Reversing valve

A reversing valve is a specialized valve component integrated into systems, primarily used in (HVAC) applications to alternate the direction of flow between the indoor and outdoor coils. This reversal enables a single unit to function as both a heater and an air conditioner by switching the roles of the and coils, thereby transferring heat either from outdoors to indoors (heating mode) or from indoors to outdoors (cooling mode). The valve's operation relies on a sliding , often called a or , housed within a cylindrical body that connects four ports: one to the discharge, one to the line, and one each to the indoor and outdoor s. In cooling mode, the valve directs high-pressure, hot vapor from the to the outdoor , where it releases heat to the outside air before the cooled expands and absorbs heat indoors; conversely, in heating mode, it routes the hot vapor to the indoor to warm the space while the outdoor absorbs ambient heat. This functionality is typically controlled by an electromagnetic coil energized by a low-voltage (24-volt) signal from the , which creates a to shift the internal slide and redirect flow without interrupting the . The reversing valve's efficiency is crucial for overall system performance, as failures—such as sticking due to debris or malfunction—can prevent mode switching, leading to inadequate heating or cooling and increased .

Design and Components

Definition and Purpose

A reversing valve is a specialized four-way valve integral to systems, designed to reverse the direction of flow within the cycle. This component enables the system to alternate between heating and cooling modes by effectively swapping the roles of the and coils. The primary purpose of the reversing valve is to allow a single unit to function bidirectionally for both heating and cooling applications, thereby enhancing in residential and HVAC systems. By redirecting , it ensures that can be extracted from the outdoor and delivered indoors during winter, or vice versa in summer, without requiring separate dedicated units. Developed in the mid-20th century alongside advancements in technology, the reversing valve was first patented for residential HVAC use in the 1950s, with an early example appearing in US 2,513,373 granted in 1950 for a system incorporating flow reversal mechanisms. This innovation built on the growing adoption of reversible refrigeration cycles for versatile climate control. At its core, the reversing valve operates on the thermodynamic principle of the cycle's reversibility, as governed by the second law of , which permits from a lower-temperature source to a higher-temperature sink when external work is supplied. This reversibility underpins the heat pump's ability to achieve efficient heat movement in either direction, distinguishing it from unidirectional systems.

Physical Structure

The reversing valve typically features a cylindrical or tubular body constructed from or , with connections to provide in refrigerant environments. These materials ensure durability under the chemical and thermal stresses of systems. Dimensions vary by capacity but generally range from 4 to 8 inches in length and 3 to 6 inches in diameter for valves handling 1 to 15 tons, allowing integration into compact HVAC assemblies. The valve includes four ports arranged in a cross pattern: two for compressor connections (suction and discharge lines) and two for the indoor and outdoor coils, facilitating bidirectional routing. In common configurations, three ports are positioned on one side—typically the larger and ports pointing downward—while the fourth, smaller high-pressure port faces opposite, often upward for optimal alignment. Port sizes are standardized, such as 3/8-inch to 7/8-inch diameters for and lines, and 1/2-inch to 1-1/8-inch for , using brazed tubes for secure containment. External features include mounting brackets for secure installation near the , electrical terminals for the solenoid coil to enable activation, and access points for service valves to allow charging or evacuation without disassembly. Seals within the valve body utilize (PTFE) or materials to maintain integrity against leaks. These components support operational pressures up to 690 psig and temperatures from -40°F to 158°F, accommodating common s like in residential and commercial heat pumps.

Internal Mechanisms

The internal mechanism of a reversing centers on a sliding , often referred to as a , , or , which is a cylindrical component that shifts laterally within the valve body to alternate connections between the four . This , typically constructed from metal with integrated sealing surfaces, measures approximately 2-4 inches in length and features or equivalent seals to maintain separation between high- and low-pressure paths. The assembly allows the to move smoothly between two positions, ensuring precise port reconfiguration without compromising the valve's structural integrity. Supporting the slide's positioning is a pilot valve system, which incorporates small internal passages or tubes that route high-pressure to specific chambers adjacent to the . These tubes, often integrated into the pilot assembly, form a compact network of narrow channels—typically on the order of fractions of an inch in diameter—that connect the main body to the mechanism, enabling directed force application across the . The itself operates as a miniature four-way , assembled coaxially or adjacent to the main for synchronized interaction. Sealing elements are critical to the valve's performance, consisting of multiple dynamic seals such as O-rings and Teflon-coated surfaces that prevent leakage during mode transitions. These , positioned along the slide's circumference and at interfaces, are engineered to withstand repeated shifting while minimizing drops.

