Gaseous fire suppression

Gaseous fire suppression, also known as clean agent fire suppression, refers to the use of electrically nonconducting gases or gas mixtures that extinguish fires by interrupting the of , reducing oxygen levels, or cooling without leaving residue upon . These systems are designed for total flooding of enclosed spaces or local application to specific hazards, making them ideal for protecting sensitive equipment, data centers, museums, telecommunications facilities, and other areas where water-based suppression could cause damage. The development of gaseous fire suppression traces back to the early , when (CO₂) emerged as the primary clean, dry gaseous agent from 1910 to the late , primarily reducing oxygen and cooling to suppress fires but posing risks to human safety due to asphyxiation hazards. In the late , (bromotrifluoromethane) became a popular alternative, chemically inhibiting combustion while being safer for occupied spaces, though its production was phased out by 1994 under the and U.S. Clean Air Act Amendments due to concerns. Modern systems (as of 2025), governed by standards such as NFPA 2001 for clean agent systems and NFPA 12 for CO₂, now rely on environmentally friendlier replacements including inert gases like , , or IG-541 (Inergen), and low-GWP halocarbon agents such as FK-5-1-12 (Novec 1230); high-GWP options like HFC-227ea (FM-200) and HFC-23 (FE-13) are being phased out under regulations like the AIM Act. Inert gas agents work by lowering oxygen concentrations to below 15%; some blends, such as IG-541 (Inergen), also include to stimulate breathing for safe evacuation, whereas agents primarily disrupt the fire's chemical with minimal environmental impact, such as zero . These agents are stored in pressurized cylinders and discharged rapidly—often within 10 seconds—to achieve design concentrations held for at least 10 minutes to prevent re-ignition. Advantages include no post-discharge cleanup, non-corrosiveness, and suitability for and irreplaceable assets, though systems require integrity testing to ensure containment and may involve higher upfront costs compared to traditional sprinklers. Ongoing research emphasizes low-global-warming-potential agents to align with goals, with NFPA 2001 updated periodically (latest 2025 edition) to incorporate safety factors, testing protocols for Class A, B, and C fires, and provisions for transitioning to low-GWP agents amid AIM Act phase-downs and restrictions.

Fundamentals

Definition and Principles

Gaseous fire suppression, also known as clean agent fire suppression, refers to the use of electrically nonconductive gases—either inert or chemically active—that are discharged into an enclosed space to extinguish fires by interfering with the combustion process, without leaving any residue upon evaporation. Unlike traditional water or foam-based systems, these gaseous agents do not conduct electricity or cause corrosion, making them suitable for protecting sensitive environments where residue could lead to secondary damage. The systems are designed for total flooding applications, where the agent fills the protected volume to a predetermined concentration that disrupts fire sustenance, typically through oxygen reduction or chemical inhibition. The fundamental principles of gaseous fire suppression rely on rapid agent delivery to achieve and maintain the required concentration in a , ensuring extinguishment while prioritizing occupant safety. In total flooding systems, the agent must such that at least 95% is released within 10 seconds for halocarbon agents or 60 seconds for inert gases, allowing quick suppression before significant growth. This rapid is followed by a hold time—minimum of 10 minutes—during which the concentration remains above the extinguishing threshold to prevent re-ignition, often facilitated by pre-discharge alarms and evacuation delays of 30 seconds to several minutes. The process operates on the premise of a sealed that retains the agent, enabling safe egress for occupants prior to full immersion in the suppressed space. Key advantages of gaseous systems over conventional methods include minimal post-suppression cleanup and no risk of to , data centers, or archival materials, rendering them ideal for both occupied and unoccupied high-value areas. These systems enable business continuity by avoiding the associated with residue removal or equipment drying. However, effective deployment requires well-sealed enclosures to prevent dilution, as leakage can compromise concentration levels; they are thus unsuitable for outdoor or open-area fires where cannot be assured. Compliance with standards like NFPA 2001 ensures these prerequisites are met through integrity testing.

