Fire classification

Fire classification is a standardized system used to categorize fires based on the type of or material involved in , which guides the selection of suitable extinguishing agents and techniques to ensure effective suppression and minimize risks. This approach is critical for protocols, as mismatches between fire type and suppression method can intensify the blaze or introduce secondary dangers, such as electrical shocks or chemical reactions. In the United States, the (NFPA) Standard 10 (2022 edition) for portable fire extinguishers defines five primary classes—A, B, C, D, and K—tailored to common fire scenarios in residential, commercial, and industrial settings. Under the NFPA system, Class A fires involve ordinary combustible solids like , , cloth, rubber, and certain plastics, which are typically extinguished with or to cool and soak the material. Class B fires stem from flammable or combustible liquids and gases, such as , oil, grease, or , requiring non-conductive agents like dry chemicals or to smother the flames without spreading the fuel. Class C fires occur with energized electrical equipment, where non-conductive suppressants like dry chemicals or CO2 are essential to avoid risks. Class D fires involve combustible metals, including magnesium, , sodium, or , and demand specialized dry powder agents to form a crust that excludes oxygen. Finally, Class K fires arise from cooking appliances with vegetable or animal oils and fats, addressed by wet chemical agents that saponify the grease to prevent reignition. Internationally, similar classifications exist, such as ISO 3941 (2007, confirmed 2022), which divides fires into five categories based on fuel nature—solids, liquids, gases, metals, and cooking oils and fats—promoting global consistency in training and equipment labeling, though regional standards like Europe's EN 2 may use letters A to F with slight variations in scope. These systems underpin broader strategies, including building codes, extinguisher placement, and emergency response training, ultimately reducing and loss of life from the estimated 1.39 million fires reported in the U.S. in 2023.

Fundamentals

Definition and Principles

Fire classification is a standardized for categorizing fires based on the type of involved, enabling the selection of appropriate extinguishing agents and methods to ensure effective suppression. This approach recognizes that different require specific interventions to interrupt the process without exacerbating the fire or endangering responders. At its core, fire classification is grounded in the principles of fire science, particularly the fire tetrahedron, which describes the four essential elements required for sustained : , , oxygen, and the chemical . guides the removal or of these elements in a targeted manner—for instance, by cooling to reduce , smothering to limit oxygen, or inhibiting the chain reaction—while preventing re-ignition and avoiding adverse reactions between the extinguishing agent and the , such as explosions or intensified burning. These principles prioritize responder by matching suppression techniques to the fire's characteristics, ensuring that inappropriate agents do not spread the fire or release toxic fumes. Fires are fundamentally distinguished by their behavior into ordinary combustibles, which involve solid materials that burn steadily and produce embers requiring cooling and soaking, and special hazards, which encompass fuels with unique properties like rapid spread or high reactivity that demand specialized agents to avoid escalation. Standards organizations such as the (NFPA) and European Norm (EN) have formalized these principles into global frameworks to promote consistency in practices.

Historical Development

The development of fire classification systems originated in the early , primarily driven by insurance underwriters addressing the distinct risks posed by different fuel types following major urban conflagrations. Underwriters Laboratories (UL) further advanced this framework in the 1910s through standardized testing protocols for fire extinguishers, establishing Class A and B ratings to guide selection based on fuel characteristics and ensuring compatibility with extinguishing agents. Key milestones in codification occurred mid-century, with the (NFPA) playing a central role. The NFPA's Committee on Portable Fire Extinguishers, formed in 1918–1919, laid the groundwork for NFPA 10, the Standard for Portable Fire Extinguishers, which was revised in 1969 to comprehensively define and integrate the emerging classes, including provisions for electrical (Class C, formalized in the early to mid-) and metal (Class D) fires. In , harmonization efforts gained momentum in the late amid the push for a , culminating in the adoption of EN 2 in 1992, which standardized fire categories (A through F) across member states to facilitate cross-border trade in safety equipment. Similarly, adopted AS 2444 in 1981 for the selection and location of portable extinguishers, with subsequent revisions—such as in 2001—incorporating Class E for energized electrical equipment and Class F for cooking oils and fats to align with local fire risks. Influential events shaped these expansions. Post-World War II industrial growth, particularly in and , highlighted the hazards of combustible metals like magnesium, leading to the formal inclusion of Class D; dry powder agents for such fires had been prototyped during the war, but commercial extinguishers emerged in 1949. The 1980s saw a surge in commercial kitchen incidents, driven by energy-efficient appliances retaining heat longer and shifts toward vegetable oil-based cooking, which prompted the dedicated Class K (or F in some systems) for fats and oils in the early —in NFPA 10's 1998 edition—to address re-ignition risks not covered by Class B extinguishers. Meanwhile, electrical fires evolved from "special" or unclassified handling—due to their non-fuel nature and conductivity dangers—to a dedicated Class C by the mid-20th century, emphasizing non-conductive agents in standards like NFPA 10.

Standards and Systems

United States (NFPA)

