Losses in electrical systems

Losses in electrical systems refer to the dissipation of as , , or other non-useful forms during the , , , and utilization of , leading to reduced and increased operational costs. These losses occur due to inherent physical limitations in materials and components, as well as external factors, and are a critical concern in for optimizing energy delivery. Technical losses, which are predictable and stem from the electrical properties of system elements, constitute the majority and include resistive (Joule or I²R) losses in conductors and windings, losses ( and eddy currents) in transformers and magnetic devices, dielectric losses in insulators, losses from in high-voltage lines, losses at higher frequencies, and impedance-related losses. technical losses, such as I²R, scale with the square of the and account for about two-thirds to three-quarters of technical losses, while fixed losses like and remain relatively constant regardless of load. Non-technical losses, often called commercial losses, arise from human activities including , metering errors, and unbilled usage, and can represent a significant portion in some regions, though they are harder to quantify precisely. Across the power chain, losses typically range from 3-5% of the load due to high-voltage, low-current , but losses are higher at around 4-10% owing to lower voltages, greater line lengths, and branching networks. Globally, combined and losses average 8-9% of total output, varying by region with developing countries often experiencing higher rates up to 20% or more due to challenges. Utilization losses in end-user equipment, such as (where inefficiencies can add 10-20% due to harmonics) and (e.g., incandescent bulbs at 10-21 lumens per watt), further compound the total, emphasizing the need for efficient designs and technologies. Mitigation strategies, including high-temperature low-sag conductors, reactive power compensation, and monitoring, can reduce these losses by 20-70% depending on the application.

Fundamental Concepts

Definition and Classification

Losses in electrical systems refer to the unintended dissipation of into forms such as , , or during the , , or utilization of , rather than delivering it as useful work. These losses arise inherently from the physical properties of materials and components, reducing the overall of the system. Such losses significantly impact electrical infrastructure by lowering , elevating operational costs, and contributing to substantial global energy waste; for instance, worldwide electricity transmission and distribution losses are estimated at 8-10% of total output annually. This inefficiency not only increases the demand for additional power generation but also exacerbates environmental concerns through higher fuel consumption and emissions. Electrical losses are primarily classified into four categories: conduction losses, which involve ohmic heating due to in conductors; magnetic losses, encompassing in ferromagnetic materials and currents induced in conductive cores; dielectric losses, occurring in insulating materials under alternating fields; and radiative or losses, such as or frictional effects in moving parts. A fundamental representation of conduction losses is given by the equation for power dissipation in resistive elements: P = I^2 R where P is the power loss in watts, I is the in amperes, and R is the in ohms. This formula derives from Joule's first law, which states that the heat generated by an is proportional to the square of the current and the , based on experimental observations of conversion in circuits. The recognition of these losses traces back to the 1840s, when conducted pioneering experiments demonstrating heat production from electric currents in wires, establishing the quantitative relationship between and thermal dissipation.

Measurement and Quantification

Direct measurement of electrical losses in power systems typically involves comparing input and output power using instruments such as wattmeters or power analyzers to determine the difference, which represents the total losses under operating conditions. This approach is particularly useful for components like or transformers where real-time power flow can be accurately metered. Indirect methods, such as temperature rise tests, estimate losses by monitoring heat generation and dissipation in components, often correlating thermal profiles to energy dissipation rates. Thermal imaging techniques further enable non-contact assessment of hotspots indicative of localized losses, aiding in system-wide diagnostics without interrupting operation. Calorimetric methods combine thermal and to isolate specific loss components, such as switching or conduction energies in . Efficiency in electrical systems is quantified using the metric \eta = \frac{P_{out}}{P_{in}} \times 100\%, where P_{out} is the useful output power and P_{in} is the total input power. This formula derives from the , where losses P_{loss} = P_{in} - P_{out}, and can be expressed as P_{loss} = P_{in} (1 - \eta), highlighting how inefficiencies manifest as dissipated , often in the form of . For system-wide evaluation, loss factors like the load factor—defined as the ratio of average load to peak load over a —and the —the ratio of the sum of individual maximum demands to the overall system maximum demand—provide context for quantifying aggregate losses by accounting for load variability and . Higher load factors indicate more consistent operation, reducing relative losses, while diversity factors help estimate non-coincident peaks that lower overall system and associated . Standardized testing protocols ensure consistent measurement of losses across components. The IEEE C57.12.90 standard outlines procedures for no-load tests, which apply rated voltage to measure losses without current draw, and short-circuit tests, which energize the winding under shorted conditions to quantify losses at full load. Similarly, IEC 60076-1 specifies these tests for transformers, emphasizing impedance voltage and loss measurements to verify performance limits. These guidelines, adopted globally, facilitate comparability and compliance in design and operation. Electrical losses are typically expressed in watts (W) for absolute power dissipation or as percentages of total input power to indicate relative impact, with system aggregation computed as the sum of individual component losses, P_{total\ loss} = \sum P_{i\ loss}, to evaluate overall efficiency. For instance, transmission losses might contribute 2-4% of generated power in watts, scaled across the network for total quantification. This approach allows utilities to benchmark and minimize cumulative effects in large-scale systems.

