Circular mil

A circular mil (CM) is a unit of area equal to the area of a circle whose diameter is one mil, or 0.001 inch (approximately 0.0254 mm), equivalent to about 5.067 × 10⁻⁴ mm² or 0.7854 × 10⁻⁶ square inches. This unit is primarily employed in to quantify the cross-sectional area of round wire conductors, excluding , facilitating precise sizing for current-carrying capacity and material comparisons. For larger conductors, the term kcmil (thousand circular mils) or its equivalent MCM (thousand circular mils) is used, such as for wires rated at 250 kcmil or greater, as specified in standards like the (NEC). The circular mil system complements the (AWG) by providing an absolute measure of conductor area, particularly useful for non-round or comparative applications across gauge systems, where 1 CM = d² (with d as in mils). It originated in early practices to simplify calculations for wire resistance and , avoiding the complexities of π in area formulas by basing measurements on squared. Conversions to units are standard in modern engineering, with 1 kcmil ≈ 0.5067 mm², ensuring compatibility in international standards like ASTM for conductor tolerances. This unit remains integral to industries such as power distribution, , and , where accurate conductor sizing prevents overheating and ensures safety.

Fundamentals

Definition

A circular mil (cmil or CM) is a unit of area equal to the area of a circle whose diameter is one mil, where one mil is a unit of length defined as 0.001 inch. This unit is particularly employed in the electrical engineering field to denote the cross-sectional area of wires and cables, facilitating calculations based on diameter measurements without requiring the full computation of π in area formulas. Mathematically, the area A of one circular mil is given by A = \frac{\pi}{4} \times (1 \, \text{mil})^2, which equals \frac{\pi}{4} square mils, or approximately 0.7854 square mils. In metric terms, this corresponds to approximately $5.067 \times 10^{-4} mm², while in beyond mils, it is approximately $7.854 \times 10^{-7} square inches. For larger wire sizes, the unit is scaled to kcmil (or MCM, standing for thousand circular mils), where 1 kcmil equals 1,000 cmil. This notation simplifies the specification of substantial conductor areas in electrical standards and applications.

Historical Origin

The circular mil unit emerged in the mid-19th century , amid the rapid expansion of and early electrical industries, which demanded standardized measurements for wire conductors to ensure consistent performance and manufacturability. Developed to address inconsistencies in wire sizing practices that varied by manufacturer, it was introduced by engineers at the Manufacturing Company in , around 1856, as part of their precision system. This innovation, proposed by Lucian Sharpe, built on geometric progressions to create a for wire diameters, facilitating easier production and specification in an era when telegraph lines spanned continents and required reliable, uniform cabling. The unit's core rationale lay in simplifying cross-sectional area calculations for round wires, where the area in circular mils equals the square of the diameter in mils, thereby eliminating the need for the constant π (pi) typically required in standard geometric formulas. This practical approach avoided complex circular geometry computations, making it ideal for engineers and wire producers dealing with resistance and current-carrying capacity without advanced mathematical tools. By the late 19th century, the circular mil had been formalized by American wire manufacturers and integrated into the American Wire Gauge (AWG) system, which became the predominant standard for North American electrical wiring by the 1880s. As electrical applications grew to include power distribution in the early , the basic circular mil proved cumbersome for specifying larger conductors due to escalating numerical values. To address this, the thousand circular mil (kcmil, also denoted as MCM for "thousand circular mils") was introduced, starting with sizes like 250 kcmil for conductors beyond 4/0 AWG, allowing concise notation for massive cables used in high-voltage transmission. This evolution reflected ongoing refinements in the wire industry to accommodate industrial-scale while maintaining the unit's foundational simplicity.

Area Equivalences

To Imperial Units

The circular mil (cmil) is defined as the cross-sectional area of a circle with a of one (0.001 inch), which equals the area of a scaled to that diameter, or \pi/4 square mils. Thus, $1 cmil = \pi/4 \approx 0.785398163 square mils, where a square mil is the area of a square with sides of one . To convert to square inches, note that one square mil equals (0.001)^2 = 10^{-6} square inches. Therefore, $1 cmil = (\pi/4) \times 10^{-6} = \pi \times 10^{-6}/4 \approx 7.85398 \times 10^{-7} square inches. The circular mil unit simplifies specifications for wire cross-sections by eliminating the \pi/4 factor in area calculations, as the area in cmil directly equals the square of the diameter in mils, making it more convenient than using es for applications. For instance, a cross-section of 1 equates to approximately 1,273,240 cmil, highlighting the scale difference and the unit's utility for large wire sizes. This equivalence reinforces the core relation for wire sizing, where the cross-sectional area A in cmil is given by A = d^2, with d as the diameter in mils.