Fire Suppression Mechanisms

The fire tetrahedron represents the four essential elements required for sustained combustion: fuel, heat, oxygen, and the chemical chain reaction. Gaseous fire suppression agents primarily target either the oxygen or the chemical chain reaction to extinguish flames, without directly removing fuel or heat. In the inerting mechanism, non-reactive gases such as nitrogen or argon dilute the oxygen concentration in the protected space to below the limiting oxygen index (LOI), typically under 15% by volume, which prevents combustion from continuing. The LOI is defined as the minimum oxygen level in a nitrogen-oxygen mixture that supports flaming combustion for a given fuel. This physical dilution lowers the oxygen available for the oxidation reaction, effectively starving the fire without altering the fuel or heat elements. Chemical suppression involves halogenated or that decompose in the flame zone to release atoms, such as or , which scavenge highly reactive free radicals (e.g., H• and OH•) essential for the propagation of the . These radicals are interrupted through catalytic cycles, reducing the overall and halting flame propagation. A representative example is the reaction involving (HBr), a product: \mathrm{HBr + OH \cdot \rightarrow H_2O + Br \cdot} Gaseous agents are deployed via total flooding, where the suppressant is uniformly discharged into an enclosed area to achieve the required concentration rapidly, or via streaming, which directs the agent from portable extinguishers onto specific sources for localized application.

Types of Agents

Inert Gas Agents

Inert gas agents are a class of electrically non-conductive, residue-free fire suppressants used in total flooding systems to extinguish fires without chemical reactions. These agents, composed primarily of naturally occurring atmospheric gases, include IG-541 (also known as Inergen), a blend of 52% , 40% , and 8% ; IG-55 (Argonite), a 50% and 50% mixture; IG-01, consisting of 100% ; and IG-100, pure . They are stored as compressed gases in seamless cylinders, typically at pressures of 200 to 300 bar, allowing for efficient delivery without liquefaction. The primary suppression mechanism of inert gas agents involves diluting the ambient air to reduce oxygen concentration below the flammability , typically to 12-15%, which requires discharging the agent to achieve 40-50% concentration by volume in the protected . This oxygen displacement smothers the while maintaining a breathable , as the resulting oxygen level remains above 10% for human safety in most applications. In IG-541, the 8% component plays a key role by increasing to about 3% post-discharge, which stimulates and enhances oxygen uptake in occupants. Unlike chemical agents that interrupt chemically for faster extinguishment, inert gases rely solely on physical dilution, resulting in a slightly slower but residue-free suppression process. These agents exhibit favorable environmental properties, including zero (ODP) and negligible (GWP <1), as they are naturally occurring and do not persist in the atmosphere. They are non-conductive, making them suitable for protecting electrical and electronic equipment without risk of short circuits. During discharge, systems release the agent through nozzles in total flooding configurations, achieving full concentration within 60 seconds as per standards like NFPA 2001, with cylinder pressures regulated to mitigate high-velocity noise and impact (initial storage up to 300 bar, but nozzle delivery often controlled to around 40-60 bar). No decomposition products are generated, ensuring clean post-discharge cleanup and no corrosion to protected assets.

Chemical Gas Agents

Chemical gas agents are electrically non-conductive, volatile compounds used in fire suppression systems to chemically interrupt the combustion process without leaving residue upon evaporation. These agents, often classified as "clean" suppressants, include modern and , as well as legacy . Examples encompass , chemically known as (CF₃CHFCF₃), , also designated as (CF₃CF₂C(O)CF(CF₃)₂) (note that as of 2025, 3M has discontinued production of Novec 1230, though existing stocks and potential alternatives from other manufacturers may still be utilized), (HFC-23, CHF₃, suitable for low-temperature applications due to its boiling point of -82°C), and historical such as (CF₃Br). These agents are typically stored as liquids under pressure in cylinders to facilitate rapid vaporization during discharge. The primary mechanism of these agents involves thermal decomposition in the flame zone, releasing reactive radicals—such as halogen atoms from halons—that scavenge chain-carrying species in the combustion reaction, thereby inhibiting fire propagation. For instance, in , bromine radicals (Br•) react with hydrogen radicals (H•) to form hydrogen bromide (HBr), disrupting the radical chain: \mathrm{Br^\bullet + H^\bullet \to HBr} This process effectively suppresses fires at low concentrations of 5-10% by volume, with negligible reduction in ambient oxygen levels, allowing safe use in occupied spaces. Modern chemical agents like and operate through a blend of chemical inhibition and heat absorption, decomposing to release fluorinated radicals that similarly interrupt flame chemistry. Key properties of these agents include their clean evaporation, leaving no solid or liquid residue to damage sensitive equipment, and favorable physical characteristics for deployment. FM-200 exhibits a global warming potential (GWP) of 3220 over 100 years, reflecting its hydrofluorocarbon structure, while Novec 1230 has a GWP of less than 1 and a boiling point of 49°C, enabling safer storage and handling as a stable liquid at ambient temperatures. These attributes contribute to their efficacy in total flooding systems, though inert gas agents generally exhibit longer discharge times compared to chemical agents, as chemical agents stored as liquids vaporize rapidly upon discharge. The use of halons has been phased out globally following the 1987 Montreal Protocol, which targeted their production due to high ozone depletion potential (ODP). Subsequently, HFCs like FM-200 faced reduction mandates under the 2016 Kigali Amendment to the Montreal Protocol, aimed at curbing their potent greenhouse gas effects through an 80-85% phasedown in production and consumption by mid-century. This has driven the transition to low-GWP alternatives such as Novec 1230, which maintains effective suppression while minimizing environmental impact.

