A recloser, also known as an automatic circuit recloser (ACR), is an automatic, high-voltage electric switch designed for use on overhead networks to detect and fault currents, such as short circuits, while attempting to automatically restore if the fault is temporary. Operating typically at voltages from 2.4 kV to 38 kV, it functions like an advanced by rapidly opening to protect the system and reclosing after a brief delay to test line conditions. This device complies with international standards such as ANSI/IEEE C37.60 and IEC 62271-111, ensuring reliable performance in medium-voltage applications. Reclosers operate through a predetermined sequence of actions: upon detecting a fault via integrated current transformers and voltage sensors, the device trips to disconnect the faulty section, isolating the issue and preventing damage to downstream equipment. If the fault clears—often the case for 80-90% of interruptions caused by transient events like strikes or falling branches—the recloser automatically re-energizes the line after a short programmable delay, typically attempting this up to three or four times before locking out for manual intervention. Vacuum interrupters are commonly used in modern reclosers for arc quenching, providing superior durability and safety compared to older oil- or air-based designs. This self-controlled automation minimizes human error and speeds up response times, making reclosers essential protective relays in distribution systems. Reclosers are available in several types to suit different network configurations, including single-phase models for rural or residential laterals, three-phase ganged units for balanced or feeds, and single-triple variants for single-phase branches off three-phase mains. They are typically pole-mounted for overhead lines but can also be installed in substations or pad-mounted enclosures for applications. Advanced models incorporate digital controls for programmable curves, communication interfaces for remote monitoring, and integration with technologies to enable fault location, isolation, and service restoration (FLISR). By automatically clearing temporary faults and localizing persistent ones, reclosers significantly enhance power reliability, reducing outage durations and improving metrics like the System Average Interruption Duration Index (SAIDI) and System Average Interruption Frequency Index (SAIFI). In overhead distribution networks, where transient faults account for the majority of interruptions, their deployment has proven critical for minimizing economic losses from downtime in residential, commercial, and industrial sectors. Overall, reclosers represent a cornerstone of modern electrical distribution, balancing protection with seamless power restoration to support resilient energy infrastructure.

Fundamentals

Description

A recloser, formally known as an automatic recloser (ACR) or autorecloser, is a self-contained protective device designed for overhead networks. It automatically detects fault currents, such as those caused by short circuits or temporary disturbances, interrupts the flow to isolate the issue, and then attempts to re-energize the if the fault clears, thereby restoring without manual intervention. This functionality is particularly valuable since extensive studies of overhead s have established that approximately 80 to 95 percent of all system faults are temporary in nature and can self-clear after a brief interruption. Reclosers are manufactured in single-phase and three-phase configurations to match various , with single-phase units often used on rural or lightly loaded lines and three-phase models for balanced or feeds. The core interrupting mechanism employs technologies such as oil-immersed contacts (in older designs), interrupters for reliable arc quenching with minimal maintenance, SF6 gas insulation for compact high-performance operation, or solid dielectric materials for , oil- and gas-free alternatives. Key specifications for reclosers include voltage ratings ranging from 2.4 to 72 —most commonly 15.5 to 38 for medium-voltage applications—continuous current ratings from 10 A to 1200 A, and symmetrical interrupting capacities from 1 to 16 to handle fault levels effectively. These devices must comply with international standards like IEC 62271-111 for and IEEE C37.60 for automatic circuit reclosers, ensuring consistent performance and . The basic components of a recloser include the interrupting mechanism for opening and closing the , a —ranging from hydraulic actuators in legacy models to modern electronic or microprocessor-based systems for precise sequencing and monitoring—and integrated sensors such as current transformers and voltage detectors to measure electrical parameters in . Enclosures are typically designed for pole-mounted on poles for overhead lines or pad-mounted for subsurface and applications, providing weatherproof and ease of into .

Operating Principles

Reclosers detect faults primarily through overcurrent relays, which monitor phase, ground, or sensitive earth fault currents to identify abnormal conditions on the power line. These relays employ time-current curves (TCCs) to differentiate between temporary faults, such as those caused by transient events like lightning-induced arcs that self-clear, and permanent faults requiring isolation. The TCC defines the operating time as a of fault current magnitude, allowing faster tripping for higher currents to minimize damage while coordinating with downstream devices. Upon detection, the recloser opens its contacts to the fault current, extinguishing the resulting via an interrupter . Modern reclosers commonly use vacuum bottles, where contacts separate within a high-vacuum environment (typically 10^{-5} to 10^{-6} ), leading to rapid arc extinction due to the quick recovery of as metal vapor from the arc condenses on the cooled surfaces, restoring in microseconds. This process prevents re-ignition and allows interruption of currents up to 16 kA or more, depending on the recloser's rating. The reclosing logic initiates a programmable sequence of operations following an open event, attempting to restore for temporary faults. After the initial , a dead time—typically 0.3 to 1.5 seconds—elapses to allow arc de-ionization and fault clearing, after which the recloser attempts to re-energize the line. Subsequent dead times are longer (e.g., 2 to 15 seconds for the second shot, 15 to 45 seconds for the third) to account for slower-clearing faults, with lockout occurring after 3 to 4 unsuccessful attempts to prevent repeated stressing of the system. This sequence is configurable to match network requirements, ensuring high reliability for overhead distribution lines. Control systems govern the detection, tripping, and reclosing actions, evolving from mechanical to advanced digital types. Hydraulic controls use oil pressure and time-based mechanisms for basic inverse-time operation, providing reliable but less flexible performance. Electronic controls introduce customizable TCCs via analog circuits, allowing tailored coordination. Microprocessor-based controls, prevalent in modern reclosers, employ adaptive algorithms for precise fault analysis, event recording, and integration of multiple protection elements, enhancing selectivity and reducing outage times. A fundamental aspect of overcurrent detection in reclosers is the time- characteristic, which ensures tripping time decreases as fault increases. For a basic time , the relationship can be approximated by I = k \cdot t^{-0.5}, where I is the fault , t is the operating time, and k is a dependent on the 's time dial setting and pickup . This form derives from the standard t = \frac{k}{I^2} for curves approximating (I²t), common in coordination or very characteristics; solving for I yields I = \sqrt{\frac{k}{t}} = k' \cdot t^{-0.5} (with k' = \sqrt{k}). More precise implementations follow IEEE C37.112 standards, using t = \frac{A}{(M^\phi - 1)} + B + \frac{C}{M} where M = I / I_s (pickup ), but the simplified inverse square root form captures the core principle for introductory analysis. No rewrite necessary — no critical errors detected.

