Key Milestones and First Installations

The conceptualization of the static synchronous compensator (STATCOM) emerged in the early 1980s as part of efforts to advance voltage source converter-based reactive power control. The first prototype—a 20 MVar unit using force-commutated thyristor inverters—was developed in 1980 by Mitsubishi Electric Corporation and Kansai Electric Power Company (KEPCO) in Japan. In October 1986, the inaugural operational STATCOM, initially termed an Advanced Static VAR Compensator (ASVC) with a capacity of ±1 MVar using GTO-based six-pulse bridges, was commissioned by the Electric Power Research Institute (EPRI) and Westinghouse Electric Corporation. In 1987, Westinghouse Electric Corporation developed a 1 MVAr prototype unit under the Empire State Electric Energy Research Corporation (ESEERCO) program titled "1 MVAR Advanced Static VAR Generator Development Program." This prototype validated the use of gate turn-off (GTO) thyristor inverters for shunt compensation, laying the groundwork for commercial applications in power systems. The first commercial STATCOM, rated at ±80 MVAr and utilizing GTO-based technology, was commissioned in 1991 at Mitsubishi Electric's Inuyama substation in Japan. A key demonstration followed with a ±100 MVAr unit commissioned in November 1995 at the Tennessee Valley Authority's (TVA) Sullivan substation in Johnson City, Tennessee. Connected to the 161 kV bus, this installation demonstrated STATCOM's effectiveness in regulating voltage and enhancing transmission capacity in a high-load area. However, the unit was retired after approximately 18 years of service due to the obsolescence of its GTO components, which were superseded by more efficient insulated-gate bipolar transistor (IGBT) and modular multilevel converter technologies. Throughout the 1990s and 2000s, STATCOM deployments scaled up significantly, transitioning from prototypes to integral components of flexible AC transmission systems (FACTS). Key examples include the ±80 MVAr installation at Japan's Inuyama substation in 1991, the world's first commercial unit, and larger systems like the ±320 MVAr device at Nanjing West substation in China in 2006. These advancements facilitated the standardization of STATCOM within FACTS frameworks, with IEEE Std 1031-2011 providing guidelines for electric power systems and CIGRE working groups defining performance specifications. Post-2020 developments have emphasized hybrid STATCOM designs to address grid modernization challenges, such as integrating renewables and enhancing inertia. A notable example is the 2020 installation by Hitachi Energy for TenneT in Borken, Germany—the world's first hybrid STATCOM combining a ±150 MVAr voltage source converter with synchronous condensers to deliver both reactive power and short-circuit strength, supporting the transmission of offshore wind energy southward. These hybrids extend STATCOM capabilities beyond pure reactive compensation, enabling active power modulation and fault ride-through in low-inertia grids.

Theoretical Foundations

Mathematical Modeling

The phasor model of a static synchronous compensator (STATCOM) represents it as a controllable sinusoidal voltage source V_c \angle \delta connected in shunt to the power system bus voltage V_s \angle 0 through a coupling reactance X, typically the leakage reactance of the interface transformer and any filters. This model is fundamental for steady-state analysis in power system stability studies, where the STATCOM emulates a synchronous voltage source to exchange reactive power dynamically. The magnitude |V_c| is regulated by modulating the voltage-source converter (VSC) output, while the phase angle \delta is controlled to minimize active power exchange. The reactive power Q injected by the STATCOM into the system is derived from the phasor diagram and given by Q = \frac{V_s (V_c \cos \delta - V_s)}{X}, where V_s and V_c are the magnitudes of the system and STATCOM voltages, respectively, and \delta is the phase angle between them. This equation shows that Q > 0 when V_c \cos \delta > V_s, corresponding to capacitive operation where the STATCOM supplies reactive power to support the bus voltage. Conversely, for V_c \cos \delta < V_s, Q < 0, indicating inductive operation absorbing reactive power. The active power P exchanged between the STATCOM and the system is P = \frac{V_s V_c \sin \delta}{X}. In steady-state operation, control algorithms ensure the average P \approx 0 by synchronizing \delta to the system phase via a phase-locked loop, preventing net DC-side energy drain except during transients or intentional active power support. This decoupling allows the STATCOM to focus primarily on reactive power compensation without significant real power involvement. For dynamic simulations, such as electromagnetic transient studies, the STATCOM is modeled using the d-q (direct-quadrature) transformation to convert three-phase quantities into a synchronously rotating reference frame aligned with the system voltage. This transformation simplifies the analysis by eliminating time-varying inductances and enabling decoupled control of active and reactive currents. The Park's transformation matrix is applied to voltages and currents as \begin{bmatrix} v_d \\ v_q \\ v_0 \end{bmatrix} = \frac{2}{3} \begin{bmatrix} 1 & -\frac{1}{2} & -\frac{1}{2} \\ 0 & \frac{\sqrt{3}}{2} & -\frac{\sqrt{3}}{2} \\ \frac{1}{2} & \frac{1}{2} & \frac{1}{2} \end{bmatrix} \begin{bmatrix} v_a \\ v_b \\ v_c \end{bmatrix}, with similar for currents, where the zero-sequence component is typically neglected in balanced systems. In the d-q frame, the STATCOM dynamics, including the coupling inductor, are described by the voltage equations v_{sd} = R i_{cd} + L \frac{di_{cd}}{dt} - \omega L i_{cq} + e_{cd}, v_{sq} = R i_{cq} + L \frac{di_{cq}}{dt} + \omega L i_{cd} + e_{cq}, where v_{s(d,q)} are the system voltages, i_{c(d,q)} are the STATCOM currents, e_{c(d,q)} are the VSC output voltages, R and L are the resistance and inductance of the coupling elements, and \omega is the fundamental angular frequency. The DC-link voltage dynamics are coupled via P = \frac{3}{2} (v_{sd} i_{cd} + v_{sq} i_{cq}), ensuring energy balance. These equations form the basis for state-space representations used in control design and simulation tools.

