Rack unit

A rack unit (abbreviated as U or RU) is a standardized unit of measure equal to 1.75 inches (44.45 mm) in height, used to quantify the vertical space occupied by equipment mounted in 19-inch racks. This measurement ensures compatibility and modularity for electronic devices, with mounting holes spaced in a repeating pattern of 0.5 inches, followed by two 0.625-inch intervals, to secure panels within each unit. The rack unit originates from early 20th-century telephony practices, where established the format around 1922 to standardize space for and equipment, reducing installation footprints in central offices. By 1934, the standard incorporated 12-24 UNC screw holes for mounting, and it was formalized under the (EIA) as specification EIA-310-D in the 1990s, though the EIA dissolved in 2011 and its standards are now maintained by successor organizations. Compliance with EIA-310-D is voluntary but widely adopted to promote across manufacturers. Rack units are essential in diverse industries, including data centers for and , telecommunications for switching , and audio-visual production for amplifiers and mixers, where racks are typically 42U tall to maximize density while allowing for airflow and cabling. The standard also specifies a minimum rack opening width of 17.72 inches (450 mm) and a width of 19 inches (482.6 mm), facilitating global equipment exchange. Modern variations, such as open racks from the , build on these foundations to address evolving needs like higher power densities in .

Definition and Dimensions

Height Unit

The rack unit, abbreviated as U or RU, is a standardized unit of measure defined as exactly 1¾ inches (44.45 ) in height, used to quantify the vertical space occupied by equipment in a rack-mounted system. This dimension originates from the hole spacing pattern in rack rails, where one U corresponds to the distance from the center of one set of mounting holes to the next, ensuring consistent stacking of components. The total height of a panel spanning n rack units is calculated using the formula h = (1.75n - 0.031) inches or h = (44.45n - 0.79) mm. The subtraction of 0.031 inches (or 0.79 mm) accounts for clearance on the mounting flanges, providing approximately 1/32 inch of space to facilitate the installation and removal of equipment without interference from adjacent units. For example, a 1U panel measures 1.719 inches (43.66 mm) in usable height. The rack unit specifically measures the height of the or between the vertical mounting rails, excluding protrusions such as flanges or rear support brackets. This focused ensures that devices fit precisely within the allocated vertical space while allowing for secure attachment via the flanges. For international applications, the rack unit maintains the standard of 1.75 inches per U, with the equivalent of 44.45 mm used as a direct soft conversion without alteration to the underlying specifications. This equivalence supports global compatibility in rack systems, where equipment heights are expressed in whole or fractional U values regardless of regional preferences.

Mounting Width and Panel Sizing

The standard width for mounting equipment in racks is 19 inches (482.6 mm) overall, as defined by the EIA-310 specification, which ensures compatibility across various electronic and networking devices. The mounting holes on the vertical rails are positioned with a center-to-center horizontal distance of 18.312 inches (465.1 mm) between the two rows, allowing panels to secure firmly within the frame. Less common variants, such as 23-inch (584.2 mm) racks, are primarily used in applications for larger equipment layouts. Equipment panels must conform to this 19-inch width to fit properly, but the actual body width of the device is typically 17.5 to 18 inches to accommodate side panels, gaps, and structural flanges that extend to the full mounting dimension. This narrower body design prevents interference with adjacent units and promotes airflow in dense installations. Unlike width and height, rack depth lacks a fixed standard under EIA-310, with equipment depths varying by application from 16 to 32 inches (406 to 813 mm) to suit networking, audio, or server needs. Deeper configurations, often up to 48 inches in data centers, allow for cabling and cooling, but shallower options prioritize space efficiency in compact environments. Rack enclosures combine multiple rack units (U) vertically, where each U measures 1.75 inches (44.45 mm) in height, to form complete assemblies. A common 42U enclosure, for instance, provides approximately 73.5 inches (1,867 mm) of mounting height excluding the base frame, supporting extensive equipment stacking in standard server rooms.

