Fact-checked by Grok 2 weeks ago

Media Redundancy Protocol

The Media Redundancy Protocol (MRP) is a standardized recovery designed for high-availability industrial systems, operating on topologies to ensure deterministic against single points of in Ethernet-based communications. Defined in the (IEC) standard IEC 62439-2:2021, part of the IEC 62439 series for high-availability networks, MRP enables rapid reconfiguration of the upon detection of a link or switch , with configurable recovery times as low as 10 ms (typically 200 ms for up to 50 nodes) to minimize in time-critical applications such as and process control. In MRP ring configurations, one designated device serves as the Media Redundancy Manager (MRM), which blocks traffic on one of its to prevent loops and maintain a logical , while other devices act as Media Redundancy Clients (MRC) that forward frames normally. The MRM periodically sends test frames around the ring to monitor integrity; upon detecting a —such as a break or device outage—it unblocks the port and floods the network to relearn MAC addresses, restoring connectivity without manual intervention. This protocol supports up to 50 nodes per ring and is compatible with protocols like , allowing integration into larger redundant architectures while adhering to defined recovery profiles (e.g., 10 ms, 30 ms, 200 ms, or 500 ms) for varying network sizes and requirements. MRP's deterministic behavior and low latency make it particularly suited for environments where even brief disruptions can impact safety and productivity, and it can interconnect multiple rings for enhanced scalability.

Overview

Definition and Purpose

The Media Redundancy Protocol (MRP) is a standardized Layer 2 Ethernet protocol defined in IEC 62439-2, designed to provide seamless redundancy in ring-based network topologies for high-availability automation systems. It achieves this by logically opening the ring at a designated point to eliminate loops and broadcast storms, while enabling rapid reconfiguration in the event of a single link or node failure. This deterministic recovery mechanism ensures that network disruptions are minimized, supporting the stringent requirements of environments where can have significant operational impacts. The primary purpose of MRP is to address single points of failure in industrial automation networks, such as those used in process control, manufacturing, and real-time systems, by delivering fault recovery times typically under 200 milliseconds—far outperforming traditional protocols like Spanning Tree Protocol (STP), which can take several seconds to reconverge. This speed is critical for maintaining continuous operation in mission-critical applications, where even brief interruptions could lead to production losses or safety risks. By focusing on ring topologies, MRP enhances overall network reliability without the scalability limitations of STP in larger deployments. MRP operates at the Media Access Control (MAC) layer, independent of higher-layer protocols, which allows it to integrate with industrial Ethernet standards like PROFINET and EtherNet/IP while preserving deterministic behavior essential for time-sensitive data transmission. This layer-2 approach ensures low-latency fault detection and recovery, making it particularly suited for environments demanding high uptime and predictable performance, such as automated factories and utility systems.

Historical Development

The Media Redundancy Protocol (MRP) originated from Hirschmann Automation and Control's proprietary HiPER-Ring protocol, which was introduced in 1998 to provide rapid fault recovery in ring topologies. HiPER-Ring was designed to address the need for sub-second network restoration in environments, compensating for single points of failure within a maximum switchover time of 500 milliseconds, thereby enabling more reliable ring-based architectures for time-sensitive industrial applications. In the early 2000s, the protocol evolved in response to the rapid growth of Industrial Ethernet standards such as , introduced around 2003, and , which gained prominence from 2000 onward, both demanding faster redundancy mechanisms than those offered by the Rapid Spanning Tree Protocol (RSTP). RSTP's recovery times, often spanning several seconds, proved inadequate for industrial control systems, prompting enhancements to HiPER-Ring for deterministic, millisecond-level in ring networks supporting up to 50 devices. This development facilitated broader adoption following 's acquisition of Hirschmann in March 2007, which integrated the technology into a wider portfolio of industrial networking solutions. MRP achieved formal standardization as part of the International Electrotechnical Commission's IEC 62439 series, with the first edition of IEC 62439-2 published in February 2010, specifying MRP for high-availability networks based on . Amendments and revisions in subsequent years, including updates around 2012 to the broader IEC 62439 framework, refined recovery parameters and improved interoperability across diverse implementations. The standard was further revised in its second edition in 2016 and third edition in 2021, with a technical corrigendum issued in 2023 to address minor clarifications and enhancements.