Operation Principles

Refrigerant Flow in Cooling Mode

In cooling mode, the reversing valve assumes its de-energized position, where the internal or is positioned to direct straight through without reversal. This configuration connects the discharge directly to the outdoor , which functions as the , while the indoor serves as the connected to the . As a result, high-pressure, superheated vapor from the enters the valve's common and exits to the outdoor , bypassing any crossover paths that would redirect indoors. The heat transfer process begins as the hot refrigerant gas arrives at the outdoor condenser coil, where it releases latent and to the ambient outdoor air, causing the refrigerant to condense into a subcooled . This then travels through the system's device—typically a thermostatic expansion valve (TXV) or tube—where its pressure drops, leading to partial and cooling. In the indoor coil, the low-pressure refrigerant absorbs heat from the indoor air, fully evaporating into superheated vapor before returning to the suction line. Proper system charging maintains of approximately 10-20°F at the condenser outlet to ensure complete and prevent flash gas, while superheat at the outlet is typically 10-20°F to protect the from liquid slugging and optimize evaporative heat absorption. This routing in the de-energized position enables efficient cooling by prioritizing rejection outdoors and indoors, supporting a (COP) of 3-4 under standard conditions, which represents a practical fraction of the theoretical Carnot efficiency approximated by \eta = \frac{T_{\text{cold}}}{T_{\text{hot}} - T_{\text{cold}}}, where temperatures are in absolute units.

Refrigerant Flow in Heating Mode

In heating mode, the reversing valve redirects the high-pressure, hot vapor from the compressor discharge port to the indoor , which functions as the . Here, the condenses, releasing to warm the indoor air. The cooled liquid then passes through the expansion device, reducing its and , before entering the outdoor , which acts as the . In the outdoor , the absorbs from the ambient outdoor air, even at low temperatures, evaporating into a low-pressure vapor that returns to the suction port to complete the . This flow reversal is accomplished by the valve's internal slide mechanism, often referred to as a , which shifts position under pressure differential to block the direct path from discharge to outdoor and instead route it to the indoor while connecting the outdoor to the suction line. The process in heating mode extracts from the outdoor —down to -22°F (-30°C) or lower for many advanced cold-climate air-source heat pumps (as of 2025)—and delivers it indoors, providing efficient heating without . As of 2025, advancements like variable-speed and low-GWP refrigerants allow many models to maintain efficiency down to -22°F (-30°C) or lower. During prolonged heating operation in humid, cold conditions, frost can accumulate on the outdoor , reducing . The reversing valve integrates with the system's defrost by temporarily shifting to reverse the flow, allowing hot to warm and melt the ice on the outdoor while the indoor fan operates to prevent cold air distribution. Once defrost is complete, the valve returns to the heating position, restoring normal flow continuity without interrupting overall heating performance. The heating capacity, or heat output Q_{\text{heat}}, is determined by the equation Q_{\text{heat}} = \dot{m} \cdot (h_{\text{discharge}} - h_{\text{suction}}) where \dot{m} is the and h_{\text{discharge}} and h_{\text{suction}} are the specific enthalpies at the compressor discharge and suction, respectively. Typical (COP) for heating ranges from 2 to 3, meaning the system delivers 2 to 3 units of per unit of electrical input, though this decreases as outdoor temperatures drop due to reduced available ambient . This mode is activated by a signal to the when heating is demanded.