Reactive Power Control Mechanism

The reactive power control in a static synchronous compensator (STATCOM) is achieved primarily by regulating the magnitude of its internal voltage V_c relative to the connecting bus voltage V_s. When V_c \cos \delta > V_s, the STATCOM injects reactive into the in capacitive , supporting voltage and . In , when V_c \cos \delta < V_s, it absorbs reactive in inductive , helping to suppress overvoltages. This magnitude adjustment is facilitated through the voltage source converter, which draws from a DC capacitor to synthesize the AC output. The phase angle \delta between V_c and V_s also influences power flow, with small variations in \delta enabling fine-tuned control of active power exchange to maintain DC link voltage while prioritizing reactive support. To generate the desired V_c waveform, pulse-width modulation (PWM) or similar techniques are applied to the converter switches, producing a near-sinusoidal output that minimizes distortion and ensures efficient reactive power delivery. Building on the core phasor-based power equations, these controls translate theoretical models into practical injection or absorption of reactive power. Voltage regulation in STATCOM operation incorporates a slope regulation characteristic, or droop control, expressed as V = V_{ref} - \frac{Q}{S_{rated}} \times m, where V_{ref} is the reference voltage, Q is the reactive power (positive for capacitive injection), S_{rated} is the rated apparent power, and m is the droop slope (typically 2-5%). This droop mechanism, often set around 3% for coordination with other grid devices, allows the STATCOM to share reactive compensation duties without causing oscillations or instability during voltage deviations. Harmonic mitigation in STATCOM reactive power control is enhanced through multilevel converter operation, which generates multilevel voltage steps that closely approximate a sine wave, thereby reducing low-order harmonics and lessening the reliance on external filters. This qualitative improvement in waveform quality supports cleaner reactive power exchange and better overall system performance.

Voltage Source Converter Topologies

Two-Level Converters

The two-level converter represents the foundational voltage source converter (VSC) topology employed in early static synchronous compensators (STATCOMs), consisting of a six-switch bridge configuration connected to a DC-link capacitor that serves as the energy storage element. This bridge utilizes insulated gate bipolar transistors (IGBTs) or similar self-commutated switches to generate a bipolar output voltage waveform, with pulse-width modulation (PWM) techniques applied to shape the AC output for reactive power injection. The DC capacitor maintains a constant voltage, enabling the converter to act as a synchronous voltage source synchronized to the grid. This topology offers a simple design with fewer components, making it economical for implementations with small power ratings, typically below several megavars. Its straightforward architecture facilitates easier manufacturing and maintenance compared to more complex alternatives, contributing to its adoption in initial developments. However, the two-level structure incurs high switching losses due to the frequent PWM operations required at elevated frequencies to approximate sinusoidal output, limiting efficiency in higher-power scenarios. Additionally, it produces significant harmonic distortion in the output current, necessitating large filtering components such as transformers and passive filters to meet grid standards. Two-level converters found primary application in STATCOM prototypes and low-power systems during the 1990s, serving as proof-of-concept devices for reactive power compensation in transmission networks before the shift to advanced topologies. Their use declined with the demand for higher ratings and improved performance in the early 2000s.

Three-Level Converters

The three-level converter topology employed in static synchronous compensators (STATCOMs) utilizes the neutral-point-clamped (NPC) inverter structure, featuring a split DC link with two series-connected capacitors that each hold half the total DC voltage (Vdc/2). Each phase leg of the inverter comprises four switching devices, typically insulated-gate bipolar transistors (IGBTs), along with two clamping diodes connected to the neutral point between the capacitors. This configuration generates three distinct output voltage levels per phase—+Vdc/2, 0, and -Vdc/2—enabling multilevel pulse-width modulation (PWM) operation. This topology provides several key advantages over simpler two-level converters, primarily through improved waveform synthesis with more voltage steps, which approximates the desired sinusoidal output more closely. Consequently, total harmonic distortion (THD) in the output voltage is significantly reduced, often by 40-50% compared to two-level designs; for instance, THD values can drop from approximately 31% to 17% under similar operating conditions. Additionally, the voltage stress across each switching device is limited to Vdc/2, reducing thermal and electrical stress, while allowing lower switching frequencies (e.g., a 68% reduction from 26.5 kHz to 8.5 kHz) to achieve equivalent current THD levels, thereby improving efficiency and minimizing filtering requirements. Despite these benefits, the three-level NPC design incurs disadvantages, including a higher component count—four switches and two diodes per phase versus two switches in two-level topologies—which increases complexity, cost, and potential failure points. A notable challenge is the tendency for voltage imbalance across the split DC-link capacitors, arising from uneven charging/discharging due to load conditions or switching losses, which can lead to output waveform distortion if not actively managed through control strategies; this often necessitates larger capacitor sizes to maintain balance. In practical applications, three-level NPC converters found prominence in medium-voltage STATCOM installations during the mid-2000s, particularly for reactive power compensation in transmission networks. A representative example is a ±36 MVA IGBT-based three-level NPC STATCOM deployed around 2008 as a back-to-back inter-tie between the Texas and Mexico grids, demonstrating effective voltage regulation and dynamic support in high-power scenarios.