In the , fire classification for portable fire extinguishers and fixed fire suppression systems is primarily governed by the (NFPA) Standard 10, titled Standard for Portable Fire Extinguishers, with the latest edition published in 2026. This standard establishes a framework for selecting, installing, inspecting, and maintaining extinguishers to ensure they effectively combat specific fire types as a first line of defense. It defines five primary fire classes—A, B, C, D, and K—tailored to different hazards, emphasizing the use of appropriate extinguishing agents to prevent re-ignition or escalation. Class A fires involve ordinary combustible solids like , , and cloth, addressed by water-based or foam agents that cool and soak the material. Class B fires stem from flammable liquids and gases, such as or , requiring smothering agents like dry chemical or to interrupt the without spreading the fuel. For Class C, which covers energized electrical equipment, non-conductive agents like dry chemical or are mandatory to avoid electrical shock or short circuits during suppression. Class D fires involve combustible metals like magnesium or , where only specialized dry powder agents are permitted, as water or other common suppressants can react violently. Class K targets cooking oils and fats in commercial kitchens, using wet chemical agents that promote —a process turning the oil into a soapy to seal the surface and prevent reignition. Notably, there is no Class E designation in the NFPA system; electrical hazards are subsumed under Class C, with de-energization recommended when feasible. Regulatory enforcement integrates NFPA 10 into federal workplace safety requirements through the (OSHA) under 29 CFR 1910.157, which mandates the provision of class-specific extinguishers based on anticipated fire hazards in non-residential occupancies. This regulation requires employers to assess workplace risks and distribute extinguishers accordingly, ensuring accessibility within specified travel distances (e.g., 75 feet for Class A fires) and conducting employee training on their use. Compliance is verified through inspections, with OSHA referencing NFPA 10 for technical criteria on agent types and ratings. A distinctive aspect of the U.S. system is the emphasis on independent certification, particularly Underwriters Laboratories (UL) listing, which verifies that extinguishers meet performance standards for specific classes through rigorous testing protocols. All portable extinguishers must bear a UL mark to confirm their reliability in real-world scenarios. The NFPA itself, founded in 1896 in response to a series of devastating electrical fires, has evolved into a key authority on fire safety standards, initially focusing on uniform electrical practices before expanding to comprehensive codes like NFPA 10.

European Union (EN)

In the , fire classification is governed by the EN 2:1992 standard, titled "Classification of fires," which provides a unified framework for categorizing fires based on the type of involved, promoting consistency in practices across member states. This standard, originally published in 1992, classifies fires into five categories: Class A for solids such as wood, paper, and textiles that may smolder or leave embers; Class B for flammable liquids and solids that can melt and burn, like or solvents; Class C for flammable gases such as or ; Class D for combustible metals including magnesium or aluminum; and Class F, introduced via the 2004 amendment (EN 2:1992/A1:2004), for cooking oils and fats. Electrical fires are not assigned a dedicated class under EN 2, as they are considered a arising from energized rather than a fuel type; instead, the primary response involves de-energizing the source before applying an appropriate extinguisher based on the underlying . Portable fire extinguishers compliant with the related EN 3 series of standards (particularly EN 3-7:2004+A1:2007 for characteristics and performance) feature standardized markings to indicate their suitability for specific classes, including a body color and pictograms or symbols for the rated fire classes, replacing earlier full-body color coding with a zonal approach for clarity. These markings ensure quick identification during emergencies, with mandatory affixed to certify conformity to EU safety requirements, including those under the Pressure Equipment Directive 2014/68/EU, which regulates the design, manufacture, and testing of pressurized extinguishers to prevent hazards like explosions. The directive applies to extinguishers as transportable pressure equipment with a maximum allowable greater than 0.5 , mandating assessments and conformity modules for market placement. A distinctive aspect of the EU system is its integration of environmental considerations in fire suppression, exemplified by the prohibition of halon-based agents since the late 1990s in line with the 1987 on Substances that Deplete the , which phased out ozone-depleting substances to protect the atmosphere while encouraging alternatives like clean agents or water-based systems. This harmonized approach, which accelerated in the post-1970s era to support the , underscores the EU's emphasis on both and in fire safety equipment.

Australia and Other Regions (AS/ISO)

In , fire classification for portable fire extinguishers is governed by the Australian Standard AS 2444-2001, which outlines the selection, location, and distribution of extinguishers based on six distinct fire classes to address common local hazards such as bushfires and industrial risks. These classes include A for ordinary combustible solids like wood and paper, B for flammable liquids such as petrol, C for flammable gases like , D for combustible metals including magnesium, E for fires involving energized electrical equipment, and F for cooking oils and fats. Unlike systems in other regions, Class E explicitly designates live electrical fires, emphasizing non-conductive extinguishing agents to prevent , a classification unique to and standards. Portable extinguishers must be labeled with their applicable classes and performance ratings, often covering multiple classes (e.g., ABC for versatile use in commercial settings), ensuring they meet site-specific needs determined through hazard assessments. The AS 2444-2001 framework draws influence from the international ISO 7165:2017 standard, which provides a global benchmark for the performance, construction, and testing of portable fire extinguishers to ensure reliability across diverse environments. This ISO standard establishes test methods for fire extinguishment efficacy, durability, and safety features like pressure retention, adopted variably in the region to harmonize with local regulations; for instance, countries like incorporate elements of ISO 7165 into national standards such as MS 1539 for enhanced compatibility in regional trade and manufacturing. In , this integration supports adaptations for unique hazards, including bushfire-prone areas where standards like AS 3959:2018 recommend extinguisher placements and types resilient to embers and radiant heat, prioritizing water or foam agents for Class A vegetation fires. Beyond , ISO 7165:2017 influences adaptations in other regions, with aligning its fire classifications closely to the U.S. model under the National Fire Code of (NFC), featuring Classes A, B, C (electrical), D, and K without a separate gas category, while incorporating ISO testing protocols for extinguisher performance to address similar North American fuel types and building practices. In , standards under the Fire Service Act, such as the Ordinance for Technical Specifications pertaining to Fire Extinguishers, adapt ISO principles for portable fire extinguishers, focusing on performance testing and specialized handling for hazardous materials in industrial and urban settings. Enforcement of these classifications in falls under the Work Health and Safety Regulations 2011, particularly Section 359, which mandates that workplaces provide appropriate and equipment tailored to identified hazards through site-specific risk assessments. These assessments evaluate factors like occupancy, fuel loads, and environmental risks—such as proximity to —ensuring extinguisher selection complies with AS 2444-2001 and periodic maintenance under AS 1851 to maintain operational readiness. Non-compliance can result in penalties, underscoring the regulation's role in promoting proactive across diverse Australian contexts.