History

Origins in Early

The rack unit concept emerged in the early as part of 's initiatives to standardize mounting systems for equipment in central offices. Around 1922, developed the format specifically for and termination apparatus, addressing the growing complexity of long-distance networks that required efficient space utilization in urban central offices. This innovation replaced haphazard custom-built installations with a uniform framework, enabling quicker deployment and scalability across the expanding infrastructure. The primary purpose of these early racks was to support modular, interchangeable frames that housed wiring panels, relays, and amplifiers essential for signal amplification and switching. Prior to this, equipment was often mounted on walls or structures, leading to inefficiencies in installation, maintenance, and upgrades; the new system allowed components to be prefabricated and easily swapped, reducing downtime in high-volume telephone exchanges. , AT&T's primary manufacturing subsidiary, played a crucial role by producing these standardized relay racks, integrating them into routine production for central office equipment. Initial rack dimensions were designed around height increments of 1¾ inches (44.45 mm), derived from the physical requirements of early gear such as electromagnetic relays prevalent in equipment. The 19-inch width accommodated standard panel sizes while providing sufficient depth for cabling and ventilation, with vertical supports spaced approximately 19.5 inches apart for stability. This configuration not only minimized floor space in crowded central offices but also facilitated the nationwide rollout of AT&T's infrastructure, where thousands of installations were supplied across the U.S. These foundational developments in rack mounting paved the way for subsequent formalization into industry-wide standards.

Development of Industry Standards

Following , the rack unit system, initially developed for , saw widespread adoption in , , and applications during the 1940s and 1950s. In , the format enabled modular equipment integration for radio and early television transmitters, facilitating scalable studio setups. systems embraced the standard for reliable, interchangeable electronics in field operations, while early hardware, such as vacuum-tube-based machines, began utilizing rack-mounted components for organized and . In the 1960s, the Electronic Industries Alliance (EIA) formalized these practices with the introduction of EIA-310, standardizing the 1¾-inch (44.45 mm) rack unit height for broader electronics applications beyond telephony. This specification established uniform mounting dimensions, promoting interoperability across industries and accelerating the rack unit's proliferation in commercial and industrial equipment. During the 1980s and 1990s, revisions to EIA-310 integrated with international norms, culminating in its adoption by the (IEC) as part of IEC 60297, which harmonized the globally. A key update occurred in 1992 with EIA-310-D, incorporating metric compatibility to align with emerging global manufacturing practices while preserving the core imperial-based unit dimensions. In the , the rack unit standard has undergone minor updates to accommodate high-density demands, such as enhanced provisions, yet the fundamental 1¾-inch unit remains unchanged. Early versions of the standard, however, lack specifics for modern technologies like fiber-optic cabling, reflecting their origins in an era dominated by copper-based systems.

Configurations

Full-Rack and Standard Setups

The standard full-rack height in rack unit systems is 42U, measuring approximately 73.5 inches (1.87 meters) for the internal mounting space, with the overall height typically around 78 inches (1.98 meters) to accommodate framing and doors, making it suitable for centers and server rooms where space efficiency is critical. Full-rack setups commonly feature vertical rails equipped with front and rear mounting posts for securing , along with horizontal supports integrated for to maintain organization and airflow within the . These configurations are widely applied in server hosting environments and for networking gear, where a 42U can accommodate up to 42 single-unit (1U) or a combination of with varying heights, such as mixing 2U and 4U devices for optimized . Ventilation in full-rack assemblies often includes built-in cooling fans at the top or rear to facilitate , while power distribution units (PDUs) are vertically mounted within the frame to supply to multiple devices; these racks typically support static load capacities ranging from 2000 to 3000 pounds (900 to 1360 kilograms), ensuring stability for loads.

Half-Rack and Specialized Variations

Half-rack configurations typically refer to equipment or enclosures with reduced dimensions compared to the standard 19-inch (482.6 mm) full-width , enabling more efficient use of space in constrained environments. The most common variant is the half-width design, measuring 9.5 inches (241 mm) across, which allows two such units to be mounted side-by-side within a single full-rack space. This approach is particularly prevalent in networking equipment, where compact switches and routers benefit from the halved footprint without sacrificing compatibility with EIA-310 standards. Half-depth and half-height variations further adapt racks for specialized installations. Half-depth units offer mounting depths of 14 to 16 inches (356 to 406 mm), ideal for shallow spaces such as wall-mounted setups or under-desk applications where rear clearance is limited. Half-height enclosures, often 18 to 22U tall (approximately 31.5 to 38.5 inches or 80 to 98 cm), provide compact floor-standing or portable options, measuring about 3 feet (91 cm) in height to suit smaller-scale deployments. These dimensions facilitate easier transport and installation while maintaining structural integrity for standard rackmount hardware. In audio and video applications, half-rack designs are widely used for their versatility in professional environments. Compact 10U to 12U enclosures house mixers, processors, and amplifiers, often in wall-mount or portable cases for live events and studios. Half-height racks are employed in studios to organize multiple half-width devices like audio interfaces and video switchers, optimizing workflow in space-limited control rooms. Mounting adaptations, such as side-by-side kits, enable pairing of two half-width units to fill a full space, using specialized ears or shelves for secure alignment. However, this configuration can introduce challenges, including shared power supplies that require balanced load distribution and cooling issues from restricted airflow between closely packed units, necessitating additional fans or ventilation planning. Modern half-rack variations emphasize flexibility for evolving needs. Open-frame designs promote superior airflow and accessibility by omitting side and rear panels, reducing heat buildup in dense or networking setups. Adjustable or telescoping rail systems allow depth customization from 23 to 40 inches (584 to 1016 mm), accommodating varied equipment without fixed constraints and supporting easy expansion in portable or modular installations. These innovations address niche demands, such as mobile rigs, by prioritizing modularity over traditional enclosed cabinets.