Protocol Architecture

Components and Roles

The Media Redundancy Protocol (MRP) architecture relies on two primary components: the Media Redundancy Manager (MRM) and the Media Redundancy Clients (MRCs). The MRM serves as the central controller in the , responsible for monitoring the overall topology and coordinating responses to maintain network integrity. It operates by transmitting periodic test frames through the ports to verify connectivity and detect potential issues, ensuring that the network remains loop-free under normal conditions. Only one MRM is permitted per to prevent conflicting control actions that could disrupt operations. In contrast, MRCs function as passive participants that support the MRM's oversight without independently managing the . Each MRC forwards MRP control frames, such as test frames, between its designated ring ports and provides status updates on conditions when queried or when changes occur. This relaying mechanism allows the MRM to assess the ring's health across all nodes. MRCs do not initiate changes but respond promptly to directives from the MRM, such as reconfiguration signals, to align with the updated network state. The interactions between the MRM and MRCs form the foundation of MRP's redundancy mechanism in a ring topology, typically supporting up to 50 devices. The MRM blocks one of its ring ports during operation to logically transform the ring into a line, preventing broadcast storms while allowing traffic to flow efficiently. All devices, including the MRM and MRCs, must be configured with two dedicated ring ports that exclusively handle MRP communications, ensuring isolation from other network traffic via optional tagging. This setup enables seamless frame propagation, where test frames circulate the ring and return to the MRM, confirming operational status.

Port States and Ring Topology

The Media Redundancy Protocol (MRP) operates on a physical topology consisting of Ethernet switches interconnected via dedicated ring ports, forming a closed loop that provides redundant paths for data transmission. To prevent network loops and broadcast storms, the is logically opened by blocking traffic on one segment, typically managed by the Media Redundancy Manager (MRM) node, while other nodes act as Media Redundancy Clients (MRCs). This configuration ensures seamless redundancy without requiring protocols, adhering to the IEC 62439-2 standard for networks. MRP defines three primary states for ring ports to control frame forwarding and maintain network integrity: disabled, blocked, and forwarding. In the disabled state, the port drops all incoming and outgoing frames, effectively isolating the port and preventing any traffic participation, which is used for inactive rings or during initial configuration. The blocked state allows only MRP control frames—such as test and topology change notifications—and certain standard frames like Link Layer Discovery Protocol (LLDP) to pass through, while dropping all data frames to preserve the logical openness of the ring and avoid loops. In contrast, the forwarding state enables normal operation, where the port transmits and receives all frames, including data and MRP control traffic, to support full connectivity. During normal operation, known as the ring-closed , the MRM designates one of its ring s as blocked to eliminate the loop, while its other and all MRC remain in the forwarding , creating a logical tree-like for efficient . Upon detecting a , such as a break, the transitions to the ring-open , where the MRM unblocks its previously blocked and sets both to forwarding, allowing all ring to forward traffic and restore end-to-end connectivity through the redundant path. This management by the MRM and s ensures rapid reconfiguration while minimizing disruptions in industrial environments.