History

Early Development

The development of the automatic circuit recloser began in the early 1940s in the , driven by the need to address frequent temporary faults on rural overhead distribution lines caused by transient events such as strikes, branches, or contact. The Kyle Corporation, founded in 1933 as the Electrical Connectors and Manufacturing Company, pioneered the technology with the introduction of the first oil-filled hydraulic reclosers around 1941. Key innovations were captured in early patents, including U.S. Patent No. 2,459,327 filed by W. D. Kyle, Jr., and associates in 1941, which described an automatic reclosing designed to interrupt fault currents and attempt reclosure to restore service without manual intervention. Other companies, such as S&C Electric Company, also contributed to early recloser development during this period. Following , reclosers saw initial widespread adoption as part of the U.S. rural electrification efforts, particularly through the programs established under the of 1936. These initiatives extended electrical service to underserved rural areas, where long overhead lines were prone to interruptions, and reclosers proved essential for maintaining reliability by automatically clearing temporary faults and minimizing downtime. By enabling power restoration in seconds rather than requiring hours for manual repairs or resets, early reclosers significantly improved service continuity in these expanding networks, supporting the REA's goal of electrifying farms and communities. The first commercial models were single-phase, oil-immersed devices rated for voltages of 7.2 to 14.4 , featuring hydraulic mechanisms with fixed sequences of one to two reclose attempts before lockout. These units operated on basic mechanical protection principles, interrupting currents up to 100–200 A continuous and higher momentary ratings, and were installed primarily on rural feeders to handle the predominant single-phase faults. Limitations included the requirement for manual reset after lockout and sensitivity to environmental factors like oil degradation, but they marked a practical advancement over fuses or manual breakers. In the 1950s, standardization efforts by the (AIEE), a predecessor to the IEEE, formalized requirements for these devices through publications like AIEE Standard No. 50 (1949, for reclosers up to 15 , and revised 1953 for up to 23 ), which specified ratings, testing procedures, and performance criteria. These standards addressed early limitations, such as manual reset needs and coordination with other protective devices, paving the way for broader utility acceptance. By the mid-1950s, three-phase gang-operated models began emerging, though single-phase units dominated rural applications. Later evolution toward electronic controls in the built on these foundations.

Technological Evolution

The transition from hydraulic to electronic controls in reclosers began in the 1970s and accelerated through the 1980s, driven by advancements in semiconductor technology that enabled programmable time-current characteristics (TCCs) and integrated voltage sensing. This shift allowed for more precise and adjustable fault response sequences compared to the fixed hydraulic mechanisms, which relied on timing and were less adaptable to varying conditions. Electronic controls improved reliability by incorporating solid-state relays, reducing maintenance needs and enabling customization for diverse scenarios. In the 1990s and 2000s, integration further revolutionized recloser , providing computational power for complex algorithms and seamless compatibility with supervisory control and (SCADA) systems. These developments facilitated exchange and remote monitoring, enhancing overall grid coordination. Concurrently, vacuum interrupters gained prominence as replacements for oil- and SF6-based designs, addressing environmental concerns such as oil leaks and the high of SF6 gas. offered superior arc-quenching performance in a compact, non-toxic form, aligning with regulatory pressures for sustainable power equipment. The 2010s marked the rise of solid-state and adaptive reclosers, incorporating for faster switching and integration with loop schemes that automatically isolate faults and restore service in meshed networks. These innovations minimized outage durations by enabling dynamic reconfiguration without manual intervention. Entering the , connectivity has enabled continuous remote monitoring, while algorithms support predictive fault analysis by processing sensor data for early . This evolution is underscored by market projections estimating the global recloser industry at $1.5 billion by 2030, fueled by widespread grid modernization initiatives. Significant milestones include the 2005 edition of IEC 62271-111, which defined ratings, testing procedures, and requirements for automatic circuit reclosers up to 38 kV. The standard was updated in 2019 to incorporate advancements in multi-pole designs and performance criteria for overhead and pad-mounted installations, ensuring in modern systems. Parallel to these updates, the adoption of three-phase electronic reclosers has optimized in grids, where balanced multi-phase prevents unnecessary outages on interconnected feeders.

Functions

Fault Protection

Reclosers serve as primary upstream protective devices for transformers and feeders in systems, detecting and interrupting fault currents to isolate faults while coordinating with downstream fuses and through selective tripping mechanisms. This coordination ensures that temporary faults are cleared by the recloser without affecting downstream devices, whereas permanent faults allow downstream fuses to operate, minimizing unnecessary outages in healthy sections of the network. Protection schemes in reclosers encompass phase overcurrent protection for balanced faults, ground fault protection for unbalanced conditions involving , and sensitive earth fault (SEF) detection, which can be tuned to low current levels as low as 200 mA in sensitive applications, to identify high-impedance faults that might otherwise go undetected. SEF capability enhances detection of subtle ground faults, such as those caused by vegetation contact, by measuring residual currents with high sensitivity, often integrated via core-balance current transformers. These schemes operate independently or in combination, with electronic controls allowing programmable thresholds and time delays for precise fault discrimination. Coordination principles rely on time-current characteristic (TCC) curves tailored to fault types: a faster TCC curve enables rapid tripping for temporary faults to preempt downstream operation, while a slower curve for subsequent attempts permits sectionalizers or to isolate permanent faults downstream, maintaining a coordination margin of approximately 0.35 seconds. This sequential approach ensures selectivity, where the recloser acts as the first line of defense without cascading interruptions. The implementation of these fault features yields significant benefits, including reduced outage durations to under one minute for approximately 80% of faults, which are typically transient, thereby enhancing system reliability and . Additionally, by swiftly interrupting faults, reclosers minimize arcing damage to conductors and equipment, extending asset life and lowering maintenance costs in overhead distribution networks.