To Metric Units

The circular mil, a unit primarily used in the imperial system for specifying wire cross-sectional areas, can be converted to the metric unit of square millimeters (mm²) for compatibility with international standards. Precisely, 1 circular mil equals approximately 5.06707479 × 10^{-4} mm², derived from the area of a circle with a diameter of 1 mil (0.001 inch), where 1 mil = 0.0254 mm, yielding an area of \frac{\pi}{4} (0.0254)^2 \approx 5.06707479 \times 10^{-4} mm². Similarly, 1 thousand circular mil (kcmil), equivalent to 1,000 circular mils, corresponds to approximately 0.5067 mm². For practical estimations in environments using mixed and units, such as projects, an approximation of 2 kcmil ≈ 1 mm² is commonly employed, introducing an error of about 1.3% (since 2 × 0.5067 = 1.0134 mm²). This rule of thumb simplifies quick cross-referencing without significant loss of accuracy for most applications. An analogous metric unit to the circular mil is the circular millimeter (cmm), defined as the cross-sectional area of a circle with a of 1 , or equivalently d² where d is in millimeters, resulting in an area of \frac{\pi}{4} ² ≈ 0.7854 ². The relation to the circular mil accounts for the unit conversion: 1 cmm ≈ 1,550.003 cmil, calculated as (1 / 0.001 inch)^2 adjusted by the inch-to-mm factor of 25.4, yielding (39.37007874)^2 cmil. Despite this conceptual similarity, the cmm is rarely used in practice because the favors the direct measurement of actual cross-sectional area in ² over diameter-squared simplifications. It appears occasionally in specialized wire specifications for consistency with imperial conventions.

Calculations

Area from Diameter

The circular mil (cmil) is defined such that the cross-sectional area of a round conductor is calculated directly from its measured in s, where 1 mil equals 0.001 inch. This unit originates from the geometric , given by A = \pi r^2, or equivalently A = \frac{\pi}{4} d^2 where d is the in consistent units. To simplify calculations for wire sizing in , the circular mil is specifically defined as the area of a circle with a 1- , which equals \frac{\pi}{4} square mils (approximately 0.7854 square mils). By this definition, the \frac{\pi}{4} factor is absorbed into the unit itself, allowing the area in circular mils to be computed simply as the square of the in mils: A_{\text{cmil}} = d^2. For units consistency, the diameter d must be expressed in mils; if the diameter is given in inches, it is first converted by multiplying by 1000 to obtain mils before squaring. This ensures the result is in circular mils, a unit of area defined as the area of a circle with a 1-mil . To illustrate, consider a wire with a diameter of 10 mils. First, confirm the diameter is in mils (here, it already is). Then, square the value: A_{\text{cmil}} = 10^2 = 100 circular mils. This 's primary advantage is enabling rapid area estimation for round conductors without needing to compute or include geometric constants like \pi, which streamlines manual calculations and comparisons in standards.

Diameter from Area

The d of a wire, expressed in mils, can be calculated from its cross-sectional area A in circular mils using the inverse of the defining , where d = \sqrt{A}. This relation follows directly from the standard definition that the area in circular mils equals the square of the in mils. For instance, consider a wire with an area of circular s. The is found by taking the : \sqrt{[10,000](/page/10,000)} = 100 s, which equals 0.1 inches (since = 0.001 inch). No rounding is typically needed for exact values like this, but in practice, measurements may involve slight adjustments for precision. This calculation is practically applied in verifying wire dimensions against specifications or assessing tolerances, particularly for electrical conductors where the cross-sectional area is predefined in circular s. The formula assumes a perfectly round cross-section; for non-circular shapes, such as certain stranded or irregular conductors, adjustments to the area measurement are required, often converting to square inches for accuracy.