System Design and Installation

Core Components

Gaseous fire suppression systems rely on a suite of integrated hardware components to detect fires, initiate responses, store suppression agents, and deliver them effectively to protected areas. These components ensure rapid activation while incorporating safeguards like pre-discharge delays to allow for evacuation or abort actions. The design emphasizes reliability, with elements compliant to standards such as for clean agent systems and for fire alarm and detection integration. Detection systems form the first line of response, utilizing smoke, heat, or flame detectors to identify fire hazards early. Common configurations include point-type smoke detectors, linear heat detectors, or advanced aspirating systems like , which draw air samples through a network of pipes to a central analyzer for heightened sensitivity in high-value environments such as data centers. These detectors connect to a suppression releasing panel, enabling automatic activation upon threshold breach or manual initiation via pull stations, thereby triggering alarms and system sequences. Agent storage typically involves high-pressure cylinders made of steel or aluminum to contain inert gases or liquefied chemical agents under pressure. For chemical agents like or , cylinders are superpressurized with nitrogen (often at 360 psi) to facilitate agent expulsion as a gas upon release, while inert gas agents like store the mixture directly in gaseous form. Each cylinder features integrated valves—such as solenoid or pneumatic types—that remain sealed until activated, connected via manifolds for modular scalability in larger installations. Pipe networks, constructed from corrosion-resistant materials like Schedule 40 steel or copper, branch from the storage bank to ensure even agent distribution throughout the protected enclosure. Discharge nozzles at the end of the piping network are engineered for uniform gas dispersion, often featuring multiple orifices to create a turbulent flow that mixes the agent with ambient air effectively in total flooding applications. Nozzle placement follows calculated patterns to achieve design concentrations without dead zones, with materials selected for compatibility with specific agents to prevent degradation. Systems incorporate abort switches and pre-discharge warnings, providing 30-60 seconds of audible and visual alerts before agent release, allowing personnel to evacuate or halt deployment if the alarm is false; this delay is mandated to prioritize occupant safety in normally occupied spaces. Control panels serve as the central hub, monitoring system integrity, agent pressure, and detector status while integrating with building management systems for coordinated responses like HVAC shutdown. Compliant with NFPA 72, these panels—such as addressable releasing units—support zoning for multiple areas, fault detection for wiring or low pressure, and event logging for up to thousands of incidents. They include primary power supplies with backup batteries (typically 24-hour standby plus 5-minute alarm capacity) to ensure operation during outages, facilitating both automatic and manual control modes.