Pressure Differential Role

The differential in a reversing valve serves as the primary driving force for shifting the internal , enabling the reversal of flow without relying on mechanical actuators. High-pressure gas, typically ranging from 200 to 400 depending on the and operating conditions, is routed through a to one side of the , while low-pressure gas, usually 50 to 150 , is directed to the opposite side. This imbalance generates a on the , calculated as F = (P_{\text{high}} - P_{\text{low}}) \times A_{\text{piston}}, where A_{\text{piston}} is the effective area of the exposed to the difference. The resulting force displaces the rapidly, typically within less than one second, to the desired position. Once shifted, the valve maintains its position through balanced pressures that equalize across the internal components, such as poppets or nose valves in slide-type designs, preventing unintended drift or oscillation. In the , the high- and low-pressure sides are isolated such that the net force approaches zero, with minimal leakage ensuring stability under normal system loads. This pressure equalization is critical for operational reliability, as it allows the valve to hold against the continuous flow of without additional energy input. The governing gas routing in the pilot system leverage principles of -driven flow, where the velocity of through narrow pilot tubes can be approximated by v = \sqrt{\frac{2 \Delta P}{\rho}}, with \Delta P as the difference and \rho as the gas density, facilitating quick buildup for actuation. However, the mechanism's effectiveness is limited by sensitivity to system imbalances, often arising from faults such as reduced capacity or oil loss, which can result in incomplete shifts or failure to overcome and leakage. A minimum differential of 10-20 is typically required for reliable operation, depending on the model, and deviations below this threshold may prevent proper response.

Control and Activation

Solenoid Operation

The component of a reversing valve features an , typically rated at 24 V , encasing a ferromagnetic connected to a mechanism. This structure allows the to open or close a small pilot port, directing high-pressure to imbalance forces on the main slide. The coil is designed for integration into HVAC control systems, with wiring often color-coded (e.g., blue for common and orange for in cooling mode). Upon receiving an electrical signal, the is energized, producing a that rapidly attracts the , typically within 0.1 to 0.5 seconds, to shift the pilot port position and initiate pressure redirection. This quick mechanical response ensures efficient mode switching without excessive delay in system operation. The activation relies on the 's movement to route discharge gas through or around the pilot circuit, creating the necessary to reposition the valve's internal . Power specifications for the solenoid coil generally include a draw of 10-20 during operation, with (up to 5 times the holding current in designs) occurring briefly upon energization to overcome initial inertia, followed by a lower holding current to maintain and reduce overall use. This design optimizes efficiency in residential and commercial applications. Common failure modes involve burnout, often resulting from voltage spikes or transients that exceed the coil's rating, leading to overheating and open circuits. Such issues are mitigated through the inclusion of suppression capacitors in the control circuitry to absorb inductive kickback and stabilize voltage fluctuations.

Thermostat and Electrical Control

The serves as the primary interface for controlling the reversing valve in systems, sending electrical signals to dictate mode selection between heating and cooling. Typically, a 24 VAC low-voltage system powers the controls, with the thermostat wiring including dedicated terminals for activation and valve reversal. The Y terminal (yellow wire) signals the contactor to engage for either mode, while the O or B terminal specifically manages the reversing valve to redirect flow. Control logic varies by manufacturer configuration, primarily distinguished by the O/B terminal designation. In O-type systems, prevalent in brands like , , and Goodman, the O wire (orange) is energized by the during a cooling call, activating the to shift the valve into cooling position; the wire de-energizes for heating, allowing the valve to default to heating mode via . In contrast, B-type systems, common in , American Standard, and Rheem units, energize the B wire (blue or black) during heating calls to position the valve for heat mode, de-energizing it for cooling. This binary energization ensures seamless mode switching without manual intervention, with the coordinating the signals based on setpoints and system demands. Safety interlocks integrate into the electrical to protect the reversing valve and overall from operational faults. Low- and high-pressure switches refrigerant levels, interrupting 24 VAC power to the and if pressures fall outside safe ranges (e.g., below 20-30 for low-pressure cutout), preventing valve sticking or damage during low charge or blockages. Low-ambient cutouts, often employing outdoor sensors or auxiliary pressure switches in cooling kits, disable energization for cooling mode when outdoor temperatures drop below approximately 55°F (13°C), avoiding low-pressure conditions and freezing in cold weather. These interlocks typically auto-reset once conditions normalize, ensuring reliable protection without constant manual oversight. Advancements in the introduced smart thermostats with capabilities, revolutionizing reversing valve control by enabling remote mode selection and automation. Devices like the Nest Learning Thermostat (launched 2011) and ecobee models integrate with heat pumps via standard O/B wiring, allowing users to switch modes, adjust setpoints, and monitor valve status through mobile apps, often incorporating geofencing and learning algorithms for optimized energy use. These -enabled controls, compatible with most 24 VAC systems, expanded accessibility while maintaining compatibility with traditional solenoid actuation for mode reversal.