Modular Multilevel Converters

The modular multilevel converter (MMC) topology for static synchronous compensators consists of six arms, each formed by a series connection of numerous submodules, typically half-bridge or full-bridge configurations, containing insulated-gate bipolar transistors (IGBTs) or integrated gate-commutated thyristors (IGCTs) and DC-link capacitors. This structure enables the generation of multilevel output voltages with hundreds of levels, allowing direct connection to high-voltage grids without step-up transformers in many cases. The half-bridge submodule, using two switches per unit, provides unipolar output, while the full-bridge variant, with four switches, supports bipolar operation for enhanced fault-blocking capabilities. Key advantages of MMC in STATCOM applications include its scalability for high-voltage operations, producing near-sinusoidal waveforms through low-switching-frequency modulation rather than high-frequency pulse-width modulation, resulting in total harmonic distortion (THD) below 5% and eliminating the need for large output filters. The distributed capacitor arrangement provides inherent fault tolerance via submodule redundancy, where faulty units can be bypassed without disrupting operation, and reduces footprint by minimizing passive components. Additionally, the modular design facilitates easier maintenance and integration with energy storage systems for hybrid functionalities. Despite these benefits, MMC topologies face challenges such as the requirement for a large number of submodules—often exceeding 100 per arm for high-voltage ratings—which increases system complexity and initial costs due to the higher component count. Circulating currents between arms must be actively managed to prevent efficiency losses and overheating, adding to design overhead. Furthermore, the need for precise capacitor voltage balancing across submodules demands sophisticated monitoring, potentially elevating operational expenses. Adoption of MMC-based STATCOMs accelerated post-2010, following the topology's conceptualization in the early 2000s by researchers like R. Marquardt, with initial commercial deployments in high-voltage applications around 2010–2012, such as ABB's SVC Light MMC systems for grid stabilization. By the mid-2010s, they became dominant for voltages above 100 kV, including hybrid configurations integrating battery storage for enhanced reactive power support and renewables integration, with installations exceeding hundreds of megavars in global transmission networks.

Operation and Control

Operational Modes

The static synchronous compensator (STATCOM) operates in distinct modes to address varying grid requirements, enabling flexible reactive power management for voltage stability and power quality enhancement. These modes allow the device to respond dynamically to normal, steady-state, and disturbance conditions without mechanical components, leveraging voltage source converter technology for rapid adjustments. In VAR control mode, the STATCOM delivers a constant reactive power output at its rated capacity, functioning independently of the connected bus voltage. This mode treats the STATCOM as a controllable current source, injecting or absorbing a fixed amount of reactive power (Q) to meet specified demands, such as maintaining power factor or compensating for predictable loads. It is particularly useful when the grid voltage remains within acceptable limits, ensuring consistent performance up to the device's thermal and current limits set by components like IGBTs. Voltage regulation mode enables the STATCOM to adjust reactive power output based on deviations in the bus voltage from a reference value, promoting grid stability through proportional response. In this mode, the device employs a droop characteristic—typically 1% to 4% at maximum reactive power—to coordinate with multiple compensators and avoid hunting or overcorrection. If the voltage falls below a threshold, the STATCOM increases capacitive reactive power injection; conversely, it absorbs inductive reactive power during overvoltages, thereby supporting coordinated operation in interconnected systems. During transient events such as faults, the STATCOM shifts to transient mode, utilizing its overload capability to provide temporary boosts in reactive current for fault ride-through support. This allows output up to 1.5 to 3.0 per unit (pu) of rated capacity for durations of 100 to 500 milliseconds, helping to mitigate voltage dips and enhance system inertia without interrupting operation. Manufacturers like ABB specify overloads up to % in application-specific designs, enabling sub-cycle response times for dynamic voltage recovery during balanced or unbalanced faults. In idle mode, the STATCOM maintains zero reactive power exchange with the grid, minimizing conduction and switching losses while remaining synchronized and ready for activation. This neutral state occurs during periods of balanced supply and demand, with the device drawing only minimal active power for its internal controls and cooling systems, ensuring energy efficiency in low-demand scenarios.