Wire Sizing Standards

AWG Formula and Sizes

The American Wire Gauge (AWG) system employs a logarithmic progression to define wire sizes, where the cross-sectional area in circular mils, A_n, for gauge number n is given by the formula A_n = \left[5 \times 92^{\frac{36 - n}{39}}\right]^2 circular mils, with n ranging from 18 to 4/0 (where 4/0 corresponds to n = -3). This equation derives from the historical wire drawing process, in which wire is successively pulled through conical dies to reduce its diameter; each draw typically decreases the cross-sectional area by a fixed ratio, leading to a geometric series. Specifically, the base diameter at AWG 36 is defined as 0.005 inches (5 mils), and the progression spans 39 steps to reach the diameter at 4/0 AWG of approximately 0.46 inches, with an overall diameter ratio of 92:1 across these steps; thus, the diameter ratio between consecutive gauges is the 39th root of 92 (approximately 1.1229), and the area, being proportional to the square of the diameter, follows the squared form of this logarithmic relation. Every six gauge steps double the diameter, while every three steps double the area, reflecting the practical increments in wire production. The AWG system was developed in 1857 by the manufacturing company in , to standardize wire sizing amid inconsistent practices in the emerging telegraph and electrical industries; this ensured consistent reduction ratios during mechanical drawing, facilitating uniform production across manufacturers. In the AWG system, gauge numbers decrease as wire size increases, meaning smaller numbers denote thicker wires with larger areas in circular mils—for instance, 12 AWG has an area of 6,530 circular mils, while 0000 AWG (also denoted 4/0) reaches 211,600 circular mils. The following table summarizes select common sizes from 18 AWG to 4/0 AWG, including areas in circular mils and approximate diameters in inches (rounded to three decimal places for clarity):
AWG GaugeArea (circular mils) (inches)
181,6240.040
144,1070.064
126,5300.081
1010,3830.102
816,5090.128
626,2510.162
441,7400.204
266,3690.258
1/0105,6000.325
4/0211,6000.460
The AWG designation is conventionally used for sizes up to (4/0) AWG, beyond which larger conductors are sized in thousands of circular mils (kcmil) for simplicity and to avoid cumbersome multiple-zero notations.

kcmil Sizes

The kcmil (thousand circular mils), also denoted as MCM, serves as the standard unit for specifying the cross-sectional area of electrical conductors larger than AWG (4/0 AWG), facilitating precise sizing for high-current applications. This notation expresses the area in thousands of circular mils, where each circular mil represents the with a 1-mil (0.001 inch) . Common standard kcmil sizes include 250, 300, 350, 400, 500, 600, 750, 800, 900, , 1250, 1500, 1750, and 2000, selected to provide incremental scalability for increasing ampacity needs in power distribution systems. These sizes are not derived from the exponential progression of AWG but instead follow discrete steps to align with practical and requirements. For instance, a kcmil conductor has a cross-sectional area of approximately 126.7 mm² and a solid diameter of 0.500 inches (12.70 mm). In contrast, a kcmil conductor equates to about 506.7 mm² with a diameter of 1.000 inch (25.40 mm). Such conversions from kcmil to metric units (1 kcmil ≈ 0.5067 mm²) aid in international compatibility. These sizes are standardized in codes like the (), particularly in tables for ratings under Article 310, ensuring safe current-carrying capacities based on , , and ambient conditions. To relate kcmil to physical dimensions, the total area in circular mils is given by A = \text{kcmil} \times [1000](/page/1000), and the diameter d in mils is d = \sqrt{A}. For example, for 250 kcmil, A = 250,000 cmil, so d = \sqrt{250,000} = 500 mils, or 0.500 inches.