Network Restoration and Management

Reclosers play a critical role in automatic restoration by attempting to re-energize the after detecting a fault, specifically targeting transient faults that clear themselves during a brief dead time. Upon fault detection, the recloser interrupts the and waits for a programmed dead time—typically ranging from 0.5 to 30 seconds—before automatically reclosing to restore power if the fault has cleared. This process is repeated up to a set number of shots (usually 1 to 4), after which the recloser locks out for persistent faults, preventing further damage and requiring manual intervention. Such mechanisms restore service to the majority of overhead faults, which are transient in nature, thereby minimizing outage durations. Integration with supervisory control and data acquisition () systems and distribution management systems () enables remote capabilities for reclosers, allowing operators to initiate reclosing or sectionalizing from a control center. Through communication protocols like or , reclosers transmit real-time status, fault data, and voltage/current measurements to the SCADA/DMS, facilitating remote commands to re-energize isolated sections or transfer loads without on-site presence. This remote functionality enhances response times during outages, particularly in expansive networks, by enabling operator-supervised reclose attempts after verifying fault clearance via diagnostic data. For instance, in coordinated schemes, remote blocking or enabling of reclosing prevents unnecessary operations during maintenance or multi-feeder faults. In network division, reclosers are deployed at tie-open points in loop schemes to isolate faulted sections while enabling load transfer from adjacent feeders, thereby restoring to unaffected areas. Normally open tie reclosers detect loss of voltage on the source side and automatically close after a short delay, transferring load to an alternate source and reconfiguring the network . This approach supports radial-to-loop restoration, where upstream sectionalizing reclosers open to isolate the fault, and the tie recloser closes to backfeed downstream loads, reducing the scope of outages in meshed configurations. Such division strategies improve overall system reliability by limiting interruptions to the faulted segment only. Reclosers contribute to load flow resolution through adaptive settings that monitor and respond to voltage conditions, helping balance uneven loads and mitigate voltage drops across the network. Voltage-supervised reclosing, for example, uses load-side voltage thresholds to delay or inhibit reclose if under-voltage persists, preventing exacerbation of imbalances during . By incorporating adaptive algorithms that adjust reclose timing or sensitivity based on load profiles, reclosers facilitate even of power flow in looped systems, reducing voltage deviations that could arise from sudden load transfers. This capability is particularly valuable in networks with variable loading, where it maintains voltage stability without manual reconfiguration.

Fault Conditions and Strategies

Common Causes

In electrical distribution systems, faults are broadly categorized into transient, semi-permanent, and permanent types, with reclosers primarily designed to address the former two through automated interruption and restoration. Transient faults, which account for 80-90% of all faults on overhead lines, are self-clearing and do not cause lasting damage to the infrastructure. These typically arise from external environmental or incidental contacts that briefly disrupt the circuit, such as lightning strikes inducing voltage surges, tree branches or vegetation swaying into phase-to-ground contact during high winds, animal interference (e.g., birds or squirrels bridging insulators), or wind-blown objects like debris temporarily shorting lines. Semi-permanent faults represent a smaller , often transitioning from unresolved transients or involving minor degradation that sustains arcing until cleared. These are commonly triggered by failures, such as cracked insulators, loose connections, or degraded conductors that allow intermittent faults to persist. Unlike transients, they may require one or more reclose attempts before resolution but do not necessitate full manual repairs. Permanent faults, comprising 5-20% of incidents, involve substantial physical damage that demands manual intervention and cannot be resolved by reclosers alone. Examples include excavations by construction activities (e.g., digs severing underground lines) or major breakdowns like fallen poles and irreparably damaged transformers. Among specific causes, strikes are a leading contributor to outages in overhead lines, responsible for 30-50% of such in many regions due to induced surges overwhelming . In rural areas, contact—particularly from overgrown trees or limbs encroaching on lines—accounts for 20-30% of outages, exacerbated by weather that cause branches to fall or sway into conductors. These statistics underscore the predominance of transient and vegetation-related issues in prompting recloser operations to maintain service continuity.

Reclosing Sequences

Reclosers employ configurable reclosing sequences to attempt restoration after fault interruption, typically involving multiple operations before lockout to accommodate temporary faults such as those caused by . A standard sequence often includes one fast initial followed by a short dead time of approximately 0.5 seconds, allowing the from transient faults to extinguish, succeeded by up to three slower reclose attempts with progressively longer dead times—ranging from 2 to 15 seconds for the first slow reclose, 15 to 30 seconds for the second, and around 45 seconds for the third—after which the recloser locks out if the fault persists, isolating the section for manual intervention. Adaptive reclosing strategies enhance effectiveness by incorporating checks to prevent unsuccessful or hazardous operations, such as voltage confirmation prior to reclosure to verify line integrity and avoid energizing downed conductors that could cause further damage or safety risks. Additionally, sensitive fault (SEF) modes are utilized in reclosers for detecting high-impedance faults, which produce low current levels insufficient for standard protection, enabling targeted single-phase tripping and reclosing to minimize outage scope in grounded systems. Dead time optimization tailors reclose intervals to fault characteristics, with shorter durations like 0.3 seconds applied for lightning-induced faults to permit rapid deionization of the path, while longer intervals of 5 to 10 seconds are used for vegetation-related contacts to facilitate self-extinction or clearance of the obstruction. These adjustments improve overall sequence success by aligning dead times with the typical duration of temporary fault conditions. The probability of reclose success can be estimated using the P = 1 - \frac{f_p}{f_t}, where f_p represents the fraction of permanent faults and f_t the total fault occurrences, reflecting the proportion of temporary faults cleared by reclosing. For instance, if permanent faults constitute % of total faults (f_p / f_t = 0.2), then P = 0.8, indicating an 80% success rate for the initial reclose attempt, as supported by field data showing 80% of faults as temporary. In a scenario with 10% permanent faults, P = 0.9, highlighting higher reliability in networks with fewer persistent issues like equipment failures.