Control Strategies and Algorithms

The control of a static synchronous compensator (STATCOM) relies on a hierarchical structure to achieve precise regulation of reactive power and voltage support. The inner loop focuses on current regulation in the d-q synchronous reference frame, employing proportional-integral (PI) controllers for the d-axis (active power) and q-axis (reactive power) components to ensure fast tracking of reference currents with minimal steady-state error. This decoupled control in the rotating frame transforms the AC-side variables into DC quantities, simplifying the PI tuning and enhancing dynamic response during transients. The outer loop, operating at a slower timescale, generates the current references for the inner loop by regulating either the DC-link voltage to maintain capacitor balance or the reactive power output to meet grid requirements, often using additional PI regulators. Modulation techniques are integral to the control algorithms, converting the regulated reference signals into gate pulses for the converter switches. For two-level and three-level voltage source converters, sinusoidal pulse width modulation (SPWM) is widely adopted, where high-frequency carrier signals compare against sinusoidal references to produce pulses that minimize harmonic distortion while operating at moderate switching frequencies up to several kHz. In contrast, modular multilevel converters (MMCs) utilize nearest-level modulation (NLM), which selects the closest discrete voltage level from the available submodules to approximate the reference waveform, reducing switching losses and computational complexity in high-voltage applications exceeding 100 kV. These techniques ensure efficient power conversion and are tuned to balance harmonic suppression with device stress. Advanced features enhance the robustness of STATCOM control under non-ideal conditions. Adaptive algorithms for harmonic mitigation, such as adaptive model predictive control, dynamically adjust switching patterns based on real-time load harmonics, achieving total harmonic distortion reductions below 5% even with nonlinear loads like variable frequency drives. Fault detection integrates into the current control loop via modified regulators that monitor IGBT currents and voltages, synthesizing diagnostic signals to isolate faulty switches within milliseconds and enabling fault-tolerant operation without full system shutdown. Virtual inertia emulation employs synchronverter-based algorithms, where the control mimics the swing equation of synchronous machines by incorporating virtual rotor dynamics into the power reference, providing frequency support equivalent to 1-10% of system inertia during disturbances. These features collectively improve grid reliability in low-inertia environments. Recent developments since 2022 have incorporated artificial intelligence for predictive control, particularly to facilitate STATCOM integration with renewables. AI-based approaches, such as reinforcement learning-augmented control, forecast wind or solar variability using historical data and adjust reactive power preemptively, significantly improving voltage stability in hybrid grids. As of 2025, advancements include battery energy storage system (BESS)-integrated STATCOM designs that enhance transient stability and inertia provision through coordinated control strategies.

Applications

Transmission Network Support

Static synchronous compensators (STATCOMs) enhance the reliability of AC transmission networks by providing dynamic voltage support at the midpoint of long transmission lines, which helps maintain voltage profiles and increases power transfer capacity. In long lines, voltage drops can limit the maximum transferable power due to stability constraints; a midpoint STATCOM injects or absorbs reactive power to regulate the voltage magnitude, effectively extending the line's surge impedance loading and reducing angular separation across the line. Studies demonstrate that this placement can boost power transfer by up to 50% compared to uncompensated lines, depending on line length and loading conditions. STATCOMs also contribute to transmission network stability by damping power oscillations, including inter-area modes that arise from disturbances or heavy loading. Through dedicated power oscillation damping (POD) controllers, STATCOMs modulate reactive power output based on oscillation signals, such as line power or bus voltage deviations, to inject counteracting torques that accelerate damping. Eigenvalue analysis on standard test systems, like the IEEE 14-bus model, shows that STATCOM integration improves damping ratios from negative or low positive values to over 10%, preventing sustained oscillations and enhancing transient stability. Additionally, STATCOMs mitigate subsynchronous resonance (SSR) in series-compensated lines by providing auxiliary damping through voltage-sourced converter controls, such as PID or fuzzy logic schemes, which respond to torsional interactions between generators and line capacitors. Simulations indicate that STATCOMs can reduce SSR oscillation amplitudes by 70-90% within seconds, avoiding mechanical stress on turbine-generators. In fault scenarios, STATCOMs enable rapid recovery by injecting reactive power (VAR) during and immediately after contingencies, sustaining bus voltages and preventing cascading failures. Unlike slower mechanical devices, STATCOMs respond in less than one cycle, supplying capacitive VAR to counteract voltage dips caused by short circuits or line outages. Quantitative assessments reveal that a STATCOM can deliver up to 26 Mvar post-fault clearance, compared to 9 Mvar from equivalent alternatives, thereby shortening recovery time and improving low-voltage ride-through in the network. Practical installations illustrate these benefits in challenging transmission environments. For instance, in series-compensated lines like the 230 kV Porter line in the U.S., STATCOMs have been evaluated for SSR mitigation and voltage support to enable higher compensation levels without resonance risks. In weak grid regions, such as parts of Germany's transmission network, GE-supplied STATCOMs provide dynamic reactive compensation to stabilize voltages under low short-circuit conditions. Similarly, ABB installations in industrial transmission feeders connected to weak utilities demonstrate enhanced stability through midpoint compensation, reducing voltage fluctuations in extended lines.