Losses in Power Generation

Generator Core and Winding Losses

In electrical , winding losses, also known as losses, arise primarily from the resistive heating in the armature and field windings due to the flow of . These losses are quantified for a three-phase as P_{cu} = 3 I^2 R_a, where I is the phase and R_a is the armature resistance per phase. This formula derives from Joule's law applied to each phase, with the factor of 3 accounting for the three phases in synchronous generators. Core losses in generators occur in the due to the alternating and are divided into and components. loss results from the required to reverse the magnetic domains in the core and is given by the Steinmetz : P_h = \eta B_{max}^{1.6} f V, where \eta is the , B_{max} is the maximum density, f is the , and V is the core volume. loss stems from induced circulating currents in the core, opposing the changes, and is expressed as P_e = \frac{\pi^2 B_{max}^2 f^2 t^2}{6 \rho} V, where t is the thickness and \rho is the resistivity. These losses are minimized through of the core to reduce currents and selection of low- materials. Several factors influence the magnitude of and winding losses in generators. Winding losses vary quadratically with load , increasing significantly under high-load conditions, while losses remain relatively constant as they depend primarily on voltage and . choices, such as silicon steel for cores, reduce by increasing resistivity and optimizing grain orientation, leading to lower overall losses compared to earlier carbon steels. Effective cooling methods, including air, , or liquid cooling, help dissipate heat from windings and cores, preventing efficiency degradation and allowing higher load capacities without excessive temperature rise. In typical synchronous generators, total electrical losses (including core and winding) are often below 5% of the rated for large units. losses typically account for 30-60% of these total losses, or about 0.5-1.5% of rated at full load, while losses contribute around 20-30%. These values highlight the scale of impact, where even small reductions can yield significant efficiency gains in generation. The evolution of design has progressively reduced these losses, transitioning from early generators with higher resistive and commutation losses to modern synchronous alternators featuring improved , thinner laminations, and advanced materials like high-silicon , achieving efficiencies over 98% in large-scale applications.

Auxiliary and Parasitic Losses

Auxiliary losses in power generation facilities encompass the consumed by essential support systems, such as pumps, fans, and , which are necessary for plant operation but do not contribute directly to electrical output. These losses typically account for 5-12% of gross generation in coal-fired thermal power plants, with an average around 8-9% of output in conventional plants. For instance, in a 210 MW coal-fired unit, feed pumps can consume about 2.95% of total , while induced and forced draft fans together account for roughly 1.7%. In thermal plants, cooling water pumps represent a significant portion of these losses, driven by the need to manage from cycles. Parasitic losses, often termed stray load losses, arise from unintended energy dissipations due to leakage fluxes, harmonics, and higher-order effects in the generator and associated systems. These are estimated at 0.5-1% of rated in large synchronous machines, as per IEEE test procedures, which involve segregating them from other load components through short-circuit and separation methods. Such losses become more pronounced under varying load conditions, where harmonic currents induce eddy currents in structural components like frames and clamping plates. Mechanical losses within generators include bearing and , which dissipate energy through physical interactions and air resistance on rotating parts. Bearing arises from and contact surfaces, while results from drag on the and ventilation fans. These can be quantified using the for mechanical power loss: P_{\text{mech}} \approx k \omega^3 D^5 where k is a machine-specific constant, \omega is the speed, and D is the ; this relation highlights the cubic dependence on speed, making high-speed operations particularly loss-intensive. In fuel-specific contexts, auxiliary and parasitic losses vary by generation type. Fossil fuel plants, such as coal-fired units, experience significant heat losses, with stack or losses reaching up to 20-30% of input energy due to incomplete and excess air, primarily through hot exhaust gases exiting at 150-250°C. Hydroelectric plants, conversely, incur inefficiencies from hydraulic losses, including friction in penstocks and draft tubes, erosion, and , which can reduce overall by 5-10% under off-design flows, though modern plants achieve about 90% .

Losses in Renewable Power Generation

As of 2025, renewable sources like and contribute significantly to global power generation, with their own characteristic losses. In turbines, losses ( and ) similar to synchronous machines account for 2-5% of output, while and aerodynamic losses in blades and gearboxes add 5-10%, leading to overall efficiencies of 35-50% for the turbine system. photovoltaic systems experience inverter losses of 2-5% due to DC-AC inefficiencies, plus panel mismatch and soiling losses up to 5-10% annually, though modern high-efficiency panels and MPPT trackers mitigate these to achieve system efficiencies over 15-20%. These losses highlight the need for advanced and materials in renewables to match conventional efficiencies. Modern quantification of these losses relies on systems, which enable real-time monitoring of parasitic draws and auxiliary consumption across plant components like pumps and fans. By integrating sensors for power, flow, and temperature data, facilitates early detection of inefficiencies, such as elevated fan loads, supporting and overall plant efficiency improvements of up to 2-3% in monitored systems.

Losses in Transmission

Resistive and Inductive Losses

Resistive losses in high-voltage lines primarily arise from the ohmic heating in , known as I²R losses, where the power dissipated as is given by P = I^2 [R](/page/Resistance), with I representing the and R the of the . The R is determined by the R = \rho \frac{[L](/page/Length)}{A}, where \rho is the resistivity of the , L is the of the line, and A is the cross-sectional area. For () , this applies directly, but in () systems, the effective increases due to additional effects, leading to higher overall losses. Inductive losses in transmission lines stem from skin and proximity effects, which are particularly pronounced in AC systems at power frequencies (typically 50 or 60 Hz). The skin effect causes the current to concentrate near the surface of the conductor, reducing the effective cross-sectional area and thereby increasing the AC resistance, quantified as R_{ac} = R_{dc} (1 + y), where R_{dc} is the DC resistance and y is the skin effect factor, often ranging from 0.05 to 0.25 depending on frequency and conductor size. The proximity effect, arising from the magnetic fields of nearby conductors, further distorts current distribution, exacerbating the increase in effective resistance, especially in bundled or closely spaced configurations. These effects collectively elevate the total resistive losses in AC high-voltage lines compared to DC equivalents. Several factors influence the magnitude of these resistive and inductive losses. directly scales the resistance, as losses are proportional to L; for instance, at , losses double for every doubling of length, such as every additional 500 km in typical setups. Conductor material plays a key role, with aluminum commonly used in overhead lines due to its lower and cost despite higher resistivity (\rho \approx 2.65 \times 10^{-8} \, \Omega \cdot \mathrm{m}) compared to (\rho \approx 1.68 \times 10^{-8} \, \Omega \cdot \mathrm{m}), allowing for lighter, more economical spans while maintaining acceptable . Temperature dependence is significant, as resistivity rises approximately 0.4% per °C increase for both materials, amplifying losses during high-load or hot-weather conditions. Typical loss values highlight the efficiency differences between systems: (HVDC) lines experience about 3% loss per 1000 km, primarily from resistive components, while high-voltage alternating current (HVAC) lines incur higher losses, around 7% per 1000 km, due to the added impact of and proximity effects on effective . To mitigate these inductive losses, bundled conductors—such as multiple strands or sub-conductors per —are employed in overhead lines, which distribute current more evenly and reduce the effect by increasing the effective surface area.