Technical Details

Key Properties

The Media Redundancy Protocol (MRP) operates at the Media Access Control (MAC) sublayer of the (Layer 2) in the , making it transparent to higher-layer protocols and applications. This Layer 2 functionality ensures seamless integration without requiring modifications to upper-layer communications, thereby maintaining compatibility with protocols such as and . In terms of frame handling, MRP enforces strict rules based on port states to maintain network integrity in a ring . Disabled ports drop all incoming frames to isolate faulty segments completely. Blocked ports, typically one per ring managed by the Media Redundancy Manager (MRM), forward only MRP-specific control frames—such as test and topology change frames—while discarding all other frames to prevent loops. Forwarding ports process all Ethernet frames normally according to standard bridging rules, allowing unrestricted . MRP delivers deterministic network behavior, enabling sub-second recovery from failures without the need for reconfiguring addresses, VLANs, or other network parameters. This predictability supports ring topologies with up to 50 devices, where the protocol automatically reconfigures paths upon detecting issues, ensuring minimal disruption to industrial communications. MRP supports configurable recovery profiles per IEC 62439-2, with worst-case recovery times of 30 ms, 200 ms, or 500 ms for rings up to 50 nodes. Additional properties enhance MRP's suitability for industrial environments, including support for hot-swappable devices that can be inserted or removed without halting the network, as the protocol detects and adapts to such changes deterministically. Furthermore, MRP facilitates load balancing by permitting user traffic to flow in both directions around the ring when feasible, optimizing utilization beyond mere .

Frame Structure

The Media Redundancy Protocol (MRP) utilizes standard Ethernet II frames for communication within ring topologies. These frames feature a fixed destination of 01-15-4E-00-00-01 for MRP Test frames and 01-15-4E-00-00-02 for control frames, with the source set to that of the transmitting device. The field is specified as 0x88E3, designating the frame as part of the slow protocols to ensure low-priority handling and prevent interference with data traffic. The of an MRP employs a Type-- (TLV) encoding scheme to structure its content efficiently. The TLV header consists of a 2-octet Type field, a 2-octet field indicating the size of the portion, and the variable-length field containing the actual data. MRP include Test for ring monitoring, for reporting status changes, and for notifying alterations. Nested sub-TLVs may be included within the Value field for additional parameters, such as organization-specific extensions. Key fields within the MRP include a 1-octet Version field (typically set to 0x01 for MRP version 1.0), a 1-octet State field (with values 0x00 indicating a closed ring and 0x01 an open ring), and a 4-octet Sequence ID for uniquely identifying frames to detect duplicates or losses. Optional fields allow for custom data from implementing organizations, but the overall frame length is constrained to a minimum of 64 bytes and a maximum of 1500 bytes to avoid fragmentation and ensure compatibility with standard Ethernet MTU limits. MRP defines three primary control frame types to manage ring operations. Test frames are transmitted periodically by the Media Redundancy Manager (MRM) in both directions around the to verify and detect faults. LinkChange frames are issued by Media Redundancy Clients (MRCs) to report detected link issues to the MRM. TopologyChange frames are generated by the MRM to notify the network of changes, enabling synchronized state across the network. These frames collectively support the protocol's fault-tolerant mechanisms without introducing loops.
FieldSize (octets)Description
Destination MAC6Multicast: 01-15-4E-00-00-01 (Test) or 01-15-4E-00-00-02 ()
Source MAC6 of sending port
EtherType20x88E3 (Slow Protocols)
Version1Protocol version (e.g., 0x01)
Type2TLV type (e.g., for Test, LinkChange, or TopologyChange)
Length2Length of Value field
ValueVariableIncludes Ring State (1 octet), Sequence ID (4 octets), and optional data
FCS4
This structure ensures deterministic processing and minimal overhead in industrial environments.