Applications and Variations

Primary Use in Heat Pumps

In split-system heat pumps, the reversing valve is strategically positioned between the and the indoor and outdoor coils, enabling it to redirect hot, high-pressure as needed for heating or cooling operations. This placement ensures seamless integration within the , where it commonly handles environmentally friendlier options like or the increasingly adopted R-32, both of which offer improved thermodynamic performance over older refrigerants. The reversing valve's core function allows air-source heat pumps to deliver year-round heating and cooling from a single unit, eliminating the need for separate furnaces or air conditioners and simplifying home HVAC setups. By facilitating this dual-mode capability, it contributes to substantial gains, with heat pumps using the valve achieving up to 50% lower consumption compared to traditional electric heating systems. Air-source heat pumps, which rely on the reversing valve for refrigerant flow reversal, hold the dominant position in the market, accounting for over 85% of installations due to their affordability, straightforward , and reliance on ambient air rather than specialized infrastructure. Ground-source (geothermal) heat pumps adapt the same valve technology but pair it with buried loops for enhanced efficiency in stable subsurface temperatures, though they represent a smaller segment given higher upfront costs. By 2025, cumulative U.S. installations have surpassed 20 million units, propelled by federal efficiency mandates like SEER2 standards that require minimum ratings of 14.3 for split-system models to promote broader adoption.

Types and Design Variations

The standard 4-way pilot-operated reversing valve dominates designs for residential systems, utilizing a -activated to harness pressure differentials for shifting the main internal slide and reversing flow between heating and cooling modes. This configuration features four ports connecting the discharge, suction, and indoor/outdoor coils, with the pilot mechanism ensuring efficient operation under typical residential pressures up to 650 psig. Its widespread adoption stems from reliable performance in unitary and systems, where the coil energizes to direct high-pressure gas through the pilot, enabling smooth transitions without excessive power draw. In contrast, the 4-way direct-acting reversing valve employs electromagnetic force from the to directly move the , bypassing a separate pilot and relying on linkage for . This simpler suits smaller HVAC systems, such as units or compact packaged systems, but is less prevalent due to limitations in handling high capacities and larger pipe sizes, which demand greater power and increase overall dimensions. Bi-flow and multi-port variants extend functionality for advanced multi-zone applications, particularly in (VRF) systems introduced commercially in the 2000s. These designs incorporate additional ports or integrated branch selectors—often 4- to 8-port configurations—that allow simultaneous heating and cooling across multiple indoor units by directing to specific zones via heat recovery mechanisms, enhancing system efficiency in large buildings without dedicated reversing valves per unit. Post-2020 regulatory shifts, including F-Gas amendments and U.S. EPA Act provisions mandating GWPs below 700 for new equipment by 2025, have driven eco-friendly adaptations in reversing valve designs. Manufacturers have introduced low-GWP-compatible seals and high-temperature-resistant slides, such as those enduring 150–160°C for refrigerants like R32 and , ensuring material integrity under elevated pressures up to 49 bar while maintaining leak-proof performance in modern heat pumps.