Fire Classes by Fuel Type

Ordinary Combustibles (Class A)

Class A fires involve ordinary combustible solid materials, such as , , cloth, rubber, and many plastics, which burn with the formation of glowing embers and typically leave an residue upon extinguishment. These fires are distinguished by their reliance on solid organic fuels that sustain through surface oxidation and require cooling to interrupt the burning process. The characteristics of Class A fires include smoldering , where glowing occurs without open flames in later stages, often accompanied by significant heat release that facilitates rapid spread through connected combustibles. Common examples encompass structural fires in with wooden frameworks or furnishings and fires in interiors involving seats and dashboards made from textiles and plastics. These fires can penetrate deeply into the , complicating suppression if not addressed thoroughly. Extinguishment of Class A fires primarily focuses on water-based agents that cool the material via , absorbing and reducing temperatures below the ignition point. Fire extinguishers suitable for these fires are rated under UL 711, where the numerical prefix before the "A" indicates the equivalent extinguishing capacity in 1.25-gallon units of , corresponding to the of a standardized wood crib fire that can be controlled, for example, a 4-A rating equivalent to 5 gallons of and capable of extinguishing a standardized wood crib fire of specified configuration. The Class A designation is universally consistent across major fire classification systems, including NFPA in the United States, EN standards in the , AS/ISO in and other regions, all defining it as fires of ordinary solid combustibles. To address deep-seated burning in these materials, penetration-enhancing agents like Class A foam are employed, which reduce water's for better soaking and prevention of re-ignition.

Flammable Liquids and Gases (Class B/C)

Class B fires, as defined in the United States by the (NFPA), involve flammable or combustible liquids, such as , solvents, and , as well as flammable gases like and . In the and , the classification distinguishes between Class B for flammable liquids and Class C for flammable gases, reflecting differences in fuel behavior and extinguishing requirements. These fires are characterized by rapid flame spread due to the ignition of volatile produced by the liquids or directly from the gases, often leading to high heat release rates and a significant risk of if accumulate in confined areas. Unlike solid combustibles, Class B/C fires typically leave no charred residue upon extinguishment, but they pose a high reignition potential from lingering that can reflash if not fully suppressed. This vapor-driven propagation aligns with the fire tetrahedron model, where the phase involves gaseous sustaining the reaction. Effective suppression of Class B/C fires requires non-conductive agents that blanket the fuel surface to exclude oxygen and inhibit vapor release, such as (CO₂), dry chemical powders, or foams, while avoiding which can spread the fire by dispersing the . In the , extinguisher ratings for Class B are based on the approximate square footage of a pan fire that can be controlled, for example, a 10B rating indicates capacity for a roughly 10 (0.93 m²) pan fire under UL 711 testing standards. In contrast, European (EN 3) and Australian (AS 1841) systems rate Class B extinguishers by the size of the test pan area, where the numeral denotes performance levels corresponding to specific pan diameters—for example, lower ratings like 21B for pans around 0.1–0.2 m² and higher ratings like 55B or 233B for progressively larger pans up to 3 meters in diameter. Unique risks associated with Class B/C fire suppression include asphyxiation in confined spaces when using CO₂ extinguishers, as the gas displaces breathable oxygen to concentrations below 16%, potentially causing or without adequate . Additionally, the choice of extinguishing agent must account for the liquid's : non-polar hydrocarbons like are effectively blanketed by standard aqueous film-forming foams (AFFF), whereas polar solvents such as alcohols require alcohol-resistant foams (AR-AFFF) to prevent foam destabilization and ensure vapor sealing.

Combustible Metals (Class D)

Class D fires involve the combustion of combustible metals, including magnesium, , zirconium, sodium, , and . These metals ignite readily under , , or exposure to moisture, leading to rapid and intense burning. The classification is standardized across major systems, including the ' NFPA framework, the Union's EN standards, Australia's AS/ISO protocols, and international ISO guidelines, where Class D denotes fires fueled by such reactive metallic substances. These fires exhibit unique characteristics due to the properties of the fuels involved. Combustible metals burn at extraordinarily high temperatures, often surpassing 2000°C, with magnesium capable of reaching up to 3100°C; temperatures vary by metal but can exceed 3000°C for highly reactive ones. Unlike typical fires, they can become self-sustaining in low-oxygen environments because the metals undergo exothermic oxidation reactions that release their own oxygen or continue via molecular decomposition. The combustion often produces molten metal pools that retain heat, spread flames, and pose risks of reignition or structural damage. Common scenarios include aerospace manufacturing processes handling or magnesium components, and laboratory incidents involving lithium-based batteries, where can trigger metal combustion. Extinguishing Class D fires requires specialized dry powder agents tailored to the specific metal to avoid exacerbating the reaction. is strictly prohibited, as it can react violently with hot metals to produce gas explosions or bursts that intensify the fire. For sodium and fires, sodium chloride-based powders (such as Super-D) form a fusible crust that excludes oxygen and absorbs heat. powders are effective for and magnesium, smothering the flames by coating the burning surface and preventing further oxidation. Other agents, like powder or aqueous dispersion, may be used for certain alloys, always applied gently to avoid splashing molten material. These methods prioritize blanketing the fire to cool it below the ignition threshold while minimizing reactivity. In the United States, Class D extinguishers are tested under UL 711 for , with manufacturers specifying effectiveness on amounts of specific metals—for instance, a unit might be rated for 6 pounds of magnesium or 5 pounds of sodium—based on UL-listed evaluations. These hazards extend to secondary risks like reactions, where metals such as aluminum interact with metal oxides at elevated temperatures, generating molten iron and extreme localized heat that can breach containment or ignite nearby combustibles.