Design and Testing Procedures

The design of gaseous fire suppression systems begins with sizing calculations to determine the required agent quantity, based on the hazard type, net room volume, and presence of unclosable openings. The net volume is calculated by subtracting fixed obstructions like machinery from the total enclosed space, ensuring the agent effectively reaches all protected areas. Minimum design concentrations are agent- and hazard-specific; for instance, (commonly known as ) requires 7% by volume for Class A surface fires involving ordinary combustibles. A safety margin of at least 20% above the minimum extinguishing concentration is typically applied to account for variables like temperature and uneven distribution, resulting in a design concentration no less than 1.2 times the tested extinguishing value. Flooding time is a critical design parameter, requiring halocarbon clean agents to achieve 95% of the design concentration within 10 seconds of discharge initiation, as stipulated in , to rapidly suppress incipient fires without allowing significant growth. Inert gas agents have extended allowances, up to 60 seconds for Class B hazards, but all systems must extinguish fires within 30 seconds post-discharge. Design incorporates measures like automatic ventilation shutdown and temporary door seals to minimize agent loss and maintain the target concentration during the flooding phase. Hazard classification guides the overall design, categorizing risks as Class A (ordinary combustibles, including deep-seated fires), Class B (flammable liquids, tested via cup burner methods), or Class C (energized electrical equipment, with a 35% safety factor). Concentrations are adjusted according to the agent type and hazard; for example, the cup burner extinguishing concentration for Class B hazards using halocarbon agents, or 1.3 times the extinguishing concentration for certain inert gas agents. For high-rack storage configurations, designs incorporate adjustments like elevated agent quantities to address the increased net volume and potential obstructions from shelving, ensuring uniform distribution through optimized nozzle placement. Acceptance testing verifies system performance prior to commissioning, encompassing pre-discharge functional checks of control valves, detection alarms, abort mechanisms, and piping integrity to confirm no leaks or blockages under simulated conditions. Post-installation, a door fan test pressurizes the enclosure to measure leakage rates, ensuring retention of at least 85% of the design concentration for the required hold time, with results documented in a contractor certification. These procedures confirm compliance with and identify any installation deficiencies before reliance on the system.

Room Integrity Assessment

Room integrity assessment is essential for gaseous fire suppression systems, as it verifies the enclosure's ability to retain the agent at effective concentrations following discharge, thereby preventing re-ignition and ensuring occupant safety during evacuation. The assessment focuses on maintaining a hold time of at least 10 minutes, typically extending to 60 minutes depending on the agent's properties and response protocols, to allow sufficient time for fire suppression and safe re-entry. Leakage rates low enough to retain at least 85% of the design concentration for the required hold time, as verified by the door fan test and effective leakage area (ELA) calculations in NFPA 2001. The primary testing method is the door fan pressurization test, outlined in Annex C of NFPA 2001 and equivalent provisions in ISO 14520, which involves installing a variable-speed fan in a door panel to create controlled pressure differentials (typically 10-25 Pa) across the enclosure. Airflow is measured under both positive and negative pressures, with the average used to calculate the effective leakage area (ELA), providing a predictive model of agent retention without actual discharge. This test categorizes enclosures into low, medium, or high leakage scenarios based on the ELA relative to room volume, where low-leakage rooms (e.g., ELA < 0.1 m² for a 100 m³ space) support longer hold times, while high-leakage ones may require design adjustments. Standards mandate initial testing post-installation and periodic retesting to account for changes. Remediation strategies address identified leaks to restore integrity, including sealing penetrations such as doors, windows, and ductwork with fire-rated materials like intumescent seals or gaskets. During system activation, HVAC systems must be automatically shut down to minimize airflow-induced leakage, and pressure relief vents are often installed to equalize overpressures from agent discharge while limiting agent escape. NFPA 2001 requires annual integrity tests or more frequent assessments after modifications to ensure ongoing compliance. Several factors can compromise room integrity over time, including building settling that widens cracks in walls or floors, unsealed gaps around cable trays and penetrations, and seismic events that damage seals or shift structures. For enclosures with complex geometries, such as those with irregular shapes or multiple compartments, software tools like model airflow and predict hold times by simulating leakage paths and agent dispersion. These assessments integrate with broader system design by informing agent quantity calculations and enclosure modifications.