Applications

Distribution Systems

Reclosers are strategically placed in traditional distribution systems to enhance fault management and service continuity, typically at substation exits to protect outgoing feeders, at midpoints along main feeders to divide long lines into manageable sections, and on laterals to isolate branch faults without affecting the primary . These placements are common in radial networks, where flows unidirectionally from the substation, as well as in looped configurations that allow for alternate paths during outages. Such positioning applies to both overhead lines in rural areas and cables in settings, enabling rapid fault detection and response across diverse network topologies. The deployment of reclosers significantly improves system reliability by minimizing outage durations and frequencies, with studies showing reductions in the System Average Interruption Duration Index (SAIDI) by 2% to 56% and the System Average Interruption Frequency Index (SAIFI) by 11% to 49%, depending on network configuration and fault types. This enhancement stems from reclosers' ability to automatically clear temporary faults—such as those caused by tree branches or lightning—and re-energize lines, preventing unnecessary sustained interruptions. Additionally, reclosers facilitate sectionalizing, allowing utilities to isolate faulted segments quickly while restoring power to unaffected areas, thereby reducing overall downtime and operational costs. Configurations of reclosers vary by application: pole-mounted units are standard for rural overhead networks due to their ease of on poles, while pad-mounted designs suit urban underground systems for aesthetic and space reasons. Single-phase reclosers are typically used on laterals to target faults on lines without de-energizing the entire three-phase main, whereas three-phase reclosers protect primary mains to ensure coordinated interruption across all phases during multi-phase faults. In the United States, rural electric cooperatives have employed reclosers since the as part of their , contributing to high reliability levels, typically achieving 99% to 99.9% uptime (2-3 nines of reliability). These organizations, serving remote areas with extensive overhead lines, adopted reclosers to address frequent transient faults from vegetation and weather, enabling them to maintain service continuity and meet growing demands post-World War II.

Renewable Energy Integration

The integration of sources, such as photovoltaic (PV) systems and turbines, into distribution networks introduces significant challenges for reclosers, primarily due to bidirectional power flow that complicates traditional unidirectional protection coordination. This flow reversal, caused by (DG) exporting power upstream, can lead to miscoordination between reclosers and downstream fuses, potentially failing to isolate faults effectively or causing unnecessary outages. Additionally, the intermittent nature of renewables results in voltage fluctuations, which challenge recloser sensitivity and timing, exacerbating stability issues during transient events. detection further complicates operations, as reclosers must distinguish between grid-connected and unintentional islanded modes to prevent safety risks and equipment damage in renewable-heavy microgrids. To address these issues, modern reclosers incorporate adaptations like sync-check relays, which verify voltage magnitude, phase angle, and frequency alignment before reclosing, ensuring safe reconnection of renewable DG post-outage without stressing the system. These relays are particularly vital in bidirectional setups, where asynchronous closure could amplify faults or harmonics from inverters. Complementing this, ride-through settings aligned with IEEE 1547-2018 standards enable renewables to withstand voltage and frequency disturbances, coordinating with recloser clearing times (typically over 2 seconds) to avoid nuisance tripping and support grid recovery. For instance, Category III performance categories in IEEE 1547 allow continuous operation within 0.88–1.10 per unit voltage, adapting recloser sequences to renewable for enhanced . These adaptations yield key benefits, including improved fault ride-through that maintains overall stability by keeping renewable resources online during disturbances, thus minimizing cascading failures in solar-integrated feeders. In microgrids, reclosers with advanced protection, such as relays, enable precise fault isolation, supporting up to 100% penetration of peak load while significantly reducing uncleared faults—for example, eliminating all uncleared events on certain feeders compared to dozens under traditional schemes. This also shortens mean fault clearing times to as low as 0.385 seconds in high- scenarios, enhancing reliability without widespread DER disconnection. In the , reclosers tailored for distributed energy resources (DER) have seen rapid adoption, driven by the need for seamless coordination in renewable-dominant grids. The global recloser market, bolstered by DER integration, is projected to reach approximately USD 1.5 billion by 2030, reflecting a of around 5% from 2023 levels, as utilities invest in to handle increasing and capacities.

Advanced Integrations

Digital and Smart Features

Modern digital reclosers incorporate microprocessor-based control units that enable advanced functionalities such as event recording and capture for detailed fault analysis. These units, often classified as intelligent electronic devices (IEDs), log sequence of events with timestamps and capture high-resolution waveforms from analog and binary channels, allowing utilities to diagnose power system disturbances accurately and prevent equipment damage. For , algorithms process sensor data from reclosers to estimate component wear, such as breaker life based on trip currents and manufacturer curves, thereby optimizing maintenance schedules and reducing unplanned outages. IoT integration in reclosers facilitates through cellular and Ethernet , transmitting to central systems for and enabling remote updates to enhance performance without on-site intervention. This supports protocols like and for seamless integration with and distribution management systems (), providing utilities with live visibility into equipment status and load conditions. Examples include Viasat's terminals that integrate with reclosers for reliable IP-based in remote areas, reducing operational response times. Smart features in digital reclosers include adaptive schemes that automatically adjust time-current curves (TCCs) in response to varying load conditions or integration, ensuring coordinated operation without manual reconfiguration. Self-adaptive systems can modify parameters like time dials to maintain fuse saving and prevent miscoordination during faults. Loop enables self-healing networks by isolating faults and restoring service to healthy sections automatically, often achieving restoration in seconds compared to manual processes that take minutes. In the 2020s, manufacturers like ABB and have introduced advanced digital reclosers with enhanced fault analysis and self-healing capabilities. ABB's RER620 series provides advanced fault recording and for analysis, enhancing reliability in feeders. 's Multilin R650 supports advanced logic for fault isolation in self-healing schemes, integrating with analytics for proactive grid management. Cybersecurity measures align with standards, incorporating , encryption, and secure communication protocols to protect against cyber threats in connected environments.