Fault Detection and Recovery Process

The Media Redundancy Manager (MRM) in MRP continuously monitors the ring topology by transmitting bidirectional MRP Test frames from both of its ring ports, typically at intervals of 20 ms, which is configurable per the protocol specifications. These Test frames circulate around the ring and return to the MRM, allowing it to verify the integrity of all links and devices; the absence of a returning Test frame after a maximum number of transmission attempts (default MRP_TSTNRmax of 3, resulting in approximately 60 ms) signals a fault, such as a link failure or device malfunction. Media Redundancy Clients (MRCs) also contribute to detection by immediately notifying the MRM of local port issues via MRP LinkChange frames (subtypes Linkdown or Linkup) upon sensing a change in link status. Upon fault detection, the recovery process initiates automatically to restore connectivity without loops. The MRM unblocks its previously blocked port, transitioning both ring ports to a forwarding state, and floods the network with MRP TopologyChange frames from both directions to alert all MRCs of the topology alteration. MRCs update their port statuses accordingly upon receiving the TopologyChange frames: devices adjacent to the fault disable the affected port while forwarding on the alternate path, and others enable forwarding on both ports to form a linear bus topology. During this phase, MRCs clear their filtering databases (FDBs) and relearn MAC addresses based on the new paths, ensuring traffic reroutes via the substitute route while the MRM continues sending Test frames to confirm the reconfiguration. The ring state shifts from Closed to Open, maintaining data flow through the redundant path. Reconfiguration to the original ring topology occurs automatically once the fault clears. The MRM detects the resolution when Test frames begin returning successfully via the full ring path, prompting it to block one port again and broadcast MRP TopologyChange frames to the MRCs. MRCs then revert their port states, reblocking as needed to restore the Closed ring configuration and repopulating their FDBs with the primary topology information. This process supports partial recovery in cases of multiple faults if they occur within the ring's limits, but full restoration relies on verifying a single operational path through ongoing Test frame circulation. MRP's error handling is optimized for reliability under single-fault conditions, reliably recovering from one simultaneous by isolating the issue and activating the . For multiple concurrent faults, the may achieve partial reconfiguration if at least one remains viable, but severe cases (e.g., two or more link ) can result in network partitioning, necessitating manual intervention to diagnose and repair the underlying issues. The MRM logs events like ring-open signals or multiple-manager detections for troubleshooting, ensuring operators can address persistent errors.

Standards and Performance

IEC 62439-2 Specification

The IEC 62439-2 standard, first published in 2010 as the inaugural edition of the IEC 62439 series on industrial communication networks for high-availability , defines the Media Redundancy Protocol (MRP) as a dedicated recovery mechanism for ring topologies using Ethernet (ISO/IEC/IEEE 8802-3) technology. Subsequent editions include the second in 2016 and the third in 2021, which cancel and replace prior versions while maintaining MRP as the core focus of Part 2. Key clauses outline MRP's operational framework, including Clause 4 for protocol overview, Clause 5 for media redundancy behavior specifying requirements for the Media Redundancy Manager (MRM) and Media Redundancy Clients (MRCs), and Clause 8 for protocol specifications detailing frame formats and port state machines. The MRM requirements mandate control of ring closure by transmitting periodic MRP_Test frames and managing port states (DISABLED, BLOCKED, FORWARDING), while MRCs must forward these frames and clear their filtering databases upon topology changes. Frame formats, defined in Clause 8.1, include Protocol Data Units (PDUs) for MRP_Test, MRP_TopologyChange, and MRP_LinkChange with fields such as source/destination addresses, version indicators, and type-length-value (TLV) headers. State machines in Clause 8.2 govern MRM and MRC transitions, using timers and event triggers to handle ring states like closed or open. Conformance testing is addressed through Management Information Base (MIB) definitions in Clause 10, with provisions for ring size limits up to 50 devices and interoperability requirements ensuring compatibility with IEEE 802.1D bridging and support for multiple rings via unique domain IDs. The standard's scope is limited to Ethernet-based ring topologies in environments, excluding links or non-ring configurations, and requires at least one MRM per domain to enable deterministic fault . The 2021 edition introduces enhancements such as extensions for rates below 100 Mbit/s, improved Continuity Check for better fault detection, and new profiles for MRP interconnections to facilitate integration with other methods like parallel rings or coupling devices. These updates also include guidance on compatibility with and provisions for handling multiple topologies, promoting broader applicability in modern industrial setups.