Applications

Critical Facilities

Gaseous fire suppression systems are essential in data centers and server rooms, where protecting electronic equipment from fire damage without residue is paramount. These systems utilize clean agents, such as hydrofluorocarbons (e.g., ) or inert gases like and , to rapidly suppress fires by reducing oxygen levels or interrupting chemical reactions, ensuring minimal impact on hardware functionality. Unlike water-based alternatives, they leave no conductive or corrosive remnants, making them ideal for environments with high-density servers and storage arrays. In modular data halls, zoned configurations enable precise application of suppression agents to specific compartments, reducing downtime and allowing unaffected areas to continue operations. System design often integrates with uninterruptible power supplies (UPS) and cooling infrastructure, automatically triggering shutdowns upon fire detection to prevent agent dilution and enhance containment. Compliance with standards like NFPA 2001 ensures uniform agent distribution and room integrity testing for effective total flooding. Telecommunications facilities, particularly switching stations, rely on gaseous suppression to safeguard sensitive infrastructure from corrosion and operational disruption. Clean agents like 3M Novec 1230, stored as liquids and discharged as gases, provide rapid fire extinguishment without residue, preserving fiber optic cables and electronic switches essential for network reliability. These systems support early smoke detection and flexible piping layouts suited to complex facility designs. Adoption of gaseous agents in telecommunications accelerated in the 1990s with the proliferation of fiber optic networks, where was widely implemented to protect high-value transmission equipment before its phaseout under environmental regulations. Post-Halon, inert and chemical gases have maintained this role, aligning with guidelines for legacy systems and for modern alternatives. In power generation settings, turbine enclosures and control rooms employ gaseous suppression to mitigate risks in energized environments where water could induce electrical shorts or thermal shock. Carbon dioxide (CO2) systems, delivering non-conductive agents via total flooding, achieve required concentrations—typically 34% for liquid fuels or 37% for natural gas—within one minute to address rapidly escalating fires near rotating machinery. Clean agents like FM-200 or Inergen serve as Halon replacements, offering similar speed without ozone-depleting effects. These installations prioritize rapid response for live equipment, integrating with gas detection and emergency shutdown devices to isolate fuel sources before discharge, as outlined in NFPA 12 and NFPA 850. Enclosure integrity is critical, with retention times of 20-30 minutes post-suppression to prevent re-ignition. Aviation applications favor pure gaseous suppression in enclosed bays and engine test cells, where residue-free extinguishment protects aircraft components and testing instrumentation from contamination. CO2 and clean agent systems, compliant with for hangars and for test facilities, enable quick deployment in confined spaces to counter fuel-related hazards without compromising structural integrity. In engine test cells, gaseous agents address high-heat, high-velocity fire scenarios by flooding the volume efficiently, often paired with automatic detection for sub-minute activation to minimize damage to prototypes and calibration tools. These setups avoid water mist in sensitive bays to prevent corrosion on avionics, emphasizing sealed environments for optimal agent retention.

Specialized Environments

In specialized environments, gaseous fire suppression systems are adapted to address unique constraints such as asset preservation, spatial limitations, corrosive conditions, and operational sensitivities, ensuring minimal disruption while complying with sector-specific standards. These applications prioritize agents that leave no residue and pose low risks to occupants or equipment, often integrating detection and discharge mechanisms tailored to confined or high-value spaces. Museums and archives employ low-concentration clean agents like to safeguard irreplaceable items such as paper documents, textiles, paintings, and artifacts from water damage associated with traditional sprinklers. , a fluoroketone-based agent, discharges as a gas that rapidly absorbs heat to suppress fires without depleting oxygen or leaving residue, making it suitable for dry storage areas like electronic records vaults where it activates at temperatures around 150°F, with backup water-based systems set higher at 285°F to prevent premature activation. In climate-controlled display cases, micro-discharge systems using enable localized suppression, minimizing exposure to broader collections while maintaining environmental stability for humidity-sensitive materials. These systems adhere to standards for clean agent extinguishing, ensuring safe evacuation and post-discharge cleanup without harming cultural property. Marine and offshore environments utilize corrosion-resistant gaseous suppression systems, often employing CO₂ or inert gas agents in engine rooms and machinery spaces to counter the harsh saltwater exposure on ships and oil platforms. CO₂ systems, which displace oxygen to smother fires, are designed with robust, marine-grade piping and cylinders to withstand corrosion, complying with and the International Code for Fire Safety Systems () Chapter 5.2.2 for fixed installations. Inert gas mixtures, such as IG-541 (nitrogen, argon, and CO₂), provide similar oxygen reduction while offering lower toxicity for crewed areas, with systems incorporating lockout valves and odor additives like wintergreen for safety during maintenance. These setups on offshore platforms emphasize modular, weatherproof enclosures to ensure reliability in explosive atmospheres, integrating with deluge backups for total flooding protection. Healthcare facilities, particularly in MRI rooms and operating theaters, rely on non-metallic gaseous agents to avoid interference with magnetic fields and prevent false discharges that could compromise patient safety or sterile environments. In MRI suites, clean agents like (equivalent to ) or CO₂ are deployed via MR-conditional extinguishers and fixed systems, absorbing heat or displacing oxygen without ferrous components that could become projectiles under high-field strengths up to 7 Tesla. Operating theaters use pre-action clean agent systems, which require dual detection (smoke/heat) before discharge, minimizing accidental activation during procedures; these integrate inert gases per to reduce oxygen to approximately 12-13% while allowing safe 5-minute exposure limits for evacuation. Such adaptations, often combined with water mist backups, protect sensitive imaging equipment and surgical areas without residue that could lead to infections. Military applications feature compact, high-reliability gaseous units for confined spaces like submarine compartments and ammunition storage, replacing legacy Halon 1301 with ozone-safe alternatives to maintain stealth and operational integrity. In submarines, inert gas blends like IG-541 or HFC-227ea (FM-200) are selected for their rapid distribution in narrow volumes, achieving design concentrations of 34.9% and 7.9% respectively, with low toxicity (NOAEL >10%) suitable for occupied areas under pressure. For ammunition storage, these systems use total-flooding inert or clean agents to suppress ignition sources without water that could destabilize munitions, incorporating vibration-resistant components and automatic detection for high-hazard reliability. U.S. transitions emphasize agents meeting MIL-STD criteria for minimal visibility and post-discharge , ensuring crew safety in sealed environments.