Standards and Compatibility

EIA-310 Specifications

The EIA-310 standard establishes the core dimensions and mounting requirements for 19-inch racks in the United States, promoting uniformity and interchangeability for electronic equipment. It defines the standard front panel width as 19 inches (482.6 mm), with the usable mounting space between vertical rails measuring 18.3125 inches (465.1 mm) center-to-center. The rack unit (U), the fundamental height increment, is precisely 1.75 inches (44.45 mm), allowing equipment to be stacked in modular increments while maintaining consistent vertical positioning. Mounting holes follow a standardized to ensure secure and repeatable installation. Vertically, holes are arranged in repeating sets of three per U, with center-to-center spacings of 0.625 inches (15.9 mm) between the first and second hole, 0.625 inches (15.9 mm) between the second and third, and 0.5 inches (12.7 mm) to the start of the next set, resulting in the 1.75-inch U height. Horizontally, the four mounting holes per panel align across the two vertical rails. For tapped holes, the primary specification is No. 10-32 UNC-2B, suitable for most U.S. , while No. 12-24 UNC-2B serves as an alternative for applications involving heavier loads. Tolerances for hole positioning are tight, with ±0.015 inches (±0.38 mm) between any two holes to minimize misalignment. These specifications, originally outlined in earlier versions like RS-310 from 1968 and formalized in EIA-310-D in 1992, ensure broad across manufacturers for electronics housing, from to . Compliance with EIA-310 guarantees that rack-mounted devices can be interchanged without modification, supporting reliable deployment in professional environments. The standard's international counterpart, IEC 60297, aligns closely but incorporates metric preferences.

IEC 60297 and Global Adoption

The (IEC) standard 60297, titled "Mechanical structures for electronic equipment – Dimensions of mechanical structures of the 482.6 mm (19 in) series," was initially published in the early as an international equivalent to the U.S.-based EIA-310 standard, providing metric-based specifications for rack dimensions to facilitate global . It defines the rack unit (U) height as 44.45 mm and the standard mounting width as 482.6 mm, ensuring compatibility for electronic equipment across borders while emphasizing principles. This orientation addressed the need for precision in , contrasting with measurements prevalent in . Globally, IEC 60297 promotes the use of metric threads for mounting hardware, which are preferred in regions outside the U.S. for their standardization in systems, enhancing ease of assembly in diverse supply chains. To accommodate varying regional preferences, the standard supports square-hole configurations in racks, allowing the insertion of cage nuts that can accept multiple thread sizes, including , thereby bridging and installations without requiring rack modifications. Adoption of IEC 60297 accelerated through efforts with EIA standards, notably via the 1992 to IEC 60297-3, which aligned subrack and plug-in unit dimensions for broader compatibility. Subsequent updates in the , such as editions in 2008 and 2014, incorporated provisions for high-density applications and modular designs, reflecting evolving needs in and . By 2023, the technical report IEC TR 60297-3-1 further refined application guidelines for the 19-inch series, with ongoing maintenance ensuring relevance amid advancements in and smart systems as of 2025. The standard also addresses regional variations by including provisions for 23-inch racks, particularly in telecommunications contexts, where wider formats support specialized equipment without deviating from core dimensional principles. This flexibility has solidified IEC 60297's role in global adoption, enabling seamless integration in international projects while maintaining with earlier iterations.