Maintenance and Failure Modes

Common Faults and Diagnosis

Common faults in reversing valves primarily involve mechanical sticking, internal leakage, and solenoid malfunctions, each leading to inefficient operation or to switch between heating and cooling modes in systems. A stuck valve often prevents the system from changing modes, such as delivering cooling air during a heating , due to , , or insufficient pressure differential to shift the mechanism. of a stuck valve involves checking for to switch modes (e.g., the system remains in cooling during a heating ), absence of pressure change or audible shift when the is energized, and performing a test using a strong placed on the body to verify if the internal moves. Internal leakage in the reversing valve allows to bypass the intended path, resulting in reduced efficiency, such as inadequate heating or from mixed flow directions. This fault manifests as a significant drop across the body exceeding 5°F (normal operational variance is 3-5°F), indicating incomplete of flows, or by noting anomalous amp draw lower than the rating due to reduced load from bypassing; observation of bleeding or migration between the hot and cold lines can also confirm leakage. probes attached to the ports can further verify leakage by detecting a differential greater than 5°F across the , beyond normal operational variance. Solenoid failure, a frequent electrical , prevents the from activating the pressure shift, often evidenced by the absence of an audible click when the is energized via the thermostat's O/B . Testing involves using a to confirm 24V at the terminals during mode change and measuring resistance, typically between 50 and 80 ohms for a functional 24V ; values outside this range or open circuits indicate a faulty . In modern systems with electronic control modules (), diagnostic tools like manifold gauge sets and probes are essential for and temperature assessments, while ECM boards may display specific codes related to faults; for example, in systems like ClimateMaster, codes such as 19 (low differential) or 99 (excessive transition mode operation) can indicate a stuck reversing valve. If faults persist beyond , is recommended to restore system performance.

Repair and Replacement

Reversing valves are rarely field-repairable due to their precision internal components and the risks associated with handling, with most faults necessitating full replacement rather than partial repairs like solenoid substitution or brazing. In cases where the coil is the isolated failure point, technicians may replace it separately, but this approach is uncommon and still requires evacuation to prevent . The replacement process begins with safety measures, including turning off the at the and disconnecting power at the to avoid electrical hazards. Next, technicians recover the using a certified in compliance with EPA regulations, followed by accessing the by removing outdoor unit panels. Electrical are labeled and disconnected, then the old is removed by unsoldering or unbolting lines with a or wrenches, taking care to minimize leaks. The new , such as an OEM-compatible model, is installed by or securing lines with fittings and seals, after which wires are reconnected per manufacturer specifications. The system is then evacuated using a to remove air and , achieving a vacuum level below 500 microns as measured by a micron , before recharging with the precise amount of specified for the unit. Finally, power is restored, and the system is tested in both heating and cooling modes to confirm proper operation. Essential tools for replacement include a refrigerant recovery machine, brazing torch, , micron gauge, adjustable wrenches, tube cutter, flaring tool, , and , all handled by EPA-certified HVAC professionals to ensure compliance and safety. Protective gear such as gloves, safety glasses, and work boots is mandatory during the to guard against exposure and burns. Replacement costs typically range from $400 to $800 for parts and labor, though this can reach $1,500 depending on the model, location, and additional needs. With proper maintenance, a reversing valve generally lasts 10 to 15 years, after which efficiency declines may warrant evaluation of the entire system.