Cooking Oils and Fats (Class K/F)

Class K fires, as classified under the National Fire Protection Association (NFPA) standards, involve the combustion of cooking media such as oils and animal fats typically found in commercial like deep fryers. These materials ignite when heated to their autoignition temperatures, which generally exceed 360°C for common oils including canola (424°C), (406°C), and (435°C). In the under EN standards and in under AS/ISO classifications, equivalent fires are designated as Class F, recognizing the same hazards from high-temperature cooking processes. Distinct from Class B flammable liquids, cooking oils and fats exhibit higher flash points—often above 315°C—making them less volatile at but highly dangerous once heated, as they can undergo self-heating through oxidation, potentially leading to spontaneous ignition without an external spark. A key characteristic is their propensity for re-ignition after initial suppression, as the oils retain significant heat and can reignite if not adequately cooled, a risk amplified in scenarios like stovetop overheating where oil temperatures can surpass 400°C before flaming. Extinguishment requires specialized wet chemical agents, such as or citrate solutions, which react with the hot oils through —a chemical process forming a thick, soapy layer that blankets the , interrupts the chain, and provides cooling to prevent reflash. In the , Class K-rated extinguishers are evaluated under UL 8 and UL 711 standards for performance on deep fat fryer fires involving specific volumes of , typically protecting fryers of 25 to 80 liters (approximately 6.6 to 21 gallons) depending on the model. Under EN 3 and Australian standards, Class F extinguishers are rated by the size of the cooking vessel they can protect, such as 75F for pans or fryers up to 75 dm² (about 20 gallons equivalent area), ensuring coverage for commercial-scale hazards. These fires pose unique risks primarily in commercial kitchens, where they account for a significant portion of structure fires due to the prevalence of deep-fat frying equipment. The separate Class K/F classification emerged in the early 1990s following incidents that demonstrated the limitations of Class B dry chemical extinguishers, which often failed to prevent re-ignition in oil fires, prompting NFPA 10 updates to mandate dedicated wet chemical systems for enhanced safety in food service environments.

Special Classifications

Electrical Equipment Fires (Class C/E)

Electrical equipment fires, classified as Class C in the United States under NFPA standards, involve energized electrical components such as wiring, , motors, and transformers where the electrical poses an additional hazard beyond the combusting material. In , these are designated as Class E fires, encompassing similar sources like faulty wiring or overloaded circuits in electrical devices. The [European Union](/page/European Union), per EN 2 standards, does not assign a specific class to electrical fires; instead, the priority is to de-energize the equipment first before addressing the underlying combustible material. These fires are characterized by ignition sources like electrical arcing or short circuits, which generate intense heat—up to 10,000°F in arc faults—and can ignite nearby materials, though the primary risk stems from the live current rather than the fuel itself. Often, the combusting elements are secondary, such as plastic or other ordinary combustibles that behave like Class A materials once the electrical source is isolated. Extinguishment requires non-conductive agents to prevent , such as dry chemical powders, (CO₂), or clean agents like Halon alternatives, which displace oxygen without leaving residue or conducting electricity. Water-based methods are strictly prohibited due to conductivity risks. In the system, C ratings are combined with others (e.g., ABC extinguishers) to address both electrical and material hazards simultaneously. A distinctive feature is reclassification upon de-energization: once power is cut, the fire reverts to its fuel-based category, such as Class A for insulation. Historical hazards include polychlorinated biphenyl (PCB)-filled transformers, used for their fire-resistant insulating properties until the US Environmental Protection Agency banned PCB manufacture and phased out most uses in 1979 due to toxicity risks, including release of harmful dioxins during fires.

Self-Sustaining Chemical Fires (Class None)

Self-sustaining chemical fires arise from oxidizing agents, such as and , which inherently supply oxygen or other oxidizing substances to support , enabling the fire to continue even in oxygen-deprived environments. These materials do not fit into standard fire classes (A through K in NFPA systems, or equivalent in EN and AS/ISO standards) because their behavior transcends typical fuel-based categories; instead, they are managed as special hazards under codes like NFPA 400, Hazardous Materials Code, which classifies oxidizers into four severity levels based on their potential to enhance or initiate fires. Key characteristics of these fires include their ability to propagate without atmospheric oxygen, leading to rapid escalation and significant explosion risks due to or contamination. Common examples occur in laboratory settings with peroxides or in industrial storage of fertilizers like , which can ignite from nearby fires and sustain burning independently. A notable incident was the 2020 Beirut port explosion, where a fire in a warehouse containing approximately 2,750 tonnes of triggered a massive , devastating the surrounding area and highlighting the explosive potential of such materials. Extinguishing these fires requires tailored approaches, as standard methods may exacerbate the hazard; for non-water-reactive oxidizers like , copious water application cools the material and prevents further decomposition, while dry chemical agents or are preferred for water-reactive types such as certain to avoid violent reactions. Containment through isolation and ventilation control is often prioritized, with NFPA 400 providing detailed guidelines for safe storage to mitigate ignition sources. Unique risks include from self-heating in contaminated or improperly stored batches, and regulatory gaps in classification necessitate site-specific suppression plans rather than generic extinguisher use. These fires share some behavioral similarities with combustible metal fires in their oxygen independence but demand distinct chemical-specific protocols.