Applications

Electrical Wiring Standards

The circular mil, particularly in the form of thousands of circular mils (kcmil), plays a central role in the , published by the , for specifying conductor sizes in electrical installations across the . According to Article 110.6, conductor sizes must be expressed in either for smaller wires or circular mils for larger ones, ensuring standardized sizing that supports safe current-carrying capacities and system performance. This adoption facilitates precise calculations for , where Table 310.15(B)(16)—formerly Table 310.16—provides allowable ampacities for insulated conductors rated up to 2000 volts, listing sizes from 18 AWG up to 2000 kcmil and linking them directly to amperage ratings based on type, , and ambient conditions. In the Canadian Electrical Code (CEC), developed by , circular mils are similarly incorporated, especially for larger conductor sizes beyond standard AWG equivalents, to align with North American practices while accommodating metric conversions. Rule 4-004 of the CEC references conductor areas in both square millimeters and equivalent circular mils for ampacity determination using Tables 1 through 4, which derate based on factors like temperature and bundling to prevent overheating. For instance, a 250 kcmil conductor corresponds approximately to 127 mm² in CEC tables, allowing installers to select sizes that match load requirements while complying with safety standards. Sizing criteria in these codes rely on circular mils to determine current-carrying capacity, , and requirements, ensuring conductors can handle specified loads without excessive resistance or heat buildup. calculations, recommended to not exceed 3% for feeders and 5% total by NEC Informational Note in Article 210.19(A), use formulas incorporating circular mil area from Chapter 9, 8, such as VD = (2 × K × I × L) / CM for single-phase circuits, where CM is the circular mil area. requirements are tied to these sizes via ampacity tables; for example, a 90°C-rated conductor like THHN in 500 kcmil size has a 90°C ampacity of 430 A, but under standard conditions with 75°C terminations, supports up to 380 A per NEC 310.15(B)(16) and 110.14(C). Internationally, circular mils are predominantly a North American standard, contrasting with the (IEC) standards, which favor square millimeters for cross-sections in documents like , promoting metric uniformity in and elsewhere without direct cmil references. These standards emphasize by mandating minimum sizes to avoid overheating and fire hazards; for a typical 15-ampere branch , the requires at least 14 AWG (approximately 4,110 circular mils), while a 100-ampere service might necessitate 3 AWG (around 52,620 circular mils) to limit and ensure thermal stability under full load. Non-compliance risks degradation or failure, underscoring the codes' role in protecting electrical systems and occupants.

Modern Usage and Comparisons

As of the 2023 (current through 2025), the circular mil remains a standard unit for specifying conductor sizes in North American electrical manufacturing and installation, particularly for larger wires beyond 4/0 AWG, where it is expressed as kcmil (thousands of circular mils). This usage is embedded in the 2023 (), which designates conductor sizes in AWG or kcmil for applications like ratings and conduit fill calculations, with no substantive revisions to this system in the 2023 edition or interpretations through 2025. Proposals for the 2026 NEC, as reviewed through 2025, do not include changes to the use of kcmil for conductor sizing. Electrical design software such as ETAP and SKM Power*Tools integrates kcmil directly into cable libraries and sizing modules, allowing engineers to select sizes from AWG/kcmil dropdowns alongside metric options for hybrid workflows. Beyond traditional power distribution, circular mils are applied in specialized wiring for automotive, , and optic systems, often for electrical conductors within these domains. In automotive wiring, U.S. standards size cables in AWG or kcmil to ensure compatibility with harnesses and current loads, prioritizing ease of with imperial-based . applications adapt the unit for wiring and bonding, where circular mil area (CMA) specifies wire and splice cross-sections to meet MIL-STD requirements for weight and performance optimization. For optics, adaptations involve analogous cross-sectional measurements for electro-optical cables, though primary sizing shifts to metric diameters; circular mils support legacy electrical components in these assemblies. Compared to square millimeters (mm²), the circular mil offers simplicity for round conductors since area equals the square of the diameter in mils, avoiding π in calculations, but mm² provides greater precision for standards and non-circular shapes. Versus AWG numbering alone, kcmil conveys absolute area directly, making it more informative for large conductors where numbers become cumbersome. These advantages sustain its role in U.S. systems amid global trade pressures favoring metric, though conversions (e.g., 1 kcmil ≈ 0.5067 mm²) facilitate . Trends indicate slow metric adoption in U.S. codes, with the retaining kcmil primacy in the 2023 edition and no mandated shift in the anticipated update. Digital tools increasingly support hybrid units, enabling seamless AWG/kcmil-to-mm² translations to align with global supply chains while preserving domestic efficiency.