References

  1. [1]
    Heat Pump Reversing Valve: Everything You Need to Know - Trane®
    When the thermostat sends a signal that it's time to heat, the reversing valve reverses the flow of refrigerant. This makes the coil inside your home become the ...Missing: definition | Show results with:definition
  2. [2]
    Heat Pump Reversing Valves: Understanding the Basics - HVAC.com
    Jan 19, 2024 · When the heat pump is in heating mode, the reversing valve directs the flow of refrigerant through the outdoor coil, absorbing heat from the ...Missing: definition | Show results with:definition
  3. [3]
  4. [4]
    Understanding the Heat Pump Reversing Valve - Lennox
    Oct 14, 2025 · Role in Heat Pump Operation. In cooling mode, the valve routes hot refrigerant to the outdoor coil, allowing heat to be released outside. In ...
  5. [5]
    Heat Pumps 101: The Importance of the Reversing Valve
    Nov 21, 2022 · The reversing valve is the one little component that allows a heat pump to function for both heating and cooling.Missing: definition | Show results with:definition
  6. [6]
    US2513373A - Heat pump system - Google Patents
    The drop in pressure maintained by the expansion valve It causes the liquifled refrigerant passing through the heat exchange coils 2| to evaporate thereby ...Missing: history | Show results with:history
  7. [7]
    The History of Heat Pumps: Technology Advances to Meet the Cold ...
    Apr 11, 2024 · Early History of Heat Pumps​​ Later development of the reversing valve allowed systems to change the flow of refrigerant and enabled heating ...
  8. [8]
    Applications of Thermodynamics: Heat Pumps and Refrigerators
    An artifact of the second law of thermodynamics is the ability to heat an interior space using a heat pump. Heat pumps compress cold ambient air and, in so ...
  9. [9]
    14.3: The Second Law of Thermodynamics - Physics LibreTexts
    Nov 5, 2020 · The second law of thermodynamics states that heat transfer occurs spontaneously only from higher to lower temperature bodies.
  10. [10]
    Reversing Valves - Wilspec
    Wilspec reversing valves are for smooth switching in heat pumps, using a solenoid to open/close ports, and are the heart of heat pumps.
  11. [11]
  12. [12]
    How a Reversing Valve on Heat Pump Works! | Vernon AC
    The reversing valve consists of several essential parts: Valve Body: A cylindrical metal structure with four ports. The top port receives high-pressure ...Missing: materials | Show results with:materials
  13. [13]
    Components for heat pumps – part 5: four-way reversing valves
    Jul 1, 2012 · A four-way reversing valve has four pipe connections, three of them on one side and the fourth on the opposite side, whereby the three copper ...Missing: physical materials ports
  14. [14]
    [PDF] HEAT PUMP REVERSING VALVE APPLICATION
    The four (4) valve connection tubes are brazed to the system in the vertical position illustrated with the body of the valve on a horizontal plane which may be ...
  15. [15]
    Reversing Valves - HVAC & Refrigeration - Robertshaw
    Metal slide with Teflon seal assures minimal pressure drop for better functionality ... Temperature Range: -40°F to 158°F (40°C to 70°C); Tube ...Missing: rating elastomers
  16. [16]
    How a Heat Pump Reversing Valve Works - HVAC School
    Feb 12, 2021 · Reversing valves reverse the refrigerant flow to send the hot, compressed vapor to the indoor coil instead of the outdoor coil.Missing: definition | Show results with:definition
  17. [17]
    [PDF] REVERSING VALVES V SERIES - Robertshaw
    • Metal slide with Teflon seal assures minimal pressure drop for better ... Note: Solenoid coils are not included with the reversing valve and are sold ...
  18. [18]
    Reversing Valve - The Engineering Mindset
    May 28, 2019 · A reversing valve in heat pumps allows refrigerant to reverse flow for heating and cooling. It uses a slider to direct refrigerant flow.Missing: structure materials
  19. [19]
    Heat Pump Reversing Valve Troubleshooting Tips (Switchover Valve)
    Mar 12, 2021 · ... inside the reversing valve. Small capillary-type tubes house the pressurized refrigerant and push the slide laterally to isolate two of the ...Missing: mechanism | Show results with:mechanism
  20. [20]
  21. [21]
  22. [22]
    Heat Pump System Subcooling Requirements - Expert Q&A