Comparative Analysis

Regional Differences in Labeling

Fire classification systems vary across regions, leading to different labels for the same types of fires, which can complicate international practices. In the United States, under the (NFPA) standards, fires are categorized into classes A (ordinary combustibles), B (flammable liquids and gases), C (energized electrical equipment), D (combustible metals), and K (cooking oils and fats). In contrast, the follows EN 2 standards, using classes A (ordinary combustibles), B (flammable liquids), C (flammable gases), D (combustible metals), and F (cooking oils and fats), with electrical fires typically treated under other classes once de-energized. aligns closely with the European system via AS 1841 and AS 2444, employing classes A, B (flammable liquids), C (flammable gases), D (combustible metals), E (electrical equipment), and F (cooking oils and fats). Key mappings between these systems highlight the overlaps and divergences: Class B encompasses both flammable liquids (/ Class B) and gases (/ Class C); Class C (electrical) corresponds to Class E, while in the , electrical fires lack a dedicated class; Class K aligns with / Class F for cooking fires; and Class D matches / Class D for metals. Ordinary combustibles remain consistently Class A across all regions. These label differences arise from historical priorities: the system, developed through NFPA in the early , emphasized electrical hazards due to widespread and combined liquids/gases under B for in contexts; and systems, influenced by efforts, separated gases (Class C) to address distinct suppression needs in chemical and energy sectors. No universal ISO standard for fire class labeling exists yet, though ISO 7165 provides performance testing guidelines that regions adapt independently. Visual identification of fire classes often relies on standardized pictograms on extinguishers, promoting quick recognition despite label variations. The table below summarizes common symbols across systems, where applicable:
Fire TypeUS (NFPA) SymbolEU (EN 2) SymbolAU (AS) Symbol
Ordinary Combustibles (Class A)Green triangle; wood crib or trash bin with flamesGreen triangle; burning wood pileGreen triangle; burning wood crib
Flammable Liquids (Class B)Red square; burning liquid spill or fuel containerRed square; burning liquid poolRed square; burning petrol puddle
Flammable Gases (US B; EU/AU C)(Included in B: gas cylinder icon)Blue circle; burning gas cylinderBlue circle; ignited gas canister
Electrical (US C; AU E)Blue circle; live electrical plug with arcs(No dedicated; crossed-out water on electrical)Blue circle; sparking electrical outlet
Cooking Oils/Fats (US K; EU/AU F)Yellow decagon; frying pan with flamesYellow decagon; burning oil in panYellow decagon; chip pan fire
Combustible Metals (Class D)Yellow star; burning metal powderYellow star; molten metal spillYellow star; ignited magnesium
These pictograms, derived from international conventions like for safety signs, use geometric shapes and imagery to denote hazards universally. A practical example of these differences is the ABC-rated extinguisher, which uses dry chemical agents effective against ordinary combustibles (/ A), flammable liquids (/ B), and electrical fires ( E; unclassified in once de-energized), but may require verification for gases (/ C) or cooking fires (/ F). This overlap aids portability in global settings but underscores the need for region-specific training to avoid mismatches.

Implications for Fire Safety Equipment

Fire classification systems directly influence the selection of portable fire extinguishers, ensuring compatibility between the extinguishing and the fire type to maximize and minimize risks. For instance, Class A fires involving ordinary combustibles like or are best addressed with water-based or extinguishers, which cool and soak the material to prevent re-ignition. In contrast, Class B fires from flammable liquids such as require non-conductive agents like dry chemical powder or (CO2) to smother the flames without spreading the fuel. Class D fires involving combustible metals, like magnesium, necessitate specialized dry powder agents that form a crust to exclude oxygen, as water can react violently with these materials. Multi-class rated extinguishers, such as types filled with multi-purpose dry chemical, are commonly selected for versatile environments like offices or commercial buildings, where multiple risks may coexist. These ratings indicate the extinguisher's capacity for each class—for example, a 4-A:40-B:C unit can handle a 4-foot deep Class A or a 40-square-foot —guiding placement based on hazard assessments per NFPA 10 standards. For from cooking oils, wet chemical extinguishers with potassium-based agents saponify the fats, creating a barrier; these are mandatory in commercial kitchens alongside portable units. Fixed suppression systems are designed around fire classes to provide automated protection in high-risk areas. Automatic sprinklers, effective primarily for Class A fires, activate individually to discharge and control fire spread in buildings, as outlined in NFPA 13. For Class C electrical equipment, clean agent systems using gases like FM-200 (heptafluoropropane) are preferred in data centers or server rooms, as they suppress fires by interrupting the without leaving residue or damaging electronics. In commercial kitchens, hood suppression systems with Class K wet chemical nozzles automatically discharge upon heat detection, protecting exhaust plenums and cooking appliances per NFPA 96 requirements. Proper and labeling are critical to use, with standards mandating pictograms to visually indicate suitable classes and hazards. NFPA 10 requires extinguisher labels to display class ratings, agent type, and usage instructions, while OSHA emphasizes employee on recognition to prevent misuse. Using an incompatible extinguisher, such as water on a , can spread flammable liquids across surfaces, intensifying the blaze and endangering occupants. Similarly, applying water to electrical fires risks , underscoring the need for non-conductive agents in Class C scenarios. Global trade in equipment presents challenges due to varying schemes, such as the U.S. system versus Europe's A-B-C-D , often requiring dual labeling for export compliance with standards like UL (U.S.) and EN 3 (EU). Post-2020 developments, including NFPA 855 updates for systems (as of the 2023 edition), address lithium-ion battery fires, which are treated as Class B and C hazards due to flammable electrolytes and energized components, along with risks—recommending specialized suppression like or clean agents to handle re-ignition risks without water, which exacerbates gas production.