References

  1. [1]
    EIA-310: What Does It Mean?
    ### Summary of EIA-310 Definition and Details
  2. [2]
    What Are EIA Standards? And Where Do They Come From?
    Jun 28, 2022 · Rack Units (U) – hole spacing for standard racks on the mounting flange is spaced in groups of three holes. This three-hole group is defined as ...
  3. [3]
    Introducing the Open Rack - Open Compute Project
    Aug 7, 2013 · The Open Rack standard seeks to right some historic wrongs in traditional rack design, set by the EIA 310-D specification, which traces its ...
  4. [4]
  5. [5]
    Rack Mounting FAQ - Micropolis
    To calculate the height of panels, use this formula: h = (1.750 * n - 0.031) inches = (44.45 * n - 0.79) millimeters, where n was the number of rack units ...
  6. [6]
    U & RU Rack-Mount Form Factor Explained - CP North America
    1U of rack space is equal to 1.75 inches. For example, a rack designated as 20U has 20 rack spaces for equipment and has 35 inches (20 x 1.75”) of vertical ...<|control11|><|separator|>
  7. [7]
  8. [8]
    What is the standard rack horizontal hole spacing? - CyberPower
    The horizontal spacing of the vertical rows of holes is specified by EIA-310 at 18 5/16′′ (18.312′′ or 465.1 mm).
  9. [9]
    Server Rack Sizes and Standards: A Complete Guide
    The industry standard width is 19 inches (482.6 mm) · Some racks are available in 23 inches (584.2 mm) for telecom applications ...<|control11|><|separator|>
  10. [10]
  11. [11]
    19" rack equipment dimensional data - Canford Audio
    Recommended equipment front panel width: 483mm (19 inches). Recommended equipment body width: 449mm (maximum). 1U incremental height: 44.45mm (1.75 inches) ...
  12. [12]
  13. [13]
    A Definitive Guide to 19-Inch Server Rack Sizes | Pure Storage
    19 inches is the standard width of a mountable server rack. In this guide, we'll cover everything you need to know about sizing rack servers.
  14. [14]
    Rack specifications - IBM
    The rack or cabinet must meet the EIA Standard EIA-310-D for 19-inch racks. The front rack opening must be 451 mm wide + 0.75 mm (17.75 in. + 0.03 in.).Missing: definition | Show results with:definition
  15. [15]
    Rack Unit Calculator - Penn Elcom
    The unit calculator below can convert rack U's into cm, inches and feet, which makes it a very useful tool for any installer or musician.
  16. [16]
    BSTJ 2: 3. July 1923: Telephone Equipment for Long Cable Circuits. (Demarest, Charles S.) : Free Download, Borrow, and Streaming : Internet Archive
    ### Summary of Relevant Content on Rack Units, Relay Racks, or Standardization of Mounting for Telephone Equipment (1922-1923)
  17. [17]
    DC power in the racks - DCD - Data Center Dynamics
    Apr 3, 2024 · Data centers adopted many things from telecoms, most notably the ubiquitous 19-inch rack, which was standardized by AT&T way back in 1922.Missing: invention | Show results with:invention
  18. [18]
  19. [19]
    The Evolution of Rack Enclosures in Military Communications Systems
    Mar 19, 2025 · The concept of rack-mounted systems began during WWII, when militaries needed to standardize communications and electronic systems across ...
  20. [20]
    ANSI/EIA RS-310-D, IEC 60297-2, and DIN 41494 Explained
    Jul 31, 2025 · This standard ensures dimensional alignment for rackmount servers, network switches, and other 1U/2U equipment used widely in data centers and ...Missing: history | Show results with:history
  21. [21]
    [PDF] Server Rack Cabinet Compatibility Guide - Intel
    Sep 4, 2005 · The Electronic Industries Association (EIA) created the EIA-310-D standard in 1992 for cabinets, racks, panels, and associated equipment. Intel ...Missing: development | Show results with:development<|control11|><|separator|>
  22. [22]
    AR3300 - APC NetShelter SX, Server Rack Enclosure, 42U, Black ...
    30-day returnsAug 31, 2025 · Overview. Lead time, Usually in Stock · Main. Product or Component Type, Rack enclosure. Number of rack unit · Physical. Height, 78.4 in (1991 mm).
  23. [23]
    42U Rack Dimensions, Cabinet Size, & Specifications
    Mar 20, 2012 · A 42U rack is 23.6" wide, 78.74" high, and has depths of 39.37" or 41.34". It can handle up to 3,000lbs.
  24. [24]
    AR2580 - APC NetShelter SV, Server Rack Enclosure, 42U, 800W x ...