Safety and Risks

Health Hazards

Gaseous fire suppression systems pose health hazards primarily through asphyxiation and acute exposure effects, though proper design and procedures minimize risks to occupants. Inert gas agents, such as or , extinguish fires by reducing ambient oxygen concentrations to 12-15%, which can impair judgment and coordination below 16% oxygen and lead to within 1-2 minutes at levels under 12%. CO2-based systems present additional dangers via , where elevated CO2 levels (e.g., 7-10%) cause headaches, , and , progressing to or convulsions within minutes to an hour at 10-15%, and rapid suffocation at higher concentrations exceeding 17%. Chemical agents like FM-200 (HFC-227ea) can decompose under fire conditions to produce (), a potent irritant gas that causes severe irritation, , and systemic toxicity even at low concentrations; mild symptoms occur above 2.9 ppm, with lethal effects reported in incidents involving exposures from suppression system activation. System discharge also generates high noise levels, often reaching 120-130 dB, which can cause immediate hearing damage without protection due to . Additionally, rapid gas expansion during discharge induces a cold effect, dropping room temperatures by 5-30°C depending on the agent, potentially leading to thermal discomfort, near nozzles, or exacerbated respiratory issues in vulnerable individuals. Safety thresholds for agents like FM-200 are defined by the (NOAEL) at 9% concentration, where no cardiac sensitization or other occur in healthy adults, and the Lowest Observed Adverse Effect Level (LOAEL) at 10.5%, beyond which risks such as arrhythmias increase. System designs maintain agent concentrations below the LOAEL—typically 7-9% for FM-200—to ensure occupant safety during brief exposures, prioritizing evacuation over prolonged presence. Mitigation strategies focus on personnel evacuation and , including mandatory 30-second pre-discharge alarms audible above ambient to occupants, followed by time for safe exit. Evacuation plans, room integrity testing, and defined safe holding times (e.g., 5-15 minutes post-discharge before re-entry) prevent re-exposure, while specialized training for at-risk personnel in facilities like data centers emphasizes rapid response to alarms and avoidance of confined spaces during activation.