Corona and Dielectric Losses

losses occur due to partial electrical discharges in the air surrounding high-voltage conductors, where the strength ionizes the surrounding gas molecules, leading to dissipation as , , and without a complete . This phenomenon is prominent in extra-high-voltage (EHV) systems and results in dissipation that varies with operating conditions. The loss from , denoted as P_c, can be estimated using Peek's empirical formula for fair weather conditions: P_c = \frac{242 (f + 25)}{\delta} \sqrt{r (V - V_0)} \times 10^{-5} \ \mathrm{kW/km/phase} where \delta is the air density factor, f is the supply frequency in Hz, r is the conductor radius in cm, V is the phase-to-ground RMS voltage in kV, and V_0 is the disruptive critical voltage in kV. This formula, derived from experimental data, highlights the dependence on atmospheric and geometric parameters. Several factors influence corona inception and magnitude. Corona typically initiates when the surface exceeds approximately 30 kV/cm under standard atmospheric conditions, a relevant for lines operating above 220 kV. Weather conditions significantly affect losses; for instance, rain reduces air density and introduces water droplets that distort the , increasing corona losses by a factor of 2 to 3 times compared to dry conditions. Conductor design also plays a key role: smooth, polished surfaces promote uniform field distribution and lower losses, whereas stranded conductors with irregular surfaces exhibit higher corona activity due to localized field enhancements at strand junctions. Historically, significant corona issues arose in early 20th-century high-voltage transmission projects, such as the to line operational since 1896, where excessive losses and audible noise prompted pioneering research by F.W. Peek at , culminating in his book on dielectric phenomena that formalized key empirical laws for corona prediction. Measurement techniques for corona include auditory detection of the characteristic hissing or crackling sounds produced by s and (UV) imaging, which captures the non-visible UV emitted, enabling remote identification of sites on live lines. In EHV lines (e.g., 500 kV and above), typical corona losses under wet conditions range from 1-2% of transmitted power, though modern bundled conductor designs mitigate this to lower levels. Dielectric losses in transmission systems arise from energy dissipation as within insulating materials, such as those used in cables or spacers, to the lag in polarization response under alternating . This lag occurs because dipoles in the cannot instantaneously align with the changing field, leading to frictional heating. The extent of these losses is quantified by the loss tangent, defined as \tan \delta = \frac{\varepsilon''}{\varepsilon'}, where \varepsilon'' is the imaginary part of the complex permittivity representing energy loss, and \varepsilon' is the real part representing storage. In high-voltage insulators, low values of \tan \delta (typically below 0.01) are essential to minimize heating and prevent thermal runaway, with losses increasing at higher frequencies and temperatures to enhanced molecular motion.

Losses in Distribution and Utilization

Transformer and Distribution Line Losses

In electrical distribution systems, step-down transformers convert high-voltage transmission power to lower voltages suitable for local delivery, incurring losses that reduce overall efficiency. No-load losses in transformers primarily arise from the core, consisting of hysteresis losses (due to magnetic domain reorientation in the iron core) and eddy current losses (from induced circulating currents in the core laminations), collectively expressed as P_{nl} = P_h + P_e, where P_h is the hysteresis component and P_e is the eddy current component. These losses, which account for over 99% of no-load power dissipation, occur even without connected load and are influenced by the core material's magnetic properties and excitation frequency. Load losses, on the other hand, stem from resistive heating in the windings, modeled as I^2 R where I is the load current and R is the winding resistance, and increase quadratically with load. Transformer efficiency, defined as the ratio of output to input power, typically peaks around 50% of rated load, where no-load and load losses are balanced, as specified in efficiency standards for distribution units. Transformer designs vary between oil-immersed and dry-type configurations, with oil-immersed units generally exhibiting lower losses due to the superior insulating and cooling properties of , which minimizes energy dissipation in the compared to air or solid dielectrics in dry-type models. Oil-immersed transformers also tend to have overall lower operating losses, enhancing in high-capacity applications, though they require to prevent oil degradation. Dry-type transformers, while safer in fire-prone environments, often incur higher and no-load losses from increased thermal resistance in air-cooled systems. These differences influence selection for urban distribution, where space and constraints favor dry-type units despite their marginally higher losses. Distribution line losses in local networks mirror transmission resistive losses but are amplified by lower operating voltages (typically 11-33 ), necessitating higher currents for the same delivery via P = I^2 R, where elevated I significantly boosts heating in conductors and connections. Urban branching further exacerbates these losses through extensive low-voltage feeders, numerous joints, and shorter but more numerous segments, leading to cumulative effects. Globally, distribution losses average 6-8% of generated , higher than transmission's 2-4%, reflecting these factors and varying quality. Underground cables in distribution systems introduce higher shunt than overhead lines—often 10-20 times greater—resulting in increased charging currents and reactive demands that indirectly elevate losses if uncompensated, though dielectric losses remain minor compared to conductor heating. Nonlinear loads, such as variable frequency drives and electronics, introduce harmonics that distort current waveforms, increasing losses by 20-30% through amplified eddy currents, in windings, and additional stray losses. These harmonics elevate both and losses, accelerating aging and necessitating or specialized designs for mitigation. Standards like ANSI/IEEE C57.12.90 and C57.123 govern testing, mandating separate of no-load (-dominated) and load (winding-dominated) losses under controlled conditions to ensure and accurate evaluation. Such protocols enable precise quantification, typically at rated voltage for no-load and short-circuit conditions for load, supporting loss minimization in distribution networks.