Integration with Renewables and Modern Grids

Static synchronous compensators (STATCOMs) play a crucial role in supporting the integration of wind and solar farms by providing dynamic reactive power compensation, which enhances low-voltage ride-through (LVRT) capabilities and mitigates voltage flicker. In wind farms, STATCOMs inject or absorb reactive power rapidly during voltage sags, allowing turbines to remain connected to the grid and comply with stringent fault ride-through requirements, thereby increasing renewable penetration without compromising stability. For instance, STATCOMs have been shown to improve LVRT in doubly-fed induction generator (DFIG)-based wind energy conversion systems by dynamically adjusting reactive power output to counteract grid disturbances. Similarly, in solar photovoltaic (PV) installations, STATCOMs address flicker caused by intermittent cloud cover or rapid irradiance changes by stabilizing voltage at the point of common coupling, reducing flicker severity indices below grid code limits. This dynamic voltage support is essential for maintaining power quality in renewable-heavy networks, where traditional synchronous generation is absent. Hybrid STATCOM systems integrated with battery energy storage systems (BESS) extend functionality beyond reactive power to include active power injection and virtual inertia provision, particularly in microgrids with high renewable shares. These hybrids allow STATCOMs to discharge stored energy from batteries during frequency deviations, emulating the inertial response of conventional generators and damping rate-of-change-of-frequency (RoCoF) events. In islanded or weak microgrids, this capability enables seamless transition between grid-connected and standalone modes, supporting active power balancing amid variable solar or wind output. For example, STATCOM-BESS configurations have demonstrated improved frequency nadir and settling times by providing both reactive and active support, enhancing overall microgrid resilience. Such integrations are vital for distributed renewable systems, where inertia is inherently low to inverter-based resources. STATCOMs contribute to grid code compliance in renewable-dominated grids by offering fault current support and black-start capabilities, addressing limitations of inverter-based resources. During faults, STATCOMs can generate controlled fault currents up to 1.2-1.5 times their rated value, aiding protection schemes and voltage recovery without relying on grid inertia. For black-start, grid-forming STATCOM variants, often hybridized with BESS, initiate grid reformation by establishing voltage and frequency references post-blackout, enabling sequential reconnection of renewable assets. These features align with evolving grid codes, such as those from ENTSO-E and IRENA, which mandate such contributions for high-renewable scenarios to ensure system reliability. Post-2020 deployments in Europe and Asia highlight STATCOMs' role in 100% renewable scenarios, with installations tailored for offshore wind and large-scale solar integration. In Europe, Germany's Amprion network deployed a grid-forming STATCOM in 2023 at 420 kV, supporting voltage control for increasing wind penetration toward net-zero goals. Slovenia's ELES installed a 150 Mvar STATCOM in 2022 at Beričevo substation to bolster renewable interconnections. In December 2024, GE Vernova was awarded a contract by 50Hertz Transmission for four STATCOM units to enhance grid stability amid rising renewables in Germany. These examples demonstrate STATCOMs' scalability in facilitating ultra-high renewable grids, with projections for over 70 units in Germany by 2030.

Comparisons with Other Compensation Devices

STATCOM versus SVC

The static synchronous compensator (STATCOM) represents an advancement over the static VAR compensator (SVC), its thyristor-based predecessor developed in the 1970s for reactive power compensation in AC transmission systems. While both devices provide dynamic voltage support, STATCOM employs voltage-source converter (VSC) technology using self-commutated switches like IGBTs, enabling superior performance in transient conditions compared to SVC's reliance on thyristor-controlled reactors (TCRs) and thyristor-switched capacitors (TSCs). A key distinction lies in response time, where STATCOM achieves reactive power adjustment in less than 2 cycles (approximately 33 ms at 60 Hz), allowing rapid mitigation of voltage fluctuations and grid instabilities. In contrast, SVC typically requires 2-3 cycles (around 50 ms at 60 Hz) for full response due to the slower firing control of thyristors in TCRs, limiting its effectiveness in ultra-fast transient events. STATCOM maintains effective operation across a wider voltage range, delivering full reactive power capability down to 0.2-0.3 per unit (pu) system voltage, which is critical for fault ride-through and low-voltage scenarios in modern grids. SVC, however, experiences significant capability degradation below 0.6 pu, as its capacitor banks cannot be easily switched out without risking overvoltages upon recovery, often necessitating protective varistors that add complexity. In terms of physical footprint and efficiency, STATCOM offers a more compact design, occupying up to 50% less space than an equivalent SVC due to the absence of large passive components like harmonic filters and varistors, while achieving higher efficiency with losses typically under 1% compared to SVC's 2-5% from thyristor conduction and filtering. However, the initial capital cost for a basic STATCOM unit is higher, around $150/kVAR versus $100/kVAR for SVC, though lifecycle savings from reduced maintenance and enhanced functionality often offset this. Regarding operational capability, STATCOM provides a full symmetric reactive power range (inductive and capacitive) without asymmetry, maintaining consistent performance even at low voltages for applications like flicker mitigation and oscillation damping. SVC's range is inherently asymmetric, with stronger capacitive support but limited inductive output at depressed voltages, constraining its use in unbalanced or weak grid conditions.
AspectSTATCOMSVC
Response Time1-2 cycles (<33 ms at 60 Hz)2-3 cycles (~50 ms at 60 Hz)
Voltage RangeEffective down to 0.2-0.3 puLimited below 0.6 pu
FootprintSmaller (no large filters/varistors)Larger due to passive components
Efficiency/LossesHigher efficiency (<1% losses)Lower (2-5% losses)
Cost ($/kVAR)~$150 (higher initial)~$100 (lower initial)
CapabilitySymmetric, full range at low voltageAsymmetric, limited at low voltage