    Hello, the subcooling of condensed liquid from the condenser coils can range from 10°F to 30°F or more, depending on the volume and temperature of the air ...
  23. [23]
    [PDF] Evaluation Of Subcooling Control In Residential Heat Pumps ...
    The High-SEER baselines was charged until the subcooling measured around 5 K, while the evaporator superheat should be between 3-5 K, while the Low-SEER ...
  24. [24]
    Heat Pump COP and SCOP: What They Mean & Why They Matter
    Rating 5.0 (23) Nov 19, 2024 · A good heat pump COP is generally between 3.0 and 5.0, and a good SCOP is typically above 3.5, indicating that the system provides efficient ...
  25. [25]
    6.4 Carnot cycles – Introduction to Engineering Thermodynamics
    Because the Carnot cycle always has the maximum COP compared to any real cycle operating between the same heat source and heat sink, the COP of a real heat pump ...
  26. [26]
    9 ways to get the most out of your heat pump all winter
    A heat pump measures temperature differently than your old heating system. ... Today's cold-climate heat pumps can handle temperatures as low as -15°F and below.<|separator|>
  27. [27]
    Defrost Cycle of a Heat Pump - InterNACHI®
    The defrost cycle removes frost by reversing the heat pump to temporarily warm the outdoor coil, stopping the outdoor fan, until the coil reaches 57°F.Missing: integration | Show results with:integration
  28. [28]
    FSEC-PF-413-04
    The practical efficiency that air-source heat pumps achieve is a coefficient of performance (COP) of 2.0-3.0. To rate heat pumps in a standard fashion, a ...
  29. [29]
    [PDF] Empirical Study of the Effect of Thermal Loading on the Heating ...
    Jan 18, 2023 · The average COP correlated with outdoor temperature, but the dependence of the COP on the level of thermal loading was not investigated. In a ...Missing: cooling | Show results with:cooling
  30. [30]
    Reversing Valves, Refrigerant Levels, and Heat Strip Testing Study ...
    Sep 23, 2025 · To change refrigerant flow, the reversing valve requires: 1) 24V at the solenoid coil, and 2) a pressure differential of at least 50 PSI between ...
  31. [31]
    Solenoid Valve Response Time Explained - Tameson.com
    Nov 21, 2024 · Not all solenoid valves have the same response time. In fact, it can vary from tens of milliseconds to several seconds. Small direct acting ...
  32. [32]
    [PDF] Sporlan Solenoid Valves - Borgen Systems
    The volt-ampere. (VA) rating is equally important. To determine the. VA requirement for a specific solenoid valve, refer to the chart below. It should be ...
  33. [33]
    Causes of Solenoid Valve Coil Burnout | Tameson.com
    Jul 25, 2024 · AC solenoid valves are particularly susceptible to burnout due to high inrush current, which can be up to five times higher than the normal ...View Our Online Selection Of... · Voltage Issues · Electrical Transients
  34. [34]
    Inrush Current and AC Solenoid Coils - Beta Valve
    Dec 1, 2016 · The failure of solenoid coils is far more common in coils used on alternating current (AC). This is primarily due to the phenomenon known as “inrush” current.
  35. [35]
    Heat Pump Thermostat Wiring Diagram (2025) - Today's Homeowner
    Apr 9, 2025 · O/B (Orange or Blue): Manages the reversing valve, which switches between heating and cooling. Some systems energize the reversing valve in ...
  36. [36]
  37. [37]
    Heat Pump Reversing Valves and Their Control Designation
    Jan 14, 2022 · Understanding these manufacturer differences is essential when troubleshooting heat pump reversing valve issues or setting up new thermostats.
  38. [38]
    Thermostat Wire Color Codes You Need to Know - Aire Serv
    May 23, 2025 · When the thermostat calls for heat, this wire signals the reversing valve to move to the heating position. Where can I find a thermostat ...
  39. [39]
    Air Conditioning & Heat Pump System Switches - InspectApedia
    This article explains where to find and how to use the switches and controls for air conditioning and heat pump systems.
  40. [40]
    Low Ambient Pressure Switch Kit (R410A) - Sigler
    The KSALA0301410 Low Ambient Pressure Switch Kit is designed for use in all single speed air conditioners or heat pumps using R-410A refrigerant.Missing: reversing valve interlocks cutout
  41. [41]
    [PDF] Smart Thermostats plus Heat Pumps - ACEEE
    This paper combines a literature review of the smart thermostat+heat pump relationship and interviews with stakeholders to outline trends, issues, barriers, and ...