Load-Specific Losses in Devices

Load-specific losses in electrical devices primarily arise from inefficiencies in converting electrical energy to the intended output, such as mechanical work, light, or heat, within end-user appliances and equipment. In electric motors, which are ubiquitous in pumps, fans, and compressors, losses include rotor and stator copper losses due to resistive heating in windings (typically 25-40% stator and 15-25% rotor of total losses), core losses from hysteresis and eddy currents in the magnetic material (15-25%), and mechanical losses from friction in bearings and windage from air resistance (5-15%). Stray load losses, encompassing leakage flux and harmonic effects not captured in other categories, account for 10-20% and are standardized under NEMA MG 1-2011, where they are segregated during efficiency testing via IEEE 112 methods. Overall, these components result in total losses of 5-10% of input power in premium efficiency induction motors, corresponding to efficiencies of 89.7-96.2% at full load. Lighting systems exhibit significant load-specific losses, particularly in older technologies. Incandescent bulbs convert only about 10% of electrical energy to visible light, with 90% dissipated as heat from filament resistance, making them highly inefficient for illumination. In contrast, light-emitting diode (LED) lamps achieve higher efficiencies through phosphor conversion, where blue LED emissions excite phosphors to produce white light, but incur 20-30% losses from non-radiative recombination and thermal effects in the phosphor layer. These losses are quantified in wall-plug efficiency metrics, with phosphor-converted white LEDs reaching up to 76% efficiency before additional system overheads. Common household appliances like electric irons and rely on resistive heating elements, which intentionally convert nearly 100% of input to during operation, aligning with their functional purpose. However, standby losses occur when devices remain powered but idle, drawing for displays, controls, or readiness features. In within inverters for appliances like air conditioners or solar systems, switching losses dominate, calculated as P_{sw} = \frac{1}{2} f C V^2, where f is switching frequency, C is output , and V is voltage, representing energy dissipated during turn-on and turn-off transitions. Standby power, often termed phantom loads, represents a pervasive consumer impact, consuming 5-10% of total household electricity on average across devices like televisions, chargers, and microwaves even when not in active use. This inefficiency arises from always-on circuits maintaining minimal functionality, contributing to unnecessary energy bills and grid demand. Recent trends toward efficient devices have mitigated these losses, exemplified by the adoption of IE4 (super premium efficiency) motors since 2010, which reduce total losses by approximately 20% compared to IE3 (premium) standards through advanced materials and designs. Further advancements include IE5 (ultra-premium efficiency) motors, introduced in 2016 per IEC 60034-30-2, achieving about 20% loss reduction relative to IE4, with increasing regulatory adoption in the EU and elsewhere as of 2023 for motors above certain power ratings. This shift, aligned with IEC 60034-30-1 regulations, has driven broader efficiency gains in motor-driven appliances, lowering operational losses without compromising performance.

Impacts and Mitigation

Economic and Environmental Effects

Electrical losses in power systems impose substantial economic burdens worldwide, primarily through the value of wasted , increased fuel consumption, and the need for excess capacity. Global transmission and distribution (T&D) losses average around 8%, representing a financial estimated at $200–300 billion annually when accounting for the cost of lost at prevailing market rates and the associated higher operational expenses for utilities. These costs encompass not only the direct value of unelectrified but also elevated investments in infrastructure to compensate for inefficiencies, straining budgets in both developed and developing economies. Environmentally, these losses amplify by necessitating additional fossil fuel-based generation to deliver the required power to end-users. Globally, compensatory generation for T&D losses contributes nearly 1 billion metric tons of CO₂ equivalents per year, equivalent to about 8% of energy-related CO₂ emissions from the sector. For context, a 1% increase in transmission losses alone can add roughly 130 million metric tons of CO₂ annually, accelerating and hindering climate mitigation efforts through inefficient use of finite fuels like and . Case studies illustrate these effects at national scales. In , distribution losses averaging around 17% as of FY 2023-24—driven by technical inefficiencies and non-technical factors like —result in annual economic costs exceeding $20 billion, equivalent to a significant portion of the country's power sector budget and contributing to higher tariffs for consumers. Similarly, in , T&D losses of about 5% require extra that bolsters the electric power sector's share of national emissions, accounting for roughly 1.3% of total U.S. energy-related CO₂, given the sector's overall footprint of about 25%. Beyond direct costs, losses interconnect with broader by inflating , including during peaks, which drives up investments by 10–15% to maintain reliability and capacity. This added strain on grids perpetuates a of higher expenditures for lines and substations. Looking ahead, persistent losses represent a key barrier to targets, as they undermine efficiency gains needed for decarbonization; projections indicate that targeted reductions could cut global losses by up to 5% by 2030, unlocking substantial emissions savings and supporting pathways to a 1.5°C-aligned .