STATCOM versus Synchronous Condensers

The static synchronous compensator (STATCOM) and synchronous condenser represent two distinct approaches to reactive power compensation in power systems, with the former relying on power electronics for static operation and the latter utilizing a rotating synchronous machine without prime mover input. While both devices can inject or absorb reactive power to support voltage stability, their fundamental differences in design lead to trade-offs in performance, particularly in dynamic response and ancillary services. In terms of response and control, STATCOM offers superior speed, achieving reactive power adjustments in milliseconds—typically within one to two electrical cycles (around 20-30 ms)—due to its voltage-source converter (VSC) technology and pulse-width modulation (PWM) control, enabling precise and continuous regulation independent of system voltage magnitude. In contrast, synchronous condensers exhibit slower response times, on the order of seconds, limited by the mechanical inertia of the rotor and the excitation system's dynamics, which require time to adjust field current for VAR output. Additionally, STATCOM inherently lacks rotational inertia, providing no natural frequency support unless augmented with virtual inertia control via its DC-link capacitor; synchronous condensers, however, deliver inherent inertia (inertia constant H ≈ 1-1.25 s) that aids in damping frequency fluctuations. Regarding maintenance and reliability, STATCOM benefits from a static design with no moving parts, resulting in lower upkeep costs, reduced downtime, and higher overall reliability in harsh environments, as it avoids mechanical wear, lubrication needs, and cooling system failures common in rotating machinery. Synchronous condensers, while proven over decades with robust construction, demand more frequent maintenance for bearings, windings, and auxiliary systems, potentially increasing operational expenses by 20-50% compared to electronic alternatives. On reliability, synchronous condensers excel in providing short-circuit capacity—contributing fault current up to 5-10 times rated current to bolster system strength— a feature absent in standard STATCOMs, which offer minimal fault contribution unless integrated with additional hardware. For cost and scalability, STATCOM installations typically range from $200,000 to $750,000 per MVAR, benefiting from modular multilevel converter (MMC) topologies that allow easy scaling to ratings exceeding 300 MVAR without proportional increases in footprint or complexity. Synchronous condensers, with capital costs of $400,000 to $900,000 per MVAR, may prove more economical for very high-power applications (>300 MVAR) due to their simpler large-scale construction and lower per-unit costs at utility scale, as seen in installations like ERCOT's 350 MVA units. However, STATCOM's compact design and lack of mechanical components often yield better lifecycle economics for medium-scale deployments. In modern grids dominated by renewables, synchronous condensers are increasingly deployed to restore lost inertia and short-circuit strength from retired thermal plants, enhancing frequency stability in low-inertia systems as highlighted in EPRI analyses of renewable integration challenges. STATCOM, conversely, excels in delivering precise, dynamic VAR support for voltage regulation during rapid fluctuations from intermittent sources, often complementing condensers in hybrid setups for comprehensive grid resilience.