References

  1. [1]
    Fire Extinguisher Types - NFPA
    Aug 1, 2023 · Class A Fires. Fires in ordinary combustible materials, such as wood, cloth, paper, rubber, and many plastics. ; Class B Fires. Fires in ...
  2. [2]
    NFPA 10-2018: Standard for Portable Fire Extinguishers
    Dec 7, 2017 · According to NFPA 10-2018, there are five primary classes of fire: Class A: result from ordinary combustible materials, including wood ...Missing: summary | Show results with:summary
  3. [3]
    ISO 3941:2007 - Classification of fires
    In stockISO 3941:2007 classifies, into five categories, the different kinds of fires defined in terms of the nature of the fuel.
  4. [4]
    Definition: Fire Classification | Firewize
    Fire classification is a system or method of categorising a fire according to the type(s) of fuel and if live electrical equipment is present.
  5. [5]
    [PDF] Fire Protection and Prevention - OSHA
    Fires are classified as A, B, C, D or K based on the type of substance that is the fuel for the fire, as follows: Class A—fires involving ordinary combustibles, ...
  6. [6]
    All About Fire: A Guide for Reporters - NFPA
    Classifying fire · Class A: Ordinary combustible materials, such as wood, cloth, paper, rubber and many plastics. · Class B: Flammable liquids (burn at room ...
  7. [7]
    Classes of Fires & Fire Extinguishers - Safety - UCLA Health
    It is important to use the right type of extinguisher on the specific class of fire to avoid personal injury or damage to property. The wrong type of ...
  8. [8]
    Origins of Public Protection Grading | How the Program Works | PPC
    The grading system originated after major fires in the early 1900s, developed by NBFU, and has been used by insurers since 1909.
  9. [9]
    The Early Development of Fire Extinguishers | F.F.A.M.
    Sep 22, 2024 · Classes of Fire UL's testing and fire class rating procedures for extinguishers became a recognized system in the United States. Early on UL ...Missing: AB | Show results with:AB
  10. [10]
  11. [11]
  12. [12]
    The History of fire extinguishers - Genesis Fire Protection
    May 4, 2017 · The first fire extinguisher was patented in 1723. Chemical foam was invented in 1904, carbon dioxide in 1924, and dry chemical in 1928.
  13. [13]
    NFPA 10 Standard Development
    1969 Standard for Portable Fire Extinguishers, 1968 Standard for Portable Fire Extinguishers, 1967 Standard for Portable Fire Extinguishers, 1966 Standard for ...Missing: history | Show results with:history
  14. [14]
    What Is a Class K Fire Extinguisher? - NFPA
    Aug 12, 2024 · Class K fire extinguishers are required by NFPA 10 to be installed within 30 ft (9 m) of any areas with a potential for Class K fires. For more ...
  15. [15]
  16. [16]
    Understanding OSHA's 29 CFR 1910.157: Portable Fire Extinguishers
    Apr 16, 2025 · The regulation references NFPA standards for guidance on extinguisher types and distribution patterns. Why It Matters. Compliance with 29 CFR ...
  17. [17]
    Choosing and Using Fire Extinguishers - U.S. Fire Administration
    Always look for the “UL Listed” or “ULC Listed” label on a fire extinguisher to ensure it is certified for use by a nationally recognized testing laboratory.
  18. [18]
    Fire Extinguisher Testing and Certification - UL Solutions
    UL Listed extinguishers can be marketed anywhere, based on their proven ability to extinguish specific classes of fires. We use full-scale flammable liquid and ...
  19. [19]
    Learn More about NFPA | The National Fire Protection Association
    Founded in 1896, NFPA is a self-funded nonprofit that's dedicated to the elimination of global loss from fire, electrical, and related hazards. Learn more.History · NFPA Awards · NFPA Leadership · Customer Support
  20. [20]
  21. [21]
  22. [22]
    Directive 2014/68/EU - pressure equipment - EU-OSHA
    Oct 20, 2023 · Directive 2014/68/EU applies to the design, manufacture and conformity assessment of stationary pressure equipment with a maximum allowable pressure greater ...
  23. [23]
    Fire safety in Europe 1992 - ScienceDirect.com
    In this article the various developments in the field of fire safety regarding the single European market, foreseen by 1992, are reviewed.Missing: Union | Show results with:Union
  24. [24]
    Fire extinguisher types and fire classes in Australia
    There are six classes of fire: Class A, Class B, Class C, Class D, Class E, and Class F. – Class A fires – combustible materials: caused by flammable solids, ...Missing: 2444 | Show results with:2444
  25. [25]
    Fire Classifications for Fire Extinguishers - Firewize
    Nov 17, 2020 · Class E - Electrical Equipment. A Class E fire is one that involves electrical equipment. Electrical equipment includes any machine powered ...<|control11|><|separator|>
  26. [26]
    ISO 7165:2009 - Fire fighting — Portable fire extinguishers
    ISO 7165:2009 specifies the principal requirements intended to ensure the safety, reliability and performance of portable fire extinguishers.Missing: testing | Show results with:testing
  27. [27]
    Malaysia Portable Foam Fire Extinguisher Market Size 2026-2033
    Sep 3, 2025 · ... Adoption Challenges:</strong> The market faces challenges related to ... ISO 7165 and MS 1539, driving demand for reliable fire ...
  28. [28]
    Bushfire protection | YourHome
    Australian Standard AS 3959:2018 specifies building membranes with a flammability index of less than 5. However, testing has shown that breathable non- ...Missing: extinguisher | Show results with:extinguisher<|separator|>
  29. [29]
    1.4.2 The Classification of Fires - Canadian Roofing Contractors ...
    Mar 19, 2020 · The four classifications of fires are: Class A – Ordinary Combustibles, Class B – Flammable Liquids, Class C – Electrical Equipment, Class D – Combustible ...
  30. [30]
    Regarding Hazardous Materials in the Fire Service Act
    Hazardous materials in the Japanese Fire Service Act are classified into six categories, from Category I to Category VI, based on their chemical and physical ...
  31. [31]
  32. [32]
    Emergency planning | WorkSafe.qld.gov.au
    Oct 4, 2018 · Under section 359 of the WHS Regulation, a PCBU must ensure the workplace is provided with fire protection and firefighting equipment that is ...