Strategies for Reducing Losses

Strategies for reducing losses in electrical systems encompass material innovations, operational optimizations, advanced technologies, regulatory frameworks, and economic considerations that collectively enhance across , , , and utilization stages. These approaches target resistive, magnetic, and losses without altering core system architectures fundamentally. In material and design enhancements, high-conductivity alloys such as aluminum conductor steel-reinforced (ACSR) lines incorporate steel cores for mechanical strength while maintaining aluminum's conductivity, potentially reducing resistance by approximately 10% compared to traditional designs through optimized stranding. For transformers, cores replace conventional silicon steel, minimizing losses by 50% to 70% due to their disordered atomic structure that lowers magnetic domain reorientation energy. These designs prioritize low-loss materials to curb I²R heating and core inefficiencies from the outset. Operational strategies focus on adapting transmission methods to environmental and load conditions. (HVDC) systems are preferred for long-distance transmission, exhibiting losses about 30% lower than high-voltage alternating current (HVAC) equivalents over distances exceeding 500 km, primarily by eliminating reactive power and skin effects. (DLR) further optimizes overhead lines by using weather data to adjust ratings, increasing throughput by 20-50% without proportional increases, thus avoiding thermal overloads. Such techniques enhance existing utilization while maintaining . Technological advancements leverage digital tools for proactive loss mitigation. Smart grids integrated with artificial intelligence (AI) enable load balancing by forecasting demand and redistributing power in real time, reducing distribution losses by up to 15% through optimized voltage profiles and congestion avoidance. In utilization, variable speed drives (VSDs) for electric motors adjust rotational speeds to match load requirements, achieving energy savings of 20-30% by minimizing unnecessary mechanical work and associated electrical dissipation. These systems promote , integrating sensors and algorithms for granular efficiency gains. Policy and standards drive widespread adoption by setting enforceable benchmarks. The European Union's Ecodesign Directive (Regulation (EU) No 548/2014) imposes stricter maximum limits on no-load and load losses for Tier 2 compliance since 2021, with no-load losses reduced by 10% compared to levels for transformers, specified as absolute values via formulas based on rated capacity. Such regulations ensure market-wide improvements, aligning with global efforts to curb energy waste. Cost-benefit analyses underscore the viability of these strategies, with rapid paybacks incentivizing implementation. For instance, LED lighting retrofits in commercial settings often recover initial costs within 1-2 years through 50-70% reductions in utilization losses, factoring in lower bills and maintenance. Broader initiatives, such as the International Energy Agency's (IEA) programs, target a 2% annual reduction in global energy losses by promoting scalable technologies and policy harmonization, yielding cumulative savings equivalent to avoiding new power plants. These evaluations highlight net positive returns, often within 1-5 years, depending on scale and incentives.