  42. [42]
    Heat Pump Components: The Reversing Valve | Kool Breeze
    Mar 18, 2015 · When the heat pump is in cooling mode, the position of the reversing valve sends the hot refrigerant from the compressor to the outdoor coils, ...
  43. [43]
    2025 Low GWP Compliant Refrigerants - LennoxPros
    We've updated our entire product lineup to use 2025 Compliant Refrigerants R-454B for whole-home systems and R-32 for ductless mini-split systems.
  44. [44]
    Air-Source Heat Pumps | Department of Energy
    A reversing valve changes the direction of refrigerant flow for cooling and for the winter defrost cycle. In warmer months, heat is extracted from the home and ...
  45. [45]
    Electric Resistance Heating | Department of Energy
    If electricity is the only choice, heat pumps are preferable in most climates, as they easily cut electricity use by 50% when compared with electric resistance ...
  46. [46]
    Heat Pump Market Size And Share | Industry Report, 2030
    The air-source technology segment dominated the market in 2024 by accounting for a share of over 84.7%. Air source heat pump works through wet central heating ...Market Size & Forecast · Market Concentration &... · Regional Insights
  47. [47]
  48. [48]
    Residential Heat Pumps - AHRI
    The national split-system heat pump minimum efficiency standard has changed from 14.0 SEER to 14.3 SEER2 (15 SEER) and 8.2 HSPF to 7.5 HSPF2 (8.8 HSPF).
  49. [49]
    Sanhua Reversing Valve Range Reaches New Heights
    Sanhua International is expanding the range of its world leading four-way reversing valves with the introduction of two new models to the North America market.
  50. [50]
    Brief Understanding of Solenoid Valve
    Sep 29, 2022 · The direct-acting solenoid valve directly uses the electromagnetic force to push the valve core reversing, while the pilot-operated reversing ...Missing: types | Show results with:types<|separator|>
  51. [51]
    [PDF] VRV Reference Guide - Daikin
    The Flex Branch Selector boxes (available as a 4, 6 and 8-port) has a number of features that set it apart from the other single & multi-port boxes ...<|control11|><|separator|>
  52. [52]
    The Role of the Four-Way Valve in Variable Refrigerant Flow (VRF ...
    Rating 5.0 (6,008) In VRF systems, the four-way valve—also called a reversing valve—is an essential part. Its primary function is to switch the system's refrigerant flow direction ...
  53. [53]
    Low GWP Refrigerants Trend & Sanhua Solutions
    Jan 31, 2024 · Sanhua has developed high-temperature resistant slides for 4-way reversing valves,as well as dedicated solutions of other products to be used as ...Missing: post- | Show results with:post-
  54. [54]
  55. [55]
    Why Is My Heat Pump Reversing Valve Stuck? - HVAC.com
    Dec 17, 2024 · Your reversing valve can become stuck in heat mode due to a bad solenoid, electrical issues, or a refrigerant leak.
  56. [56]
    Heat Pump Reversing Valves Explained: How They Work in HVAC ...
    Jun 17, 2025 · The Reversing Valve utilizes differential pressure to get the “Valve” to move. This is achieved through utilizing High Pressure Discharge gas to flow through ...System Layout · Valve Stuck In One Position · Solenoid Coil FailureMissing: definition | Show results with:definition<|control11|><|separator|>
  57. [57]
    [PDF] Service Tool Fault Codes - ClimateMaster
    Stuck Reversing Valve. Faulty Compressor. 20. ECM Configuration. Incorrect Unit ... Heat Sink Thermistor Error. Damaged Inverter board. 67. Current Sensor ...
  58. [58]
    Heat Pump Reversing Valve: How It Works & Troubleshooting
    Jul 22, 2025 · Inside this valve is a sliding mechanism that moves back and forth to change the refrigerant's path.Missing: ring | Show results with:ring
  59. [59]
    How Do I Fix a Faulty Heat Pump Reversing Valve? - Desert West
    Sep 10, 2025 · One of the most telling signs of a failing reversing valve is that your heat pump can no longer switch between heating and cooling. For ...Missing: diagnosis | Show results with:diagnosis
  60. [60]
    Replacing a Heat Pump Reversing Valve Safely and Effectively
    ### Step-by-Step Procedure for Replacing a Reversing Valve
  61. [61]
    A Guide to Heat Pump Repair Costs - HVAC.com
    Nov 1, 2024 · Heat pump repair costs can vary depending on the type of repair. For example, replacing the reversing valve typically costs $400 to $700.