  33. [33]
    CLASS A FOAM FOR STUCTURE FIREFIGHTING - Fire Engineering
    Jul 1, 1992 · Add Class A foam concentrate to water, forming a foam solution that when applied to a surface will spread, wet, and penetrate, absorbing heat and cooling fuels.
  34. [34]
    Fire Extinguisher Ratings - NFPA
    Aug 26, 2022 · Class A Fires. Class A fires. Fires in ordinary combustible materials, such as wood, cloth, paper, rubber, and many plastics. ; Class B Fires.Missing: summary | Show results with:summary
  35. [35]
    UL 711 - Rating and Fire Testing of Fire Extinguishers - UL Standards
    Aug 6, 2018 · These requirements cover rating, and performance during fire tests, of fire extinguishers intended for use in attacking Class A, B, C, D, and K fires.
  36. [36]
    Flammable Liquids Classes & Categories - Chemical Strategies, Inc.
    Jul 30, 2019 · According to NFPA, a flammable liquid is a liquid with a closed-cup flash point less than 100°F (38°C). A combustible liquid is a liquid with a ...
  37. [37]
    Fire Extinguisher Ratings [Complete Guide] | Scutum South East
    Rating 4.5 (46) In the USA, flammable liquid and flammable gas fires both fall under Class B – in the UK and Australia, these are Class B and C, respectively.
  38. [38]
    6 Fire Extinguisher Classes In Australia - Fire Equipment Online
    Rating 5.0 (1) May 3, 2020 · Class A – Ordinary combustibles · Class B – Flammable liquids · Class C – Flammable gases · Class D – Combustible metals · Class E – Electrical ...
  39. [39]
    Class B Fire: Definition, Causes, and Extinguishing Techniques
    Class B fires spread quickly and usually involve flammable or combustible liquids like alcohol, oil, and gasoline. Mishandling fuels or chemicals in labs, gas ...
  40. [40]
    Class B Fires: Risks, Causes, and Prevention Methods
    Class B fires involve flammable liquids and flammable gases ... Extreme heat increases vapor production from flammable liquids, creating explosive atmospheres in ...
  41. [41]
  42. [42]
    "FIGHTING FLAMMABLE LIQUID FIRES: A PRIMER, PART 2"
    Feb 1, 1993 · Any Class B foam will extinguish a fire involving nonpolar hydrocarbons, such as gasoline, diesel, or kerosene. Not all Class B foams will ...
  43. [43]
    Fire extinguisher ratings explained - uk-preppers.co.uk
    A class B test will consist of varying sizes of trays and the amount liquid containing the tray is split in two parts, two parts heptane to every one-part water ...
  44. [44]
    AS 1841- Portable fire extinguishers General Requirements
    AS 1841 is the Australian standard that sets the rules for making sure portable fire extinguishers are safe, well-built, and work properly.Missing: bushfire adaptations
  45. [45]
    When Would It Be Dangerous to Use a Carbon Dioxide Fire ...
    Jan 21, 2021 · Asphyxiation – If a carbon dioxide extinguisher is used in an enclosed or poorly ventilated area, there is a serious risk of asphyxiation.
  46. [46]
    What are the different fire classes and how a fire occurs? BIOEX
    Polar solvents are hydrophilic (water attractive), they are water-mixable. Using AFFF on polar solvent fire will cause the foam to break down and will quickly ...Missing: polarity | Show results with:polarity
  47. [47]
    Class D Fires - The ANSI Blog
    Jan 28, 2019 · The combustible metals that can set off Class D fires typically include magnesium, titanium, zirconium, sodium, lithium, and potassium.
  48. [48]
    Classes of Fire as per ISO/NFPA and how to extinguish each
    Nov 16, 2022 · As per ISO Standard 3941, there are 5 main classes of fire depending on the fuel source. These are: Class A Fire.
  49. [49]
    Proper Handling of Combustible Metal Fires - Fire Engineering
    Feb 1, 2008 · Most combustible metals involved in fire produce extreme temperatures ranging from 5,000°F to 8,500ºF. These temperatures result in the ...
  50. [50]
    Why Are Class D Fires So Dangerous? - Firetrace International
    Apr 30, 2025 · Class D fires involve combustible metals and are uniquely dangerous due to their extreme temperatures, violent chemical reactions, ...
  51. [51]
    Class D Fire Extinguishing Methods | Combustible Fire Safety Guide
    Oct 7, 2024 · Class D fires are types of fires fueled by combustible metals such as magnesium, titanium, sodium, zirconium, lithium, and potassium.
  52. [52]
    Lithium Battery Incidents - Federal Aviation Administration
    Aug 31, 2022 · These are lithium battery related events involving smoke, fire, or extreme heat that the FAA is aware of and should not be considered a complete listing of all ...
  53. [53]
    Extinguishers For Metals - Fire Extinguisher Guide
    Sodium Chloride fire extinguishers are designed for use on Class D fires involving magnesium, sodium, and potassium. They can also be used on fires ...
  54. [54]
  55. [55]
    Understand Fire Extinguisher Ratings - Holmes Fire & Safety Solutions
    (In practice, users often read the rating as square feet – e.g. a 10B is said to cover a 10 ft² fire – but UL's actual test fire is larger for a safety margin.) ...
  56. [56]
  57. [57]
    [PDF] Fire hazards in chemical plant from friction sparks involving the ...
    SYNOPSIS. Impacts involving aluminium and rusty mild steel can initiate a thermite reaction. It is shown that the glancing impact of stainless steel, ...
  58. [58]
    (PDF) Auto-Ignition of Cooking Oils (2010) | Krystyna Buda-Ortins
    The auto-ignition temperatures for the oils were determined to be as follows: canola oil: 424, vegetable oil: 406 and olive oil: 435. The flame point of canola ...
  59. [59]
    5 types of fire extinguishers: A guide to using the right class
    Aug 26, 2023 · Carbon Dioxide (CO2) extinguishers are used on fires involving burning liquids (Class B), and electrical fires, such as of large computer ...
  60. [60]
    [PDF] The Most Flammable Cooking - Utah.gov
    A flashpoint is the temperature at which an oil creates flammable vapors that when exposed to heat can cause a fire. For most cooking oils, the flashpoint is ...
  61. [61]
    Practical Aspects of Analyzing Vegetable Oils in Fire Debris* - 2009
    Jun 23, 2009 · Abstract: Vegetable oils undergo burning, self-heating, and spontaneous ignition, resulting in their presence in fire debris.Missing: cooking re-
  62. [62]