References

  1. [1]
    Static Synchronous Compensator (STATCOM) - entso-e
    Mar 25, 2025 · A STATic synchronous COMpensator (STATCOM) is a fast-acting device capable of providing or absorbing reactive current and thereby regulating the voltage.
  2. [2]
    [PDF] Chapter 1. INTRODUCTION - University of Waterloo
    jointly by EPRI and the Westinghouse Electric Corp. A ± 320 MVA, 138 kV UPFC ... In 1986, the first. STATCOM, at the time called Advanced Static Var ...
  3. [3]
    Understanding FACTS: Concepts and Technology of Flexible AC ...
    Pioneers in FACTS and leading world experts in power electronics applications Narain G. Hingorani and Laszlo Gyugyi have teamed together to bring you the ...
  4. [4]
    Static Synchronous Compensators - an overview - ScienceDirect.com
    A Static Synchronous Compensator (STATCOM) is defined as a power electronic device that manages grid voltage by absorbing or providing reactive power.
  5. [5]
    STATCOM | Hitachi Energy
    STATCOM (static compensators) continuously provides variable reactive power in response to voltage variations, supporting the stability of the grid.
  6. [6]
  7. [7]
    [PDF] Static Synchronous Compensator (STATCOM) Solutions - GE Vernova
    The STATCOM generates or absorbs reactive power by producing a controlled voltage waveform. Basic Principles of Operation. The STATCOM system is shunt connected ...
  8. [8]
    [PDF] Smart Inverter PV-STATCOM for Effective Application of Solar ...
    It can provide dynamic reactive power compensation with a response time of 1-2 cycles, and can provide rated reactive current for voltages as low as 0.2 pu.
  9. [9]
    Static Synchronous Compensator (Phasor Type) - Simulink
    A STATCOM is a shunt device using power electronics to control power flow and improve transient stability by regulating voltage via reactive power.Missing: invention | Show results with:invention
  10. [10]
  11. [11]
    [PDF] Exclusive Technology Feature - How2Power.com
    Sep 11, 2015 · In 1985, Westinghouse installed a ±1-MVA-rated power electronics ... 1 MVAR Advanced Static VAR Generator Development Program, ESEERCO ...<|control11|><|separator|>
  12. [12]
    ABB pioneers new grid technology to support Germany's energy ...
    Jan 24, 2020 · ABB's Power Grids business has completed the installation of the world's first hybrid static compensator (STATCOM) to TenneT – a leading ...
  13. [13]
    None
    ### Summary of STATCOM Mathematical Model, Phasor Model, Power Equations, and d-q Transformation from https://www.ijeit.com/vol%202/Issue%205/IJEIT1412201211_31.pdf
  14. [14]
  15. [15]
    [PDF] VOLTAGE CONTROL AND DYNAMIC PERFORMANCE OF ... - IJAET
    This paper will discuss and demonstrate how STATCOM has successfully been applied to power system for effectively regulating system voltage. One of the major ...
  16. [16]
  17. [17]
    Development considerations of DSP-controlled PWM VSC-based ...
    The STATCOM is based on a conventional six-switch bi-directional voltage-source convertor topology using insulated gate bipolar transistors. The sinusoidal ...
  18. [18]
    [PDF] Development of Novel Power Electronic Topologies for the ...
    The advantages of the multi-level structure for the StatCom are [3]:. · elimination of the need for bulky transformers,. · reduction of the output harmonic ...
  19. [19]
    [PDF] A new STATCOM modular multilevel converter technology - ABB
    03 STATCOM converter topologies with output voltage waveforms together with corresponding fundamental frequency voltages. 03a Two-level VSC. 03b Three-level VSC ...
  20. [20]
    STATCOM Technology Evolution for Tomorrow's Grid - Nxtbook Media
    The MMC technology is an evolution from two- or three-level converters that were used widely in STATCOM applications in the 1990s and early 2000s. MMC ...
  21. [21]
    [PDF] Control of a Modular Multilevel Flying Capacitor Based STATCOM ...
    Following that, a 1 MVAR STATCOM using high power GTO inverters was developed by Westinghouse Electric Company [18]. Some other installations documented are ...
  22. [22]
    [PDF] A Statcom Based on Neutral Point Clamped Multi Level Inverter ...
    Despite its several advantages such as harmonic reduction, reduced stress across switching devices, and achieving high-voltage and high-power capabilities ...
  23. [23]
    [PDF] A Three-Level Inverter Based Static Compensator (STATCOM)
    Jul 3, 2018 · It can be seen from the table that the. THD has been reduced from 31.08 to 16.86, and this is achieved by maintaining the same average power ...
  24. [24]
    [PDF] Two-Level vs Three-Level Neutral-Point Clamped Inverters
    5.6 THD COMPARISON FOR TWO AND THREE-LEVEL INVERTERS. In order to have further reduced total harmonic distortion of line-to-line voltage especially in the ...
  25. [25]
  26. [26]
    A Comprehensive Review on Modular Multilevel Converters ... - MDPI
    The main disadvantages reside in the need for each submodule to require a DC-source. The cascaded transformer approach mitigates this problem, obtaining a ...
  27. [27]
  28. [28]
    A Review of Modular Multilevel Converters for Stationary Applications
    In 2010, this innovative converter was first commercially used by Siemens in San Francisco's Trans bay project [2]. Since its first introduction, the MMC ...
  29. [29]
  30. [30]
    STATCOM – Working Principle, Design and Application
    Feb 19, 2018 · STATCOM or Static Synchronous Compensator is a power electronic device using force commutated devices like IGBT, GTO etc. to control the reactive power flow.
  31. [31]
    [PDF] VArPro™ STATCOM Dynamic reactive power compensation - ABB
    In addition, the fast dynamic voltage control, which operates during balanced as well as unbalanced grid faults (fault ride through), allows the system to meet ...
  32. [32]
    D-STATCOM d-q Axis Current Reference Control Applying DDPG Algorithm in the Distribution System
    **Summary of D-STATCOM Control with d-q Axis and Inner Current Loop PI Controllers:**
  33. [33]
    A Comprehensive Review on STATCOM: Paradigm of Modeling, Control, Stability, Optimal Location, Integration, Application, and Installation
    Insufficient relevant content. The provided URL (https://ieeexplore.ieee.org/document/10366254) links to a general review paper on STATCOM, but the full text is not accessible here to extract specific sections on control strategies (e.g., hierarchical control, inner/outer loops, PI in d-q frame, SPWM, advanced algorithms for harmonics, fault detection, virtual inertia). Without access to the document, key details cannot be summarized.
  34. [34]
    Power Transfer Capability of Long Transmission Lines with Midpoint Sited FACTS and HVDC
    Insufficient relevant content. The provided URL (https://ieeexplore.ieee.org/document/4312185) points to a page titled "Power Transfer Capability of Long Transmission Lines with Midpoint Sited FACTS and HVDC," but no full text or detailed content is accessible for extraction and summarization based on the given input.