    30-day returnsFeatures integrated vertical 1U mounting spaces allowing for efficient cable management. notification_ok. Includes pre-installed casters, leveling feet, and ...
  25. [25]
    IT Racks and Accessories | Schneider Electric USA
    Robust rack accessories that manage rack level cabling and provide a complete rack systems with more optimized airflow and cable management. Part of ...EcoStruxure Micro Data Centers · Custom Racks · APC NetShelter Open Frame...Missing: vertical rails
  26. [26]
    [PDF] ©2021 Jamie Levinson ALL RIGHTS RESERVED - RUcore
    This is the same number of servers which would fit in a 42U rack which is a standard size option which is commonly available. During the simulation, the ...<|control11|><|separator|>
  27. [27]
    [PDF] Small-World Datacenters - CS@Cornell
    Aug 29, 2011 · Consider a data- center with 10K servers in standard 42U Racks. Usually the width, depth and height of the rack are 0.6, 1, and 2 me- ters ...
  28. [28]
    42U Server Rack Cabinet, Locking Front/Rear Doors, Excellent Airflow
    Rating 5.0 (19) Constructed from heavy-duty steel with a durable black powder-coated finish, the SR42UB has a maximum stationary load capacity of 3500 pounds (1588 kilograms) ...
  29. [29]
    [PDF] Specifications 42U Server Rack, Euro-Series - Tripp Lite
    ... load capacity of 1360 kilograms and a maximum rolling load capacity of 1020 kilograms. Keeps Important Equipment SecureThe reversible front door, split rear ...
  30. [30]
    Understanding U Space, and Why It's Important | Server Technology
    Jun 16, 2025 · "Full rack" server models are 19 inches, while “half rack” equipment – such as networking gear – occupies 9.5 inches. Common heights are 42U ...
  31. [31]
    Half Size Racks (9.5 inch) - ProCase Shop
    However, there is no 9.5 inch standard width. The 19 inch standard width is defined by the width of the front panel with 482.6 mm (= 19 inch) as well as the ...
  32. [32]
  33. [33]
  34. [34]
    Standard Depth Server Rack, 25U - Tripp Lite - Eaton
    Rating 4.4 (7) 25U SmartRack half-height server rack enclosure, includes locking door and side panels.
  35. [35]
    HALF RACK - RDL®
    RDL Half-Rack products are studio-quality, 1/2 rack width, 1RU high, with front controls, rear connectors, and can be rack-mounted or used standalone. They are ...
  36. [36]
  37. [37]
  38. [38]
  39. [39]
    Open Frame IT & Telcom Racks | Eaton
    Tripp Lite carries a broad range of floor-standing and wall mount racks, including heavy-duty 2-post and 4-post floor standing racks for IT and telcom equipment ...
  40. [40]
  41. [41]
    Half Rack Shelf System - Mounting Hardware - Extron
    Compact, 1U half-rack width size fits narrow lecterns and cabinets · Holds one half-rack, two quarter-rack, or four eighth-rack width products · Includes mounting ...
  42. [42]
    [PDF] EIA-310 Rack Standard - CASA Modular Systems
    The EIA-310 standard defines dimensions for rack compatibility, covering 19", 24", and 30" widths, with 19" preferred. Racks are floor-standing structures for ...Missing: unit | Show results with:unit
  43. [43]
  44. [44]
    [PDF] IEC TR 60297-3-1:2023 - iTeh Standards
    The dimensions of the rack and chassis were adopted from the 19-inch EIA standard, and the following development concept was established to mount the PBs into ...
  45. [45]
    IEC TR 60297-3-1:2023
    Feb 7, 2023 · IEC 60297-3-1:2023 provides information on the technological schemes of the IEC 60297 series and shows how to apply the 19-inch series standards.
  46. [46]
    IEC 60297-3:1984/AMD1:1992
    International Standards facilitate technical innovation, efficient and sustainable energy access, smart urbanization and transportation systems, climate change ...Missing: harmonized | Show results with:harmonized
  47. [47]
    IEC 60297-3-105:2008
    Nov 26, 2008 · IEC 60297-3-105:2008 specifies the dimensions for 1U chassis mounted into IEC 60297-3-100 compliant racks/cabinets.<|control11|><|separator|>
  48. [48]
    [PDF] EHP Series 19” & 23” Rack mounted batteries designed for ...
    Design Assessment of 19- and 23-inch rack. ❑ 19- and 23-inch rack is designed based on IEC 60297-3-100 guidelines. ❑ These standard rack designs are ...
  49. [49]