References

  1. [1]
    Technical Losses in Power Networks: Mechanisms, Mitigation ...
    Power losses in electrical grids are typically categorized into technical and non-technical components. NTLs stem from unmetered or unbilled energy consumption, ...
  2. [2]
    [PDF] LOSSES IN ELECTRIC POWER SYSTEMS - Purdue e-Pubs
    Dec 1, 1992 · This report discusses losses in power systems, from transmission to utilization, including transmission, distribution, lighting, and motors.  ...
  3. [3]
    Total Losses in Power Distribution and Transmission Lines | EEP
    Mar 28, 2025 · This article discusses two types of transmission and distribution losses, technical losses and non-technical losses (or commercial losses)
  4. [4]
    Disruptive Technology in the Energy Sector - World Bank PPP
    Footnote 12: The global average of losses during transmission and distribution is 8 to 9 percent of the electricity generated, although many developing ...
  5. [5]
    Electric power transmission and distribution losses (% of output) | Data
    Electric power transmission and distribution losses (% of output) · Electricity production from oil sources (% of total) · Electricity production from renewable ...
  6. [6]
    Electricity - Energy System - IEA
    Unabated fossil fuels currently account for over 60% of total global electricity generation. To be consistent with the Net Zero Scenario, that share needs to ...
  7. [7]
    Electric Losses - an overview | ScienceDirect Topics
    SIW losses are divided into three main contributors, the conductor, dielectric and radiation losses. Conductor losses exhibited by these structures are due to ...
  8. [8]
    Joule's 1840 manuscript on the production of heat by voltaic electricity
    Sep 30, 2020 · In 1840, James Prescott Joule submitted to the Royal Society a paper describing experimental research on the heat produced by electric currents in metallic ...
  9. [9]
    (PDF) Joule's 1840 manuscript on the production of heat by voltaic ...
    In 1840, James Prescott Joule submitted to the Royal Society a paper describing experimental research on the heat produced by electric currents in metallic ...
  10. [10]
    A Calorimetric and Electrical Method for Measuring Loss Energies of ...
    A methology which combines different calorimetric and electrical measurements to separately determine the switching and conduction energies in a half-bridge.
  11. [11]
    Efficiency Formula - Used Keysight Equipment
    Efficiency is the ratio of useful output energy or power to the total input energy or power. Engineers typically express it as a percentage to reflect how close ...
  12. [12]
    [PDF] Chapter 10, Peak Demand and Time-Differentiated Energy Savings ...
    More generally, load factor is the average demand divided by any number of peak demands, such as load factor at the time of system peak and load factor at the ...
  13. [13]
    Demand Factor, Diversity Factor, Utilization Factor, Load Factor
    Diversity Factor = Sum of Individual Max. Demand. / Max. Demand on Power Station. Diversity Factor = Installed load. / Running load. Diversity factor is usually ...
  14. [14]
    Guide to Transformer Testing Standards
    Excitation/no-load loss testing is another standard factory routine test for new factory-built transformers (IEEE C57.12.00), and it is an essential part of the ...
  15. [15]
    The US Energy Information Administration (EIA) estimates
    Nov 7, 2023 · The U.S. Energy Information Administration (EIA) estimates that annual electricity transmission and distribution (T&D) losses averaged about 5% ...Missing: Bank | Show results with:Bank
  16. [16]
    How big are power line losses? - Schneider Electric Blog
    Mar 25, 2013 · Overall power line losses range from 8-15%. Transmission lines lose 2-4%, and distribution network transformers and cables lose 4-6%.
  17. [17]
    [PDF] Assessment of Transmission and Distribution Losses in New York
    Technical losses are due to the loading and electrical characteristics of the electrical system; non-technical losses are caused by factors outside the ...
  18. [18]
    Losses in Alternator - Power Stages in Synchronous Generator
    It depends on the amount of current passing through a conductor and its resistance. It is usually known as I2R losses. it occurs in both the stator and rotor of ...
  19. [19]
    [PDF] ENERGY CONVERSION 1 - GP Sonepur
    Copper loss: These losses occur due to currents in the various windings of the machine. a. Armature copper loss = Ia. 2R a.This is the loss due to current ...
  20. [20]
    Core Loss Analysis of Permanent Magnet Linear Synchronous ...
    Sep 28, 2017 · Core loss is usually calculated using the classical Steinmetz equation, but it leads to erroneous results. ... hysteresis loss, eddy current loss, ...
  21. [21]
    [PDF] High Frequency Magnetic Core Loss Study - VTechWorks
    Feb 22, 2013 · Excess loss accounts for the difference between the measured loss and the sum of calculated hysteresis loss and the classic eddy current loss.
  22. [22]
    [PDF] Analysis of Loss Components in a Synchronous Generator under ...
    Mar 30, 2019 · A common way of defining the loss components in synchronous generators is to categorize them by their origin and mechanisms. Most of the losses ...
  23. [23]
    A Comprehensive Review of Advanced Core Materials-Based High ...
    Aug 14, 2024 · Historical development of silicon-steel magnetic material (1900-2022). offered low overall losses when it was used in a transformer core [81].
  24. [24]
    Key Factors Affecting the Cost of Generator Stators and Rotors
    Steel grade and thickness: Lower-loss grades (e.g., high-silicon or cobalt-alloyed steels) and thinner gauges (0.35 mm → 0.27 mm → 0.20 mm) cut core losses and ...Rotor Materials And... · Cooling Method And Thermal... · Typical Cost Structure And...
  25. [25]
    Electric generator - Rating, Output, Efficiency | Britannica
    Sep 26, 2025 · In large synchronous generators, these losses are generally less than 5 percent of the capacity rating. ... A typical example of use is with a ...
  26. [26]
    History | IEEE Power & Energy Magazine
    As ac emerged by the early 20th century as the preferred system and dc power began a long, gradual decline, it remained necessary to continue to supply existing ...
  27. [27]
    (PDF) Enhancing Energy Ef! ciency of Auxiliary Power in a Coal ...
    May 4, 2017 · This paper describes the auxiliary power consumption in Indian coal-! red thermal power plants. The factors in" uencing the ...Missing: exciters | Show results with:exciters
  28. [28]
    [PDF] ENERGY CONVERSION ALTERNATIVES STUDY (ECAS ...
    All other values are typical of current steam plants. These auxiliary loads consume 8.9 percent of the generator output in the plant. COSTS-GENERAL. Costs ...
  29. [29]
    (PDF) Stray losses in large synchronous machines - ResearchGate
    Aug 6, 2025 · Stray losses are caused by the magnetic leakage and fringing flux in the rotating machine, and their prediction is subject to uncertainties in the machine ...