References

  1. [1]
    CM - Circular Mil Area - The Engineering ToolBox
    A circular mil is the equivalent area of a circle whose diameter is 0.001 (10-3) inch, or approximately 0.7854 millionths of a square inch. Mils of circular ...
  2. [2]
    Circular Mils Explained - Blue Sea Systems
    Circular Mils is the term created for the measurement system devised to measure wire conductor (without the insulation) sizes in absolute terms.Missing: standards | Show results with:standards
  3. [3]
    Electrical FAQs | Cerrowire
    They are equal measurements and refer to thousands of circular mils. A circular mil is equal to the area of a circle with a diameter of one mil. One mil is ...<|control11|><|separator|>
  4. [4]
    AWG - American Wire Gauge vs. Circular Mils
    CM - Circular Mil Area. The circular mil area (CM) unit denotes the cross-sectional size of a wire or a cable.
  5. [5]
    [PDF] Copper wire tables - NIST Technical Series Publications
    or, 0.0409 ohm-circular mil/ft. The International Electrotechnical Com¬ mission specified the temperature coefficient of standard copper to be 0.00393 at 20 ...
  6. [6]
    [PDF] Transmission Line Design Information
    Mar 21, 2024 · A circular mil is a unit of area, equal to the area of a circle with a diameter 1mil (1 mil=0.001in=0.0254 mm). It corresponds to ...
  7. [7]
    NIST Guide to the SI, Appendix B.8: Factors for Units Listed ...
    Feb 1, 2016 · circular mil, square millimeter (mm2), 5.067 075, E-04.
  8. [8]
    [PDF] AWG and Circular Mils - PDH Online
    KCMIL versus MCM: KCMIL is the same as MCM, which is 1,000 circular mil. KCMIL stands for 1,000 (K) circular (C) mil (MIL) and MCM stands for. 1,000 (M, from ...
  9. [9]
    The Development of Wire Gages - Radio World
    Apr 6, 2003 · A gage consisted of a flat circular piece of steel with precision-machined slots corresponding to the different sizes of wire. It was a big hit ...Missing: origin | Show results with:origin
  10. [10]
    Conductor Size | Electronics Textbook - All About Circuits
    A = πr2 (square units) Calculating circular-mil wire area for a circular wire is much simpler, due to the fact that the unit of “circular mil” was sized just ...
  11. [11]
    Wire sizes - Global-Electron.com
    Background. Imagine you were an 19th century engineer ... Therefore, sizes are usually given in thousands of circular mils, denoted kcmil or previously MCM.
  12. [12]
    [PDF] Window Utilization, Magnet Wire, and Insulation
    Circular mil and Square mil. There are engineers that use circular mils (CM)/amp or square mils/amp. This is the reciprocal current density. The norm is to ...
  13. [13]
    Convert circular mil to mm squared - Conversion of Measurement ...
    Do a quick conversion: 1 circular mils = 0.0005067074790975 square millimeters using the online calculator for metric conversions.Missing: exact | Show results with:exact
  14. [14]
    Thousand Circular Mils to Square Millimeters - Kyle's Converter
    1 Thousand Circular Mils to Square Millimeters = 0.5067, 70 Thousand Circular Mils to Square Millimeters = 35.4695 ; 2 Thousand Circular Mils to Square ...
  15. [15]
    FAQ: AWG chart and the metric system | Eland Cables
    Circular mil is the area of a 1/1000 (or 1 mil) diameter circle. Such measurements are made on only the wire and not on the wire's jacketing or insulation. In ...
  16. [16]
  17. [17]
    What does circular measure mean? - Definitions.net
    For example, 1 circular mil is equivalent to 0.7854 square mil in area, 1 circular millimeter = 1550 circular mils = 0.7854 square millimeter. Here 0.7854 = π / ...
  18. [18]
    MECHANICAL AND ELECTRICAL REVIEWER: Wires, Insulation ...
    The local circular millimeter area is found by multiplying the circular area ... Circular MIL (CM)- this is the unit of cross- section in American wire gauge.
  19. [19]
    Aircraft Wiring Flashcards - Quizlet
    Amount of current a wire is capable of carrying is determined by its cross-sectional area. Expressed in circular millimeter. 0.7854 of a square millimeter ...<|separator|>
  20. [20]
    Introduction to Electrical Conductors, Wiring Techniques ... - RF Cafe