Recovery Times and Limitations

The Media Redundancy Protocol (MRP) ensures deterministic recovery times for single network faults, as defined in the IEC 62439-2 standard. For ring topologies with up to 14 devices operating at 100 Mbps Ethernet, the maximum recovery time is 10 ms, enabling seamless continuity in time-critical industrial applications. Rings with up to 50 devices achieve a maximum recovery of 30 ms under the same conditions, while configurable profiles extend to 200 ms or 500 ms for larger configurations or compatibility with legacy systems. MRP provides single-fault tolerance, detecting and recovering from one link or device failure by transitioning to a ring-open state and propagating topology change notifications. Multiple simultaneous faults, however, can degrade performance to partial recovery or complete outage, as the protocol lacks mechanisms for concurrent error handling. The maximum ring size is limited to 50 devices to maintain these timing guarantees, beyond which propagation delays from test frames and reconfiguration messages exceed specified thresholds. Native support for multi-ring coupling requires extensions, such as MRP interconnection ports, to avoid loops across segments. Scalability in MRP is constrained by frame propagation delays, which increase linearly with due to the sequential flooding of control frames around the . At 100 Mbps, these delays are minimal for small rings but accumulate in larger ones, potentially impacting ; the protocol includes notes on compatibility with for reduced latency in modern deployments. Conformance testing mandates simulation of link failures to verify times, ensuring devices meet the standard's under worst-case scenarios like maximum and fault .

Applications and Comparisons

Industrial Use Cases

In factory , the Media Redundancy Protocol (MRP) is widely deployed in ring topologies to connect PROFINET-enabled devices such as programmable logic controllers (PLCs), sensors, and variable frequency drives, ensuring continuous operation in manufacturing environments. For instance, S7 PLCs and SCALANCE X industrial switches form redundant rings that support exchange for assembly lines and robotic systems, where even brief interruptions could halt production. This setup is particularly valuable in , as it allows for cost-effective wiring reductions while maintaining against common disruptions like cable damage from machinery vibration. In process industries, MRP enables fault-tolerant networks for applications requiring , such as chemical where precise monitoring and actuation are essential to prevent hazardous conditions. Phoenix Contact's network components, including gigabit switches and media converters, integrate MRP to create redundant structures that sustain communication during failures, supporting sectors like pharmaceuticals and oil refining. These deployments often link distributed control systems (DCS) with instruments, mitigating risks in environments exposed to corrosive substances or extreme temperatures. For smaller facilities, single-ring configurations with 10-20 managed switches suffice, accommodating up to 50 devices in a closed to provide seamless without complex infrastructure. In larger plants, multiple rings are coupled redundantly using protocols like MRP interconnection, as implemented with SCALANCE XC-300 series switches, to extend coverage across expansive areas while preserving overall network integrity. The protocol's benefits include recovery times of 10 ms or less upon fault detection, critical for safety-sensitive operations like controls in factories or continuous-flow processes in chemical plants, where could lead to damage or violations. MRP integrates natively with vendor-specific managed Ethernet switches, such as SCALANCE X and Industrial Ethernet 3500 series, facilitating easy configuration via tools like TIA Portal for environments. By design, it addresses prevalent challenges in harsh settings, including breaks from physical wear and switch failures due to dust or heat, through automatic path rerouting that minimizes operational disruptions.