    Characterization of Stovetop Cooking Oil Fires - PMC - NIH
    Both gas and electric ranges were tested. The amount of oil and types of cooking pans were varied in the experiments. Oil was heated on a cook top burner until ...
  63. [63]
    Saponification and Fire Suppression Systems - State Systems Inc
    Feb 20, 2025 · – Unlike standard extinguishers, wet chemical agents react with the oil to create a non-combustible barrier, fully extinguishing the fire.
  64. [64]
    What is a Class K Fire Extinguisher - Getz Fire Equipment
    Feb 4, 2019 · Class K fire extinguishers work by saponification. Saponification takes place when alkaline mixtures are applied to burning cooking oil or fat ...
  65. [65]
    [PDF] What is a Class K Fire?
    2 - Class K fire extinguishers shall be provided for cooking appliance hazards that involve combustible cooking media (vegetable oils and animal oils and fats).Missing: definition | Show results with:definition<|control11|><|separator|>
  66. [66]
    Understanding Class F Fires and Fire Extinguisher Ratings - Fireology
    Oct 25, 2023 · For example, a 75F-rated fire extinguisher can be used on all deep fat fryers that are 75 litres and below. It's crucial to select an ...
  67. [67]
    What is a Class K fire? - Amerex Fire Systems
    Aug 27, 2024 · The fire classification of K for fires in “cooking appliances that involve combustible cooking media,” which was introduced in the early 1990s ...
  68. [68]
    Fire classes - EMME Antincendio
    The standard defines 5 fire classes; the fire classes are used to determine the extinguishing capability of fire extinguishers - Find out the details.Missing: Union | Show results with:Union
  69. [69]
    Arcing Explained: Types, Causes, and Role in Fires - Blazestack
    Dec 15, 2024 · Arcing involves the flow of electric current through a gas or a gap in a circuit and can play a major role in the ignition of fires. By ...Types Of Arcing · Role Of Arcing In Fire... · Identifying Arcing In Fire...
  70. [70]
    Electrical Fires: Causes and Safety Tips | SafetyCulture
    Sep 25, 2025 · The class can vary depending on your jurisdiction, as follows: Class C (US), Electrical (UK), and Class E (EU). Once you've selected the ...
  71. [71]
    EPA Bans PCB Manufacture; Phases Out Uses
    Aug 8, 2016 · The Environmental Protection Agency today issued final regulations banning the manufacture of polychlorinated biphenyls (PCBs) and phasing out most PCB uses.Missing: hazards | Show results with:hazards
  72. [72]
    Learn About Oxidizers After Georgia Chemical Plant Fire - NFPA
    Oct 11, 2024 · NFPA 400, Hazardous Materials Code, defines oxidizers as “any solid or liquid material that readily yields oxygen or other oxidizing gas or ...
  73. [73]
    Can Fire Burn When There's No Oxygen? - ScienceABC
    Jun 12, 2019 · Compounds containing these reactive non-metals, such as carbon trichloride, can burn metals in the absence of oxygen. What is this?Missing: sustaining | Show results with:sustaining
  74. [74]
    Responding to incidents involving oxidizers takes awareness and ...
    May 9, 2022 · A good definition of oxidizers can be found in NFPA 400, Hazardous Materials Code, 2022 edition. Oxidizers are: “Any solid or liquid material ...
  75. [75]
    NFPA 400, Hazardous Materials Code (2025)
    3-day delivery 30-day returnsNFPA 400 consolidates the requirements for oxidizers, organic peroxides, pesticides, and ammonium nitrate based on requirements from these previous stand-alone ...
  76. [76]
    Ammonium nitrate | H3N.HNO3 | CID 22985 - PubChem
    Accelerates the burning of combustible material. Produces toxic oxides of nitrogen during combustion. Used to make fertilizers and explosives, and as a nutrient ...
  77. [77]
    Beirut explosion: What we know so far - BBC
    Aug 11, 2020 · A fire appears to have triggered the explosion of the ammonium nitrate in Beirut. Lebanese broadcaster LBCI and Reuters news agency cited ...
  78. [78]
    Lessons in ammonium nitrate - Firefighting in Canada
    Fires involving AN cannot be extinguished by oxygen deprivation. Water is the most effective means of fire fighting (it acts like a heat sink).
  79. [79]
    Luperox ® organic peroxide safety precautions
    Organic peroxide fires are more difficult to extinguish and do greater damage to storage facilities than fires involving common flammable and combustible ...
  80. [80]
  81. [81]
  82. [82]
    [PDF] FIRES CLASSIFICATION
    BS EN 2 is a standard about classification of fires that used in UK and European countries. In BS EN 2, fire is also divided into 5 classes. The difference ...Missing: Union | Show results with:Union
  83. [83]
  84. [84]
    What Do the Symbols on a Fire Extinguisher Indicate? - Hiller Fire
    Symbols on fire extinguishers indicate the type of fire they are designed for. Multiple symbols mean the extinguisher can handle multiple fire classes. ...Missing: Australia | Show results with:Australia
  85. [85]
    Types of Sprinkler Systems | NFPA
    Mar 26, 2021 · Types of sprinkler systems permissible by NFPA 13, Standard for the Installation of Sprinkler Systems, are wet, dry, preaction, and deluge.
  86. [86]
    Clean Agent System Basics - NFPA
    May 6, 2022 · In the event of a fire clean agent systems are activated by a suppression releasing panel which detects the fire using automatic detection.
  87. [87]
    Restaurant Fire Protection Basics - NFPA
    Apr 27, 2021 · Extinguishers in kitchens need to be Class K to be appropriate for use on the cooking medium. Signage is required at the extinguisher in the ...
  88. [88]
    Guide to Fire Extinguisher Inspection, Testing, and Maintenance
    Oct 30, 2020 · This blog will address the NFPA 10, Standard for Portable Fire Extinguishers, requirements that help ensure your extinguisher is ready.
  89. [89]
    Harmonization of Standards for Fire Protection, Detection, and ...
    Jul 22, 2016 · Codifies the use of UL standards for testing and labeling of fire extinguishers. These standards provide detailed, technical requirements ...Missing: dual | Show results with:dual
  90. [90]
    Lithium-Ion Battery Safety - NFPA
    Lithium-ion batteries can overheat, catch fire, or explode if damaged or improperly used, charged, or stored. Buy, charge, and recycle safely.