    a circular mil is the area of a circle having a diameter of 1 mil, as shown in view B of figure 1-2. The area in circular mils of a round conductor is obtained ...
  21. [21]
    Diameter to Circular Mils - vCalc
    Aug 14, 2024 · The Diameter to Circular Mils equation computes the circular mils for a single wire (one strand) from an input diameter.<|control11|><|separator|>
  22. [22]
    B258 Standard Specification for Standard Nominal Diameters and ...
    Oct 12, 2018 · This specification prescribes the standard nominal diameters and cross-sectional areas of American Wire Gage (AWG) sizes of solid round wires, used as ...
  23. [23]
    The Crazy World of Conductor Sizing – The Origins of the AWG ...
    The metric system was officially adopted by the French government in 1795. It had its ups and downs, and was at one point banned by Napoleon, but gradually won ...
  24. [24]
    What is American Wire Gauge (AWG) and how does it work?
    Jul 19, 2021 · All other sizes are derived as logarithmic steps between these two defined sizes. ... There are 39 gauge steps between these sizes, and the ratio ...
  25. [25]
    AWG Wire Chart, Aught, MCM kcmil, US Inch, and Metric Wire Sizes
    ### Summary of Standard kcmil Sizes and Specific Details
  26. [26]
  27. [27]
    Conductor Sizing, based on 2017 NEC - Part 1 - Mike Holt
    Conductor sizes are expressed in American Wire Gage (AWG), typically from 18 AWG up to 4/0 AWG. Conductor sizes larger than 4/0 AWG are expressed in kcmil ( ...
  28. [28]
    Guide to the Canadian Electrical Code, Part 1[i], 26th Edition
    Jan 7, 2024 · Size of conductors. Rule 4-002 requires that the minimum size for all copper conductors, except for flexible cord, equipment wire, or control ...<|control11|><|separator|>
  29. [29]
    circular mils | Canadian Electrical Code – my notes - WordPress.com
    Nov 24, 2014 · However, as per British system, the nearest standard conductor size is 120mm2, so a 250 MCM corresponds to approximately a 120mm2 conductor.
  30. [30]
    Voltage Drop Calculations - Mike Holt
    The maximum conductor voltage drop recommended for both the feeder and branch circuit is 5 percent of the voltage source; 120 volts x 5% = 6 volts.
  31. [31]
  32. [32]
  33. [33]
    [PDF] 2023 National Electrical Code (NEC ) - SunCam
    Conductor sizes are specified as AWG (American. Wire Gauge) or in circular mils (cmil or kcmil) (Art. 110.6). Wire sizes up to 4/0 (called “four aught" or ...
  34. [34]
    ETAP User Guide 16.0. - Part54 PDF - Scribd
    You can specify the engineering properties of the cable on this page. Dimensions. Size Select the cable size in AWG/kcmil or mm2 from the pull-down list. kV
  35. [35]
    celebrating 50 years of excellence - SKM Systems Analysis
    Step 1 - Copy a cable from your source library to your new designation library. Step 2 - In the source cable properties window, click on circular mils. ...
  36. [36]
    US Standard Automotive Wires - Eland Cables
    US standard cables are sized in AWG and where appropriate kcmill, not mm2 - our conversion table can provide a guide where comparative sizing is needed. The ...
  37. [37]
    [PDF] AC 21-99(1): Aircraft Wiring and Bonding
    ... Circular Mil Area (CMA) of Wires and Splices. 13. 6–A–1. MS25036 – Terminal Lug ... manual for general wiring practices, and is primarily used by personnel ...
  38. [38]
    Copper Wire Sizes: MCM, Mils, Measurements, and Conversions
    Aug 4, 2022 · When a wire is larger than 0000, it has to be measured in MCM (thousands of circular mils), or kcmil. MCM and kcmil can be used interchangeably, ...
  39. [39]
    Conductor Sizing: AWG, Circular Mils, and mm² Conversions
    Sep 4, 2025 · AWG (American Wire Gauge): Standard in the U.S. up to 4/0. • Circular mils (cmil or kcmil): Used for larger sizes above 4/0. • Square ...
  40. [40]
    NEC® 2026 Significant Code Changes - IAEI Magazine
    Jul 1, 2025 · The 2026 edition of the National Electrical Code® (NEC®) brings significant updates that reflect the rapid advancement of technology and the growing complexity ...Missing: metric | Show results with:metric
  41. [41]
    Cable Systems | Cable Ampacity Software - ETAP
    ETAP Cable Systems helps design cable systems to operate to their maximum potential while providing secure and reliable operation.