Environmental Impacts

Gaseous fire suppression agents have varied environmental profiles, with historical agents like halons posing significant risks to the , while newer alternatives aim to minimize atmospheric impacts. Halon 1301, a brominated compound, exhibits a high (ODP) of 10, contributing to stratospheric breakdown and leading to its global phase-out under the . Modern chemical agents, such as hydrofluorocarbons (HFCs) and fluoroketones, have an ODP of zero, avoiding further depletion of the . Many gaseous agents also influence through their global warming potentials (GWPs), which measure heat-trapping capacity relative to over 100 years. HFCs like FM-200 (HFC-227ea) have a high GWP of 3,220, amplifying climate forcing despite their zero ODP. In contrast, fluoroketone agents such as Novec 1230 (FK-5-1-12) feature a short atmospheric lifetime of approximately 5 days, resulting in a negligible GWP of less than 1 and reduced long-term ; however, as of 2025, 3M has discontinued production of branded Novec 1230, though the generic compound FK-5-1-12 remains available from other manufacturers. Beyond direct atmospheric effects, some agents produce byproducts during events that can harm ecosystems. Thermal breakdown of HFCs and similar compounds yields (HF), a highly corrosive acid that can enter waterways, lowering levels and stressing organisms through acidification. Inert gas agents, including and mixtures, leave negligible ecological footprints as their components are naturally occurring atmospheric gases with no persistent byproducts or concerns. Sustainability efforts in the field emphasize transitioning to lower-impact alternatives and , including the phase-down of high-GWP HFCs like FM-200 under the U.S. AIM Act (starting 2022, targeting 15% of baseline by 2036) and a recent EPA rule extending allowances through 2030 (August 2025). Hydrofluoroolefins (HFOs), such as HFO-1336mzz(Z), are emerging as fire suppressants with GWPs below 1 and zero ODP, offering a pathway to reduce from suppression systems. Additionally, recycling programs for agent cylinders, including recovery of residual halons and HFCs, help curb manufacturing-related emissions by reusing materials and preventing atmospheric release of potent gases.

Regulations and History

Standards and Compliance

Gaseous fire suppression systems are governed by several key international and national standards that ensure their safe design, installation, and operation. The (NFPA) 2001, Standard on Clean Agent Fire Extinguishing Systems, provides comprehensive requirements for total flooding and local application systems using electrically nonconductive gaseous agents that leave no residue upon evaporation. The 2025 edition includes added clarifications for time delay mechanisms and enhanced safety factors for testing protocols. Similarly, the (ISO) 14520 series, particularly Part 1: Physical properties and system design, outlines requirements and recommendations for the design, installation, testing, maintenance, and safety of gaseous fire-extinguishing systems, including specific parts for various agents like FK-5-1-12 and HFC-23. In the , Regulation (EU) No 517/2014 on fluorinated greenhouse gases imposes a phase-down of hydrofluorocarbons (HFCs), limiting their use in fire suppression to reduce emissions by up to 79% by 2030 compared to 2005 levels, thereby encouraging low-global-warming-potential alternatives. Certification processes are essential for verifying the reliability of gaseous suppression components. Underwriters Laboratories (UL) provides listing services for agents and system units, such as UL 2166 for clean agent extinguishing system units and standards for systems, ensuring they meet performance and safety criteria for fire hazards. In workplace settings, the (OSHA) standard 29 CFR 1910.160 mandates annual inspections of fixed extinguishing systems by personnel knowledgeable in their design and function, with monthly checks for portable components to maintain operational readiness. International variations address sector-specific needs, particularly in maritime and environmental contexts. The International Maritime Organization's (IMO) Safety of Life at Sea (SOLAS) Convention, through its International Code for Fire Safety Systems (FSS Code), requires fixed gas fire-extinguishing systems on ships, including equivalents to traditional agents tested per IMO MSC/Circ. 848 guidelines for machinery spaces and cargo pump rooms. In the United States, the Environmental Protection Agency's (EPA) Significant New Alternatives Policy (SNAP) program evaluates and approves substitutes for ozone-depleting substances in fire suppression, listing acceptable options like 2-BTP and Powdered Aerosol H while restricting high-global-warming-potential HFCs. Compliance involves rigorous processes to enforce these standards. Systems must feature clear labeling on agent containers to identify contents and hazards, as required by OSHA's Hazard Communication Standard (29 CFR .1200) and EPA rules for ozone-depleting substances like HCFCs. Record-keeping is mandatory for agent recharges, inspections, and maintenance to demonstrate adherence, often via tags or digital logs. Third-party audits by certified bodies verify installations against NFPA 2001 or ISO 14520, ensuring ongoing conformity. Non-compliance with obligations, implemented nationally, can result in substantial civil penalties in the US under the Clean Air Act or equivalent civil penalties elsewhere, alongside potential trade restrictions for ozone-depleting substance misuse in fire suppression.