  30. [30]
    [PDF] PREDICTION OF WINDAGE POWER LOSS IN ALTERNATORS
    The purpose of this report is to develop a method of predicting the windage loss of rotating electrical machines operating in various gases under different ...
  31. [31]
    Internal losses that reduce efficiency of a DC generator
    Jun 15, 2013 · Mechanical losses consists of viscous friction losses (~kn^2) + coulomb friction losses (varies with temp but unaffected by speed) + windage ...Missing: formula P_mech omega^ D^ 5
  32. [32]
    (PDF) Energy Savings and Emission Reductions in Industrial Boilers
    Stack losses are the heat losses from the boiler through the flue gas and ... energy is lost through flue gases in the boiler. About 10-30% of the ...
  33. [33]
    Analysis of hydraulic losses in the series from 1990 to 2022 at ... - NIH
    Apr 16, 2024 · Hydraulic losses are a crucial variable in hydroelectric ventures as they can cause significant reductions in power generation.
  34. [34]
    SCADA based intake monitoring for improving energy management ...
    Sep 11, 2022 · The study shows monitoring of intake energy parameters as well as the feeding substation, showing that SCADA can be efficiently used as an energy management ...
  35. [35]
    Condition monitoring and early fault warning of power plant auxiliary ...
    Adaptive condition monitoring of the auxiliary equipment can reduce maintenance costs and improve reliability in the thermal power units. Most existing studies ...
  36. [36]
    9.3 Resistivity and Resistance – University Physics Volume 2
    Temperature affects resistivity; for relatively small temperature changes , resistivity is ρ = ρ 0 ( 1 + α Δ T ) , where is the original resistivity and is the ...
  37. [37]
    Ac Resistance - an overview | ScienceDirect Topics
    To obtain the ac resistance, Rs(dc) has to be corrected for skin effect by multiplying it by the skin effect factor, which is typically between 1.05 and 1.25.
  38. [38]
    Skin and Proximity Effects of AC Current - Technical Articles
    Jun 5, 2015 · This results in higher resistance to AC than to DC and is known as skin effect. This is due to more flux linkage per ampere to inner filaments ...
  39. [39]
    Copper vs. Aluminum Conductors - Anixter
    For the weight and cost savings, electrical utilities use aluminum for overhead transmission lines. Aluminum also sees usage where its low-weight properties ...
  40. [40]
    [PDF] Electrical Tech Note — 212 - Michigan Agricultural Energy Council
    The resistance of copper and aluminum wire will change by about. 8% (0.08) for a 25oC change in wire temperature. R2 = R1 × [1 + α × (T2 – T1)]. Eq. 212.2 αcu.
  41. [41]
    [PDF] Electricity Transmission and Distribution - IEA-ETSAP
    Apr 12, 2014 · Losses are lower in HVDC than in HVAC over long distances: for a ±800 kV line voltage, losses are about 3% per 1,000 km for an HVDC while they ...
  42. [42]
    Understanding Skin Effect in Transmission Lines | Electrical4U
    May 3, 2024 · A special type of stranded conductor called litz wire is designed to minimize the skin effect by twisting the strands in a way that each strand ...What Causes Skin Effect in... · How to Quantify Skin Effect in...
  43. [43]
    AC Transmission Line Losses - Stanford University
    Oct 24, 2010 · Corona Loss kW/km/line, 25kW/km. Corona Loss % (1000km line at 2.25 GW), 3.3%. Table 2: Sample corona loss calculation based on Peek's formula.
  44. [44]
    [PDF] Corona on Conductors - nbn Elektronik
    A broken strand, for that matter violates the electrical field uniformity and becomes an irregular shape emitting strong corona.
  45. [45]
    [PDF] Analyzing the effect of corona losses on dynamic line ... - UPCommons
    Feb 20, 2025 · High-voltage transmission lines tend to generate corona activity. The value of corona losses is highly dependent.
  46. [46]
    [PDF] Corona Pulses And Radio Interference Levels Of High Voltage ...
    Equation (48) is valid for low field strengths and is not of use in practical situations encountered in laboratory setups and outdoor transmission lines for ...
  47. [47]
    The Case of High-Voltage Power Transmission Systems - jstor
    Peek in his early engineering research fo- cused upon the corona problem. About 1913 he shifted his interest to the effects of lightning upon high-voltage ...Missing: issues | Show results with:issues
  48. [48]
    (PDF) The Ultraviolet Detection of Corona Discharge in Power ...
    Aug 10, 2025 · In order to detect the presence of corona in power line components, a UV camera can be used. Most of the corona energy comes from a ...Missing: auditory | Show results with:auditory
  49. [49]
    Dielectric Loss Tangent - an overview | ScienceDirect Topics
    The dielectric loss tangent (tan δ) of a material denotes quantitatively dissipation of the electrical energy due to different physical processes.
  50. [50]
    Energy Efficiency - Introduction to Transformer Losses - Copper.org
    Hysteresis losses and eddy current losses contribute over 99% of the no-load losses, while stray eddy current, dielectric losses, and I 2R losses due to no-load ...Missing: I2R IEEE
  51. [51]
    Transformer Losses and Efficiency - Technical Articles - EEPower
    Jun 16, 2021 · The four main types of loss are resistive loss, eddy currents, hysteresis, and flux loss. Resistive Loss. Resistive loss, or I2R loss, or copper ...Missing: peak IEEE
  52. [52]
    Transformer DOE Efficiency Standards
    Efficiency values are at 50% of nameplate-rated load at a reference temperature of 75 deg. C. What kinds of transformers are exempt from DOE efficiency ...
  53. [53]
    Right Choice of Dry Type or Liquid-Filled Transformer
    Sep 1, 2015 · When purchased on the basis of lowest first cost, dry type transformers typically have significantly higher operating losses than the more ...
  54. [54]
    [PDF] Liquid vs Dry Type (VPI) Medium Voltage Transformers
    Dry type transformers have few restrictions, while liquid type requires liquid confinement and has restrictions based on fire point and building type.
  55. [55]
  56. [56]
    (PDF) Impact of Harmonics on Power Quality and Losses in Power ...
    Aug 7, 2025 · The simulation results show that harmonic distortion in distribution systems can increase power losses up to 20%.
  57. [57]
    Derating of transformers under non‐linear load current and non ...
    Aug 1, 2015 · Harmonic voltage and current increase the losses, leading to temperature rise which causes accelerated ageing of transformer and eventually ...2.2 Harmonic Content Indices · 3.3 Experimental Method · 3.4 Finite Elements Method
  58. [58]
    IEEE C57.12.90-2015
    Mar 11, 2016 · Resistance measurements, polarity and phase-relation tests, ratio tests, no-load loss and excitation current measurements, impedance and load ...
  59. [59]
    IEEE C57.123-2010