Coordination with Other Devices

Reclosers are designed to coordinate with downstream fuses to enhance selectivity and minimize unnecessary outages. In this scheme, the recloser's fast operating curve is set to interrupt temporary faults quickly before the can blow, restoring service without affecting lateral lines protected by . For permanent faults, the recloser's slower curve allows sufficient time for the downstream to clear the fault entirely, preventing the recloser from locking out and isolating a larger portion of the . This coordination is achieved by aligning the recloser's time-current characteristic with the 's total clearing curve, where the intersection point defines the minimum fault current for reliable operation. Sectionalizers complement reclosers by providing precise fault in downstream segments without interrupting power during reclose attempts. Positioned between the recloser and the fault, a sectionalizer counts the number of fault current pulses from the recloser's operations and opens automatically after a predetermined count—typically matching the recloser's reclose sequence—during the dead time before lockout. This sequential operation ensures the sectionalizer isolates only the faulted section upon the recloser's final , allowing upstream while limiting the outage to the affected lateral. Proper timing is critical, with the sectionalizer's opening speed faster than the recloser's dead time and its reset period longer than the reclose interval to avoid misoperation. Integration with protective s, particularly those at substations, enables upstream-downstream grading to maintain system selectivity across the distribution network. Upstream s are configured with time delays longer than the recloser's operating times, allowing downstream reclosers to clear faults first and preventing widespread outages from substation breakers. This grading extends to sequence coordination, where the upstream or recloser adjusts its reclose attempts to match or differ by one from the downstream , ensuring backup protection without premature tripping. Such coordination is essential for handling evolving faults, where initial recloses may fail, and the upstream intervenes only after downstream exhaustion. In loop schemes, two reclosers at the ends of a normally open tie point, combined with mid-line sectionalizers, significantly enhance reliability by enabling automatic reconfiguration. Upon detecting a fault, the nearest recloser isolates the section, the sectionalizer pinpoints and opens the faulted segment, and the tie closes to restore power from the alternate source, potentially reducing the number of affected customers by up to 90% compared to radial configurations. This approach minimizes outage duration and scope, as demonstrated in utility implementations where fault isolation limits interruptions to isolated laterals rather than entire feeders.

Safety and Environmental Aspects

Fire and Wildfire Mitigation

Reclosers play a critical role in mitigating fire and wildfire risks by addressing the ignition hazards posed by electrical faults in overhead distribution lines. High-impedance ground faults, such as those caused by downed conductors contacting dry vegetation, can produce sustained fault arcs with currents as low as 200-500 mA, generating sufficient heat to ignite surrounding foliage under dry conditions. Sensitive Earth Fault (SEF) protection integrated into reclosers detects these low-level imbalances, tripping the device to isolate the fault before prolonged arcing occurs. Studies indicate that SEF settings at 500 mA can reduce the risk of fire ignition from such faults by approximately 80%, as these faults account for a significant portion of vegetation-contact ignitions in overhead networks. To further minimize ignition potential, reclosers employ specialized operational modes tailored to elevated fire danger. In "total fire" or non-reclose configurations, automatic reclosing is disabled on high-risk days—such as those declared under total fire bans—preventing repeated energization of a faulted line that could exacerbate arcing and spark dry materials. This tripping approach ensures immediate isolation without retries, prioritizing safety over service restoration during extreme conditions. Additionally, in bushfire-prone areas, reclosers can be programmed with reduced thresholds, such as 200 mA for SEF detection, to capture even subtler faults that might otherwise go unnoticed and lead to smoldering ignitions. These adjustments are dynamically applied based on forecasts and local risk assessments, balancing protection with grid reliability. Post-2009 Black Saturday bushfires in , , which were partly attributed to powerline faults, prompted the implementation of stringent protocols through the Victorian Bushfires recommendations and the subsequent Powerline Bushfire Safety Taskforce. These included mandatory SEF-equipped reclosers and non-reclose modes on high fire danger days across affected networks, significantly enhancing fault isolation in rural distribution systems. In the United States, (PG&E) adopted Enhanced Powerline Safety Settings (EPSS) on reclosers and similar devices starting in 2021, which incorporate faster tripping and non-reclose operations in high fire-threat districts; this initiative achieved an 80% reduction in reportable ignitions within the first year of deployment (as of December 31, 2021). Recent advancements integrate sensor networks with recloser controls for proactive prevention. sensors, such as those using detection for partial discharges or thermal imaging for hot spots, feed real-time data to recloser relays, enabling preemptive tripping before faults escalate to ignitions. For instance, systems like those from Sentient Energy and allow reclosers to adjust settings dynamically in response to detected anomalies or rising fire weather indices, linking early fault signatures directly to commands. This sensor-recloser has shown promise in pilot programs, reducing response times and containing potential starts at their inception.

Standards and Regulations

Reclosers, as automatic circuit breakers used in medium-voltage distribution networks, are governed by several international standards that ensure their performance, testing, and . The IEC 62271-111:2019 standard specifies requirements for overhead, pad-mounted, dry vault, and submersible single- or multi-pole automatic circuit reclosers and fault interrupters for rated voltages above 1 kV and up to 38 kV, focusing on , , and operational capabilities in medium-voltage applications. Complementing this, the IEEE C37.60 standard outlines testing procedures for reclosers and recloser controls, including requirements for interrupting ratings, operating duty, and mechanical endurance to verify reliability under fault conditions. For integration with distributed energy resources (DER), the IEEE 1547-2018 standard establishes uniform criteria for interconnecting DER with systems, mandating protective functions in reclosers such as anti-islanding and ride-through capabilities to maintain grid stability. Environmental regulations increasingly target the use of (SF6) in reclosers due to its high . The EU F-gas (EU) 2024/573, effective from March 2024, accelerates the phase-out of SF6 in new medium-voltage , including reclosers, with prohibitions starting in 2026 for installations up to 24 kV and requiring tested annual leakage rates below 0.1% for permitted equipment to minimize emissions. This regulation promotes alternatives like vacuum interrupters and solid dielectric technologies, which offer lower environmental impact without compromising performance in recloser applications. Regional variations address specific risks, such as . In and , reclosers in bushfire-prone areas must comply with network configuration guidelines under the Electricity Safety (Bushfire Mitigation) Regulations 2023, which include disabling automatic reclosing during total fire ban days on rural overhead lines to prevent ignition from fault arcs. In , the NERC PRC-005-6 standard requires documented maintenance programs for protection systems, including automatic reclosing devices affecting bulk electric system reliability, with intervals based on manufacturer's recommendations and performance data. Compliance with these standards imposes requirements like mandatory event in reclosers for operational audits, enabling utilities to track faults, reclose attempts, and maintenance history to demonstrate adherence to testing and reliability criteria. Recent updates in cybersecurity, such as IEC 62351-9:2023, extend to reclosers with controls by specifying protocols for securing communications in system equipment, with ongoing revisions through 2025 enhancing protection against cyber threats in integrations.