  35. [35]
    Mid-point siting of FACTS devices in transmission lines
    Insufficient relevant content. The provided URL (https://ieeexplore.ieee.org/document/634196) points to a page about "Mid-point siting of FACTS devices in transmission lines," but the content is not accessible or detailed enough to extract specific benefits of mid-point siting of STATCOM for voltage support and power transfer. No full text or specific data is available from the given link alone.
  36. [36]
    Request Rejected
    - **Status**: Insufficient relevant content.
  37. [37]
    Power Oscillation Damping By Utilizing PV-STATCOM
    Insufficient relevant content. The provided URL (https://ieeexplore.ieee.org/document/9753472) only contains a title and metadata without accessible full text or detailed information on how STATCOM damps power oscillations.
  38. [38]
    Mitigation of sub synchronous resonance using STATCOM controlled by PID and FL controllers
    Insufficient relevant content. The provided URL (https://ieeexplore.ieee.org/document/7115744) points to an IEEE Xplore page, but no full text or detailed content is accessible without a subscription or login. Thus, specific information on how STATCOM with fuzzy logic or PID mitigates subsynchronous resonance, including key results, cannot be extracted or summarized.
  39. [39]
    Mitigation of subsynchronous oscillations by 48-pulse VSC STATCOM using remote signal
    **Summary of STATCOM Mitigation of Subsynchronous Oscillations in Series Compensated Lines:**
  40. [40]
    Comparative Study of SVC and STATCOM Reactive Power Compensation for Prosumer Microgrids With DFIG-Based Wind Farm Integration
    - **STATCOM Role in Fault Recovery**: STATCOM provides faster and more effective reactive power (VAR) injection during faults in microgrids with DFIG-based wind farms. It dynamically compensates VAR, improving voltage stability and fault ride-through capability.
  41. [41]
    GE's STATCOM system to improve grid stability in Germany
    Sep 1, 2022 · The custom-designed system provides grid operators with reactive power compensation and improved range of operational voltage, resulting in a ...
  42. [42]
    [PDF] STATCOM Systems - ABB
    Jun 5, 2013 · The aim of this presentation is to give: ▫ An understanding of the voltage stabilisation principle. ▫ An overview of the power quality ...
  43. [43]
    [PDF] STATCOM Technology for Wind Parks to Meet Grid Code ...
    Key issues are steady state and dynamic reactive power capability, continuously acting voltage control and fault ride through behavior. Some commonly used ...
  44. [44]
    Mitigation of flicker in a distribution-connected wind farm with ...
    This paper details the flicker problems encountered upon the connection of wind power to distribution networks and its effects on the network characteristics ...Missing: solar | Show results with:solar
  45. [45]
    Evaluation and mitigation of voltage flicker caused by constant ...
    This paper addresses the problem of voltage fluctuation caused by constant speed wind turbines that are based on induction generators. Comprehensive wind speed ...Missing: solar | Show results with:solar
  46. [46]
    Research on the STATCOM Mathematical Model of Battery Storage ...
    Jun 22, 2022 · This study proposes to use battery energy storage STATCOM (STATCOM/BESS) and gives the main circuit topology of STATCOM/BESS.
  47. [47]
    [PDF] Fault Current Generation by STATCOM - Chalmers Publication Library
    Dec 19, 2017 · Renewable energy resources are not required, by the current grid codes, to contribute to restore the voltage stability. Moreover, they do ...
  48. [48]
    [PDF] Grid-Forming Technology in Energy Systems Integration - ESIG
    To demonstrate black-start capability, several experiments were conducted soft-starting a BESS. Soft start is the ability of GFM inverter to ramp its voltage ...
  49. [49]
    Hitachi Energy and Ørsted to ensure grid stability at Hornsea 4 with ...
    Dec 23, 2024 · Hornsea 4 is expected to be Europe's first offshore wind farm to feature Enhanced STATCOM, the next generation of grid stabilization technology.Missing: Dogger Bank Asian farms 2020
  50. [50]
    [PDF] Utilization of STATCOM Systems at Wind Power Plants to Meet ...
    As the Indian. Grid Code continues to evolve to accommodate higher levels of renewable energy penetration, the need to specify more precise behavior during low ...
  51. [51]
    A promising year for the STATCOM market - PTR Inc.
    To provide reactive power support and maintain voltage stability, all four transmission system operators of Germany aim to install roughly 70 STATCOMs by 2030.
  52. [52]
    Technical and Operational Comparison of SVC, STATCOM ... - EPRI
    Apr 29, 2022 · This report provides a clear comparison between SVCs, STATCOMs, and Synchronous Condensers from various operational, technical, and economic perspectives.Missing: response time footprint
  53. [53]
  54. [54]
    Power System Studies - Comparison of SVC and STATCOM
    Static Synchronous Compensator (STATCOM) is a shunt-connected voltage source converter-based VAR generator to control the VAR generation and absorption.
  55. [55]
    (PDF) Performance comparison of STATCOM versus SVC to ...
    Apr 1, 2015 · The results showed that STATCOM provides a better voltage support than SVC. Also, the reactive power control performance of STATCOM and SVC ...
  56. [56]
    FACTS: costs of STATCOMs and SVCs? - Thunder Said Energy
    Based on aggregating cost data from 25 prior projects, we think typical costs for SVCs are around $100/kVAR, while STATCOMs are above $150/kVAR.Missing: time voltage range footprint
  57. [57]
  58. [58]
    [PDF] Shunt- Connected FACTS and Synchronous Condensers
    STATCOMs are a form of shunt-compensation devices that provide reactive-power support, voltage regulation, and the ability to increase short-circuit ...<|control11|><|separator|>
  59. [59]
    [PDF] Comparison of Synchronous Condenser and STATCOM for Wind ...
    A STATCOM consists of a three-phase GTO/IGBT voltage source converters (VSCs), step-down transformer with leakage reactance, DC capacitors and VSC controller. ...
  60. [60]
    Comparison of synchronous condenser and STATCOM for inertial ...
    Feb 14, 2017 · PDF | This paper shows a comparison between synchronous ... Comparison of synchronous condenser and STATCOM for inertial response support.
  61. [61]
    [PDF] Looking Forward: Dynamic Reactive Device Technologies
    Feb 17, 2021 · • Synchronous condensers contribute short-circuit current and inertia, just as synchronous generators do. • Capability in the positive MVAR ...
  62. [62]
    Synchronous Condenser Performance Analysis and Alternate ...
    Jun 16, 2021 · This report is meant to be a companion report to Synchronous Condenser Cost and Performance Study: 2021 Update (3002020357).