Comparison with Other Protocols

The Media Redundancy Protocol (MRP), defined in IEC 62439-2, provides faster recovery times compared to the (STP) and its rapid variant (RSTP), with MRP achieving worst-case recovery times configurable to 10 ms, 30 ms, 200 ms, or 500 ms in ring topologies of up to 50 devices, with typical recovery times varying by profile and ring size (e.g., under 10 ms for the fastest profile). In contrast, RSTP, standardized in IEEE 802.1w, supports arbitrary network topologies but exhibits typical recovery of 100-200 ms in ring configurations with 40 devices and worst-case delays exceeding 2 seconds upon multiple losses. While STP/RSTP offers greater topological flexibility for complex networks, MRP's deterministic ring-based operation ensures more predictable (configurable from 10 ms to 500 ms worst-case), generally offering faster and more consistent recovery than STP/RSTP in ring topologies where the latter's non-deterministic reconvergence can introduce variability. Compared to the Parallel Redundancy Protocol (PRP) in IEC 62439-3, MRP employs a single ring with logical ring openness for , reducing wiring complexity and infrastructure costs without requiring duplicated networks. PRP, however, duplicates all communication paths across independent networks of any , delivering zero recovery time by parallel transmission and discarding duplicates at the , at the expense of doubled cabling, switches, and bandwidth usage. This makes MRP more economical for moderate-availability ring setups, whereas PRP suits mission-critical applications demanding seamless, topology-agnostic redundancy despite higher deployment overhead. MRP also contrasts with (HSR), another IEC 62439-3 protocol tailored for or coupled- topologies, where HSR achieves zero time through device-integrated duplex transmission and loop prevention, similar to PRP but without separate networks. HSR incurs 50% overhead from redundant frames and necessitates specialized hardware support at each , increasing costs for up to 512 devices, while MRP leverages standard switches with simpler software-based management for cost-effective under 50 ms in non-zero-downtime-tolerant scenarios. Selection criteria for MRP emphasize ring-based environments requiring sub-50 ms recovery without full infrastructure duplication, such as process automation where cost and wiring simplicity outweigh the need for zero-time . In scenarios demanding absolute seamlessness or flexible topologies, PRP or HSR may be chosen despite their higher expenses, while RSTP suffices for less stringent, non-ring networks.
ProtocolTopologyRecovery Time (Typical/Worst-Case)Key StrengthsKey WeaknessesRelative Cost
MRP (IEC 62439-2)Ring (up to 50 devices)Configurable: typical <10–60 ms / worst-case 10–500 ms (depending on profile)Deterministic, low-cost ring redundancyLimited to ringsModerate
RSTP (IEEE 802.1w)Arbitrary (rings up to 40 devices)100-200 ms / >2 sFlexible topologiesNon-deterministic, slowerLow
PRP (IEC 62439-3)Dual independent networks (any)0 ms / 0 msZero recovery, topology-agnosticDoubled infrastructureHigh
HSR (IEC 62439-3)Ring/coupled rings (up to 512 devices)0 ms / 0 msZero recovery in rings, single networkBandwidth overhead, device-specificHigh