References

  1. [1]
    [PDF] What is a recloser? - Eaton
    A recloser is an automatic, high-voltage electric switch. Like a circuit breaker on household electric lines, it shuts off electric power when.Missing: engineering | Show results with:engineering
  2. [2]
    Recloser Fundamentals | NOJA Power
    A Recloser is a special type of electrical circuit breaker that is designed to rapidly open and close. Unlike circuit breakers, which are designed to “trip” ...
  3. [3]
    Automatic Circuit Recloser: Fundamentals - Tavrida Electric
    Automatic Circuit Recloser (ACR) is an intellectual protective device capable of interrupting fault current and which purpose is to increase distribution ...
  4. [4]
    [PDF] Recloser general ratings information catalog - Eaton
    Extensive studies of overhead distribution systems have established that approximately 80 to 95 percent of all system faults are temporary in nature and, at ...
  5. [5]
    Elastimold Solid Dielectric Reclosers – Single-phase up to 38 kV
    The single-phase recloser contains no oil or gas but uses solid dielectric insulation with vacuum interruption for virtually maintenance-free operation.Missing: interrupter immersed SF6
  6. [6]
    Outdoor vacuum recloser (OVR) - Outdoor (Medium Voltage - ABB
    ABB's OVR is a three-phase vacuum recloser, for IEC and ANSI standards, rated up to 38 kV, with a solid dielectric insulator designed. ABB's OVR reclosers ...Missing: types oil SF6
  7. [7]
    Viper-HV Recloser - G&W Electric
    G&W Electric's Viper-HV 72.5KV recloser is designed to provide overcurrent protection through fault isolation and automatic restoration.
  8. [8]
    VSA electronically controlled three-phase reclosers - Eaton
    VSA reclosers are electronically controlled, three-phase, automatic circuit reclosers with vacuum interrupters, providing overcurrent protection with ratings ...
  9. [9]
    Fundamentals of reclosers | Eaton
    A recloser is an automatic, high-voltage electric switch that shuts off electric power when trouble, such as a short circuit, occurs.
  10. [10]
    NOVA three-phase recloser | vacuum interruption - Eaton
    Eaton's Cooper Power series NOVA recloser is a three-phase, vacuum-interrupting recloser that successfully combines four patented technologies.Missing: immersed SF6
  11. [11]
  12. [12]
    Vacuum Circuit Breaker: Fundamentals - Tavrida Electric
    Arc Quenching - is the process of influencing an electric arc, leading to its complete extinction at the moment when the power frequency current reaches zero.
  13. [13]
    [PDF] D1 Auto-Reclosing - Schneider Electric
    The circuit breakers must have very short operation times and then be able to reclose the circuit after a dead time of the order of 0.3s-0.6s to allow for fault ...Missing: 1.5 | Show results with:1.5
  14. [14]
    [PDF] SEL-651R Recloser Control - Schweitzer Engineering Laboratories
    Learn the settings and operation of one recloser control and retrofit numerous existing recloser installations. Three-Phase Reclosers With. Single-Phase ...
  15. [15]
  16. [16]
    Inverse Time Overcurrent Relays and Curves Explained - Articles
    Jul 29, 2021 · A = Time factor for over-current trip · I = Actual Current · Is = Relay Pickup Setting · = Exponent for inverse-time · B = Timer coefficient for ...
  17. [17]
    Cooper power series - Eaton
    Kyle Corporation started as Electrical Connectors and Manufacturing Company in 1933. In the early 1940s, Kyle marketed a number of innovative circuit reclosers ...
  18. [18]
    Automatic reclosing circuit breaker - US2459327A - Google Patents
    AUTOMATIC RECLOSING CIRCUIT BREAKER Original Filed June 6, 1941 3 Sheets- Sheet 2 IIFI: Jan. 18, 1,949. w. D. KYLE, JR., ErAL AUTOMATIC RECLOSING CIRCUIT ...
  19. [19]
    Top Auto Recloser Manufacturers | Reliable Grid Solutions 2025
    Aug 15, 2025 · Kyle Corporation developed the first oil-filled hydraulic reclosers in the early 1940s in the USA, featuring basic mechanical protection ...
  20. [20]
    History - America's Electric Cooperatives - NRECA
    Enjoy a fast-paced hand-drawn history of America's electric cooperatives. As late as the mid-1930s, nine out of 10 rural homes were without electric service.Missing: reclosers post-
  21. [21]
    [PDF] Ensuring Recloser Control Compliance With IEEE C37.60–2003 ...
    1950s. Technology ... Choose equipment that meets or exceeds IEEE and IEC standards for protective relays as well as the IEEE standards for reclosers.
  22. [22]
    IEEE/AIEE 50-1949
    This standard applies to all single or multipole alternating-current automatic circuit reclosers rated from 1,500 to 15,000 volts. Status: Superseded Standard ...Missing: 1950s | Show results with:1950s
  23. [23]
    IEEE/AIEE 50-1953
    This standard applies to all single or multipole alternating-current automatic circuit reclosers for the nominal voltages from 1,500 to 23,000 volts.Missing: 1950s | Show results with:1950s
  24. [24]
    Recloser - Wikipedia
    A recloser, also known as autorecloser or automatic circuit recloser (ACR), is a switchgear designed for use on overhead electricity distribution networks
  25. [25]
    Application benefits of single-phase digitally controlled vacuum ...
    This technology has been used in the area of single phase reclosers. The electronic method of recloser control is more flexible, more easily adjusted and ...Missing: evolution | Show results with:evolution
  26. [26]
  27. [27]
    [PDF] Effect of Distribution Automation on Protective Relaying
    In the early 2000's microprocessor based relays became available in pole mounted controls for distribution line reclosers. In some cases, these line devices ...
  28. [28]
    Recloser Control Market Growth & Trends - ReAnIn
    The integration of digital automation and smart communication is transforming recloser controls. Roughly 41% of deployed systems now feature microprocessor- ...<|separator|>
  29. [29]
    Advantages of Vacuum Interrupter Technology in Medium Voltage ...
    The OSM Series uses vacuum interrupters enclosed within a solid dielectric pole to achieve rated voltages of 15kV, 27kV and 38kV, which have all been ...Missing: immersed | Show results with:immersed
  30. [30]
    Are vacuum interrupters environmentally friendly? - Knowledge
    Jun 7, 2024 · Vacuum interrupters are considered naturally inviting for a few reasons. Firstly, they contain no nursery gasses such as SF6, which is commonly ...
  31. [31]
    What is distribution system loop automation? - Schneider Electric