    Aug 3, 2010 · Information and general recommendations of instrumentation, circuitry, calibration, and measurement techniques of no-load losses.
  60. [60]
    [PDF] Premium Efficiency Motor Selection And Application Guide
    ... Efficiency Levels and Copper Rotor Motor Full-Load Efficiency ... Efficiency: NEMA minimum nominal full-load efficiency standard for premium efficiency motors.
  61. [61]
    LED Lighting | Department of Energy
    Heat: LEDs emit very little heat. In comparison, incandescent bulbs release 90% of their energy as heat and CFLs release about 80% of their energy as heat.
  62. [62]
    [PDF] LED Lighting Efficacy: Status and Directions - OSTI.GOV
    The phosphors lose 37% or 0.244 W of the initial blue optical power to a combination of internal quantum efficiency losses due to non-radiative recombination ...
  63. [63]
    From physics to fixtures to food: current and potential LED efficacy
    Mar 30, 2020 · Blue LEDs can be 93% efficient, phosphor-converted “whites” 76% efficient, and red LEDs 81% efficient. These improvements open new opportunities ...
  64. [64]
    [PDF] Contents
    Thus, switch- ing power, Psw = fEsw, increases with switching frequency f. A magnetic component of a given size, on the other hand, has a loss that decreases ...
  65. [65]
    3 Easy Tips to Reduce Your Standby Power Loads
    While it may not be readily noticed, standby power is a big issue. It accounts for 5 percent to 10 percent of residential energy use, and could cost the average ...
  66. [66]
    [PDF] Energy Conservation Standards for Electric Motors
    May 1, 2023 · ... IE4. Level, which approximately represents a 20 percent reduction of losses over. Premium/IE3. Table II-5 presents a comparison of the current ...
  67. [67]
    Electric Motors - European Commission - Energy Efficient Products
    Due to the previous motor Regulation 640/2009, the average efficiency of 0.75-375 kW AC 3-phase motors increased from 77.5% in 2009 to 82.1% in 2016. In ...
  68. [68]
    We calculated emissions due to electricity loss on the power grid
    Dec 11, 2019 · We calculated that worldwide, compensatory emissions amount to nearly a billion metric tons of carbon dioxide equivalents a year.
  69. [69]
    CO2 Emissions – Global Energy Review 2025 – Analysis - IEA
    In 2024, CO2 emissions from fuel combustion grew by around 1% or 357 Mt CO2, while emissions from industrial processes declined by 2.3% or 62 Mt CO2.
  70. [70]
    Reducing T&D Losses: Insights and Solutions for India
    Jan 29, 2025 · This translates to a significant economic burden, with estimated losses exceeding $20 (~INR2000) billion per year. These losses significantly ...
  71. [71]
    Electric Power Sector Emissions | US EPA
    Mar 31, 2025 · In 2022, the electric power sector was the second largest source of U.S. greenhouse gas emissions, accounting for 25% of the U.S. total.
  72. [72]
    [PDF] THE ECONOMICS OF DEMAND FLEXIBILITY - RMI
    In the residential sector alone, widespread implementation of demand flexibility can save 10–15% of potential grid costs, and customers can cut their electric ...Missing: impact | Show results with:impact
  73. [73]
    Net Zero by 2050 – Analysis - IEA
    May 18, 2021 · This special report is the world's first comprehensive study of how to transition to a net zero energy system by 2050 while ensuring stable and affordable ...<|separator|>
  74. [74]
    Reduction of energy losses in electrical distribution systems
    The main objective of this paper is to minimize technical and non-technical losses in power systems. There are losses in power systems that cannot be predicted ...Missing: types | Show results with:types
  75. [75]
    [PDF] Dynamic Line Rating: Innovation Landscape Brief - IRENA
    Dynamic line rating (DLR) reduces congestion on power lines, optimises asset utlisation, improves efficiency and reduces costs. This permits increased solar ...
  76. [76]
    [PDF] Type of ACSR - JCM
    standard is overachieved at present, resulting in deployment of conductors whose resistance ... in 2% reduction in resistance since resistance is inversely ...
  77. [77]
    [PDF] Amorphous Core Liquid Immersed Distribution Transformers
    The result is that no load losses (hysteresis losses and eddy current) are reduced by 50% to 70% as compared to conventional materials (Hitachi) (Ramanan).
  78. [78]
    Reducing core loss of amorphous cores for distribution transformers
    The aim of this paper is to systematically study the influence of core structure, fluctuation of composition and field annealing technique on core loss.
  79. [79]
    [PDF] Transmission Systems: HVAC vs HVDC - IEOM Society
    HVDC transmission losses are lower than AC losses in all cases and HVDC cables also have lower losses than HVAC cables of the same size (Meah and Ula). In long ...
  80. [80]
    [PDF] Dynamic Line Rating - Department of Energy
    An additional benefit of implementing DLR is increased situational awareness of the transmission system and the potential for condition-based monitoring of ...
  81. [81]
    AI-Powered Smart Grids: How They Are Revolutionizing Energy ...
    Oct 2, 2025 · 1. AI-powered smart grids can reduce energy distribution losses by up to 30%. Energy distribution losses happen when electricity is transmitted ...Ai Optimizes Energy Flow To... · 29. Ai-Based Battery Storage... · Why Ai-Driven Outage...<|separator|>
  82. [82]
    Save Money with a Variable Frequency Drive for AC Motor - Canroon
    Apr 7, 2025 · VFDs save money by reducing energy use (20-50%), lowering maintenance costs, and extending motor life, with a quick return on investment.
  83. [83]
    The Smart Grid: How AI is Powering Today's Energy Technologies
    Sensors: IoT sensors across the network can help detect risk early on, redistributing power to decrease outages and help balance loads without direct ...
  84. [84]
    [PDF] COMMISSION REGULATION (EU) No 548/•2014 - EUR-Lex
    May 22, 2014 · (8). Ecodesign requirements for the energy performance/efficiency of medium power transformers and for the energy efficiency of large power ...
  85. [85]
    Power Transformers - Energy Efficient Products
    Without regulations these losses would have been 28 MWh in 2020, but due to the Ecodesign regulations they were reduced to 23 MWh (-17%). Energy Savings. -5.7 ...
  86. [86]
    The Complete Guide to Commercial LED Lighting Retrofits
    Mar 26, 2025 · Payback period of 1.4 years after utility incentives. Enhanced safety with better visibility and instant-on capability during power fluctuations ...<|separator|>
  87. [87]
    Energy Efficiency - Energy System - IEA
    Dec 17, 2024 · Energy efficiency is called the “first fuel” in clean energy transitions, as it provides some of the quickest and most cost-effective CO 2 mitigation options.
  88. [88]
    Tripling renewable power and doubling energy efficiency by 2030
    TOTAL GLOBAL RENEWABLE POWER GENERATION CAPACITY WILL NEED TO TRIPLE BY 2030 · ENERGY EFFICIENCY IMPROVEMENTS MUST DOUBLE BY 2030 TO REMAIN ON A 1.5°C PATHWAY.