References

  1. [1]
    IEC 62439-2:2021
    Dec 15, 2021 · The IEC 62439-2:2021 specifies a recovery protocol based on a ring topology, designed to react deterministically on a single failure of an inter-switch link.
  2. [2]
    Media Redundancy Protocol Configuration Guide for IE 2000 ... - Cisco
    Feb 13, 2023 · MRP, defined in International Electrotechnical Commission (IEC) standard 62439-2, provides fast convergence in a ring network topology for ...
  3. [3]
    Ring Protocol MRP (IEC 62439-2) | Media Redundancy ... - Perle
    Media Redundancy Protocol (MRP) is a standards-based protocol used in Ring topologies to avoid single points of failure by providing a recovery time of 10ms or ...
  4. [4]
    [PDF] Media Redundancy Protocol - Cisco
    Media Redundancy Protocol (MRP), defined in International Electrotechnical Commission (IEC) standard. 62439-2, provides fast convergence in a ring network ...
  5. [5]
    Support - MRP Technology White Paper-6W100 - H3C
    Jul 26, 2024 · MRP can eliminate loops and prevent broadcast storms in the ring network; it can also provide redundancy for nodes and links.
  6. [6]
    [PDF] MRP (IEC 62439-2) Functions User Guide - Lantronix
    Jun 12, 2013 · The Media Redundancy Protocol (MRP) specifies a recovery protocol based on a ring topology. One of the nodes has the role of a media redundancy ...
  7. [7]
    [PDF] Media Redundancy for PROFINET IO - Felser Engineering
    This protocol was called. HiPER-Ring and allowed the compensation of one single point of failure in the ring structure with a maximal switch over time of 500 ms ...
  8. [8]
    What is PROFINET? – PROFINET Explained - PI North America
    Feb 10, 2021 · It was introduced in the early 2000s and is the most well-adopted Industrial Ethernet solution. Since PROFINET is an open standard, hundreds ...
  9. [9]
    [PDF] Industrial Ethernet Technologies: Overview and Comparison
    First spec (V0. 9) published in March 2001 (EtherNet/IP was first introduced in 2000). Meanwhile CBA is not supported by Profibus International any more. The ...Missing: growth | Show results with:growth
  10. [10]
    Belden to buy Germany's Hirschmann for $260 mln - Reuters
    Aug 9, 2007 · The deal, expected to add to Belden's 2007 earnings, would close in 45 days and Hirschmann Chief Executive Officer Reinhard Sitzmann will ...Missing: date | Show results with:date
  11. [11]
    IEC 62439-2:2010
    Feb 26, 2010 · Under development IEC 62439-2 Edition 4.0 Stage code: ACD Forecast publication date 2028-05-31. History. Edition, Date, Publication, Edition ...
  12. [12]
  13. [13]
    [PDF] Media Redundancy Concepts | IPD
    This protocol is described in the IEC 62439 2 standard, which is the industry standard for high-availability Ethernet networks. MRP is specified only for ring.<|control11|><|separator|>
  14. [14]
    Redundancy for industrial communication networks
    Jul 7, 2011 · This is defined in IEC 62439, the industry standard for high availability networks. MRP is defined exclusively for ring networks, but guarantees ...
  15. [15]
  16. [16]
    PROFINET Media Redundancy + Media Redundancy
    MRP – Media Redundancy Protocol which offers a few milliseconds of recovery time in a network up to 50 switches and MRPD – Media Redundancy for Planned ...
  17. [17]
    Media Redundancy Protocol (MRP) - TIA Portal
    The "MRP" process works in conformity with the Media Redundancy Protocol (MRP) that is specified in the standard IEC 62439-2. Requirements. All devices in the ...
  18. [18]
    [PDF] INTERNATIONAL STANDARD
    – adding specifications of the HSR (High-availability Seamless Redundancy) protocol ... The Media Redundancy Protocol (MRP) specifies a recovery protocol based on ...
  19. [19]
    IEC 62439-2:2016
    Mar 30, 2016 · IEC 62439-2 Revised​​ This second edition cancels and replaces the first edition published in 2010. This edition constitutes a technical revision.
  20. [20]
    [PDF] SIST EN IEC 62439-2:2022 - iTeh Standards
    Jan 19, 2022 · a) improvements for the Continuity Check Protocol, b) introduction of further specifiers for the rings, the interconnection links, and the ...Missing: differences | Show results with:differences
  21. [21]
    Media Redundancy Protocol [Cisco Catalyst IE3200 Rugged Series]
    Sep 23, 2025 · MRP works with Spanning Tree Protocol (STP) to prevent unwanted broadcast loops in the event that a user accidentally connects a device that ...
  22. [22]
  23. [23]
    [PDF] Which PROFINET devices support media redundancy and which ...
    The PROFINET devices, which are part of this redundant network, form a so called MRP domain. MRP / MRPD is generally designed as a ring topology and therefore ...
  24. [24]
    Redundancy concepts – the process industry | Phoenix Contact
    Our range includes suitable network components for setting up a failsafe communication solution, e.g., with RSTP (Rapid Spanning Tree Protocol) or MRP (Media ...
  25. [25]
    Redundant Coupling of MRP Rings - ID: 109988447 - Support
    Jul 31, 2025 · In this application example we show on a concrete, simplified example, how redundant coupling of uninterruptible and interruptible redundancyMissing: MRRT | Show results with:MRRT
  26. [26]
    Configuring PRP - Cisco
    Parallel Redundancy Protocol (PRP) is defined in the International Standard IEC 62439-3. PRP is designed to provide hitless redundancy (zero recovery time ...Missing: comparison | Show results with:comparison<|separator|>