    Feb 21, 2011 · Using standard recloser features, the Loop Automation Scheme reconfigures protection settings, sectionalises faults, minimises affected areas, ...Missing: solid- state adaptive 2010s
  32. [32]
    Autoloop system and method of operation - Google Patents
    An automatic loop system for an electrical distribution system is provided. The system includes a first branch circuit having a first feeder recloser and a ...
  33. [33]
    [PDF] Advanced Automation and Protection Coordination: Leveraging AI ...
    Findings indicate that AI techniques (e.g., machine learning for fault prediction) and widespread sensor data can reduce fault detection and isolation times ...
  34. [34]
    Recloser Industry worth $1.5 billion by 2030 - MarketsandMarkets
    Mar 25, 2024 · The global Recloser Market industry growth is projected to be USD 1.5 billion by 2030, growing from USD 1.1 billion in 2024, at a Compound ...
  35. [35]
    IEC 62271-111:2005
    This standard covers required definitions, ratings, procedures for performing design tests, production tests, and construction requirements for overhead, ...
  36. [36]
    IEC 62271-111:2019
    Feb 12, 2019 · IEC 62271-111:2019 applies to all overhead, pad-mounted, dry vault and submersible single or multi-pole alternating current automatic circuit reclosers.
  37. [37]
    [PDF] Summary of C37.230-2007, IEEE Guide for Protective Relay ...
    A recloser is defined as a “protective device that combines the sensing, relaying, fault interrupting and reclosing functions in one integrated unit ...Missing: mechanisms | Show results with:mechanisms
  38. [38]
    Improvement of Recloser-Fuse Operations and Coordination in a ...
    Dec 23, 2010 · Here, the recloser is set to trip using TCC curve for a temporary fault before any of the fuses can melt. If the fault is a permanent fault ...
  39. [39]
    Techniques for Detecting Earth or Ground Faults on Delta Networks
    The OSM Recloser can also report which phase had the lowest voltage at the fault site, allowing utility engineers to determine both the faulted phase and ...
  40. [40]
    [PDF] REVIEW OF GROUND FAULT PROTECTION METHODS FOR ...
    This paper reviews ground fault protection and detection methods for distribution systems. First, we review and compare medium-voltage distribution-system ...
  41. [41]
    Auto-recloser whys and wherefores | Megger
    Sep 30, 2017 · Auto-reclosers are most commonly found in overhead cable networks and they are useful because, in such networks, only around 7% of faults are permanent.<|control11|><|separator|>
  42. [42]
    Identification, Prioritization, and Placement of Automatic ...
    Jul 27, 2015 · ... open on loss of voltage. • Tie Recloser (T) – Normally open, close on loss of voltage. Circuit transfers are designed with peak loads in mind.
  43. [43]
    [PDF] Distributed Generation Intertie With Advanced Recloser Control
    In voltage-supervised reclosing, a voltage signal from the load side (rather than the source side) of a reclosing device (breaker, recloser) can be used as a ...
  44. [44]
    Auto-reclose schemes for re-energising the line after a fault trip | EEP
    May 15, 2017 · 80-90% of faults on any overhead line network are transient in nature. The remaining 10%-20% of faults are either semi-permanent or permanent.
  45. [45]
    Distribution System Transient Measurement Data Evaluation
    May 27, 2022 · These types of faults are usually caused by lightning strikes to the circuit, tree limbs contacting the circuit, or animals contacting the ...
  46. [46]
    [PDF] Analysis of distribution system reliability and outage rates | Eaton
    Therefore, if 70% of faults are initially transient by nature, outage rates will decrease by 70%.
  47. [47]
    Lightning Protection: Improving Reliability Through the Use of Surge ...
    Apr 1, 2005 · Several studies in recent years indicate that outages related to lightning can account for up to 40 percent of the total outages experienced.
  48. [48]
    [PDF] Vegetation Management Resilience Investment Guide
    Vegetation-related impacts to the power system are the most common cause of power outages in the U.S., accounting for more than twenty percent of incidents [1,2] ...
  49. [49]
    Reclosing 101 | NOJA Power - Recloser Switchgear Engineers
    Configuring auto reclosing circuit breakers requires an understanding of likely fault scenarios for the overhead distribution network.
  50. [50]
    [PDF] Advanced Recloser Protection & Control RER620 Product guide - ABB
    The relay also features optional high impedance fault (HIZ) and sensitive earth fault (SEF) protection for grounded and un- grounded distribution systems. Also, ...
  51. [51]
    [PDF] Evaluating Overhead Line Reclosing Sequences Based on ...
    This paper evaluates reclosing sequences using transformer through-fault capability curves to assess damage from reclosing into faults, considering temporary ...
  52. [52]
    None
    ### Summary of Recloser Benefits for Reliability Indices
  53. [53]
    [PDF] Reliability Improvements from the Application of Distribution ...
    In general, reliability improved overall because of reductions in SAIFI and SAIDI. The projects expect that improvements in outage frequency and CMI to continue ...
  54. [54]
    Recloser Fundamentals: Understanding Reclosers on Poles
    Jun 17, 2025 · Reclosers on poles automatically detect and interrupt temporary faults, then quickly restore power by reclosing the circuit, minimizing outages.Why Is A Recloser Pole... · Understanding Pole Mounted... · Types Of Reclosers On PolesMissing: logic | Show results with:logic
  55. [55]
    Pad-mounted Types PWE, PWVE Three-Phase Recloser - Eaton
    Designed for 15 and 27 kV system applications, such as feeder protection, sectionalising and transformer high-side protection, these reclosers are pad-mounted ...Missing: configurations | Show results with:configurations
  56. [56]
    [PDF] THE POTENTIAL BENEFITS OF DISTRIBUTED GENERATION AND ...
    respectively) and average reliability being about three to four nines, or 99.9% to 99.99%. ... rural electric cooperatives and municipal utilities. IOUs are ...
  57. [57]
    [PDF] Bulletin 1724E-102 RD-GD-2012-68 - USDA Rural Development
    Oct 23, 2012 · This bulletin is a guide for making sectionalizing and protection studies on electric distribution systems for rural electric cooperatives. It ...
  58. [58]
    Microgrid Protection Challenges and Mitigation Approaches–A Comprehensive Review
    **Summary of Challenges of Reclosers with Renewable Integration (from https://ieeexplore.ieee.org/document/9749209):**
  59. [59]
    Cogeneration and Sync-Check with Reclosers - NOJA Power
    How to use Cogeneration Protection features and ANSI 25 Synchrocheck to connect renewable energy to the distribution network.
  60. [60]
    Distributed Energy Generation Connection Using Reclosers
    Aug 31, 2021 · To avoid stress on the system when connecting DG to the grid Sync check feature is often specified as a requirement for DG connection switchgear ...
  61. [61]
  62. [62]
    [PDF] Protection of Distribution Circuits with High Penetration of Solar PV
    Oct 7, 2021 · The recloser at the PV site is primary protection for faults in zone 7. Looking back into the grid, this recloser should also trip to clear ...
  63. [63]
    Multilin R650 Recloser Controller | GE Vernova
    ### Summary of GE Multilin R650 Recloser Features
  64. [64]
    (PDF) Smart Grid Data Analytics for Digital Protective Relay Event ...
    Aug 10, 2025 · Digital protective relays are multi-functional intelligent electronic devices based on microprocessors, which are being installed in substations ...
  65. [65]
    The Benefits of IoT: Real World Examples | Digi International
    Remotely monitoring and managing meters, reclosers and other equipment in utilities. Detecting gas leaks in oil and gas operations. Tracking the location of ...
  66. [66]
    Recloser monitoring and control - Viasat
    Easy integration: Viasat's small, low-power IoT Pro terminal easily integrates with reclosers to provide reliable, uniform coverage, while its standard IP ...Missing: examples | Show results with:examples
  67. [67]
    Automatic Recloser Adjustment for Power Distribution Systems
    In this paper, a self-adaptive protection system is proposed for adjusting the time dial (TD) of reclosers found in electrical power distribution systems ...
  68. [68]
    US20040105204A1 - Adaptive protection for recloser control
    A recloser is adaptively controlled so that it will operate in a manner responsive to prevailing conditions such as time of day, day of week, and/or load ...
  69. [69]
    [PDF] Automatic Loop Restoration - S&C Electric Company
    Dec 19, 2022 · IntelliRupter fault interrupters have 80% more accurate time and current tolerances than conventional reclosers.
  70. [70]
    Cyber security: understanding IEC 62351
    Jan 23, 2023 · IEC 62351 gives detailed advice on protecting energy management systems and on the secure exchange of energy-related data.Missing: reclosers | Show results with:reclosers
  71. [71]
    [PDF] Cyber Security Issues for Protective Relays - PSRC - IEEE PES
    This work is to be published by the IEC as IEC 62351,. Parts 1-7: • IEC 62351-1: Introduction. This first part of the standard covers the background on ...
  72. [72]
  73. [73]
    [PDF] Distribution Automation: Multiple Scheme Complexity & Benefits
    The reliability indices (CAIDI and SAIFI) are often used to track the benchmark reliability performances in terms of reducing outage duration and frequency.<|control11|><|separator|>
  74. [74]
    Bushfire Mitigation using Automatic Circuit Reclosers | NOJA Power
    These reports indicated that reclosers capable of detecting a 500mA Sensitive Earth Fault would reduce fire start risk by 80% [1]. Achieving reliable and ...
  75. [75]
    2009 VBRC - Final Report - Vol 2 - Electricity-Caused Fire
    Sensitive earth protection operates at much lower fault ... Parliament of Victoria | © 2009 Victorian Bushfires Royal Commission, Australia.
  76. [76]
    Techniques to mitigate bushfire risk when deploying reclosers
    Apr 23, 2018 · Any form of reclosing is not the solution to wildfire or bushfire mitigation, reclosers must be used in single shot mode on fire risk days.Missing: reduced settings
  77. [77]
    Wildfire Mitigation - Schweitzer Engineering Laboratories
    Mitigate Fire Risk With SEL Recloser Controls · Instantly adjust reclosing and trip behavior in response to weather conditions or local fire risk. · Trip closer ...Missing: sensor- | Show results with:sensor-
  78. [78]
    [PDF] Powerline Bushfire Safety Taskforce: Final Report - Energy
    Sep 30, 2011 · Victorian Bushfires Royal Commission (―Royal Commission‖) related to powerline replacement ... settings (for example sensitive earth fault ...
  79. [79]
    [PDF] Enhanced Powerline Safety Settings - PG&E
    • Free and reduced-cost backup power options. • How safety settings protect you from wildfire risk. Last year, we saw a 65% reduction in ignitions on.
  80. [80]
    Wildfire Risk Mitigation Solutions | Sentient Energy
    Sentient Energy's wildfire mitigation solution is powered by the Ample Analytics Platform. Intelligent MM3ai overhead line sensors detect faults.
  81. [81]
    Flexible Reclosers for Fire Mitigation | G&W Electric
    Jun 17, 2025 · Discover how flexible recloser designs improve wildfire mitigation by enhancing grid adaptability, fault isolation, and protection for critical
  82. [82]
    IEEE C37.60-1981
    This standard applies to all overhead, pad mounted, dry vault and submersible single or multi-pole alternating current automatic circuit reclosers and fault ...
  83. [83]
    [PDF] Introduction to​ IEEE 1547 Standard For Interconnecting Distributed ...
    Nov 9, 2023 · Purpose: This document provides a uniform standard for the interconnection and interoperability of distributed energy resources (DER) with ...
  84. [84]
    EU-Rules - Fluorinated Greenhouse Gases – Climate Action
    Building on the success of its predecessor, the F-gas Regulation (EU) 2024/573 was adopted on 7 February 2024 and started to apply on 11 March 2024. The F-gas ...
  85. [85]
    [PDF] UNIFE F-Gas Regulation factsheet November 2024
    The phase-out of F-gases will be significantly accelerated through a more stringent phase-down. The phase-down until 2032 was set in the F-Gases Regulation (EU) ...Missing: reclosers | Show results with:reclosers
  86. [86]
    [PDF] ISSC 33 Guide for Network Configuration During Total Fire Ban Days
    It's recommended that auto-reclose be disabled on TOBAN days on rural overhead bare conductor radial 11kV, 22kV, 12.7kV SWER and 33kV where: feeders are deemed ...
  87. [87]
    IEC 62351-9:2023
    CHF 410.00Jun 6, 2023 · IEC 62351-9:2023 specifies cryptographic key management, primarily focused on the management of long-term keys, which are most often asymmetric key pairs.