Historical Evolution

The development of gaseous fire suppression systems began in the early with the pioneering use of (CO₂) as an extinguishing agent. In 1917, the Kidde Company acquired patent rights for CO₂ application in suppressing large-scale fires, particularly on ships, marking an initial shift toward gaseous methods over traditional water-based systems. By 1924, Walter Kidde & Company introduced the first portable in response to demands from industries like for non-damaging alternatives. These innovations laid the groundwork for fixed gaseous systems, which gained prominence during for protecting aircraft engines; CO₂ suppression was deployed in models such as the C-46, C-47, B-17, B-26, and B-45 to rapidly displace oxygen in engine compartments and prevent in-flight fires. The mid-20th century saw the rise of halon-based agents, which offered superior efficiency and minimal residue. 1301 () was developed in 1954 through a between the U.S. Army and , and commercially introduced in the as a total-flooding gaseous suppressant ideal for enclosed spaces. Its adoption accelerated in the , particularly in military applications for vehicle and ship protection, as well as in emerging computer data centers where clean, non-conductive extinguishment was essential to avoid equipment damage. 1301's chemical action—interrupting the fire's free radical —made it the dominant choice for high-value assets, with systems installed on following major and incidents that underscored the need for rapid, reliable suppression. Concerns over environmental impacts prompted a global phase-out of halons, beginning with the 1987 , which identified them as significant ozone-depleting substances and mandated reductions in production and consumption. This treaty, ratified by numerous nations, accelerated research into alternatives, leading to the commercialization of inert gas mixtures like Inergen in the 1980s; composed of , , and a trace of CO₂, it safely lowered oxygen levels without products. As halon stocks dwindled, (HFC) agents emerged, with DuPont's FM-200 (HFC-227ea) approved by regulatory bodies in 1994 as a direct replacement, offering similar performance in total-flooding applications for data centers and . In the , further environmental pressures drove innovation toward lower-global-warming-potential (GWP) options. launched Novec 1230 (a fluorinated ) in the early as a non-ozone-depleting, low-GWP alternative suitable for occupied spaces, emphasizing its rapid heat absorption mechanism for suppressing electronic and ordinary combustibles. The 2016 Kigali Amendment to the extended phase-down targets to HFCs, including those used in fire suppression like FM-200, prompting a shift toward inert gases and next-generation chemicals to mitigate climate impacts. By the 2020s, integration of (AI) with gaseous systems enabled predictive capabilities, such as real-time sensor analysis for early and automated agent release, enhancing response in like farms.

References

  1. [1]
    Clean Agent System Basics - NFPA
    May 6, 2022 · Here we will review the different types of gaseous fire protection systems and how they work. How do gaseous suppression agents work?
  2. [2]
    Gaseous Fire Suppression Systems: FE-13, FM-200, Novec 1230
    Gaseous fire systems are designed with the intent of fire extinguishment as opposed to fire control normally provided by a traditional fire sprinkler system.
  3. [3]
    Clean Agent Fire Suppression Update
    ### Summary of Historical Overview of Clean Agent Fire Suppression
  4. [4]
    NFPA 2001 Standard Development
    NFPA 2001 is a standard on clean agent fire extinguishing systems, covering total flooding and local application systems. It is for those who purchase, design, ...
  5. [5]
  6. [6]
    Which Gases Are Used in Fire Suppression Systems?
    Jul 23, 2020 · Gaseous fire suppression systems are perfect for protection of electronics and machinery. But there are several types of gases used in fire ...
  7. [7]
    Room Integrity for Gaseous Fire Suppression Systems - NFPA
    Mar 12, 2021 · Here we'll review how gaseous suppression agents work, why the integrity of the room matters, how that is tested, and finally controls that can be set in place.
  8. [8]
  9. [9]
  10. [10]
    Advantages Of Gaseous Fire Suppression Systems | MEP Fire
    Jul 3, 2023 · Unlike water-based systems, gaseous suppression systems do not cause damage in the aftermath. They do not leave behind residue, water, or foam, ...
  11. [11]
    Gas Suppression Systems | No Water Damage Fire Protection
    Oct 28, 2025 · Protect data centres, documents & equipment from fire with clean, fast-acting gas suppression systems. No water, no residue, no downtime.
  12. [12]
  13. [13]
    [PDF] 0451 - F206S - Fire Protection For Fuel Cycle Facilities - Background.
    The triangle/tetrahedron (Figure 1) illustrates these elements that must be present for a fire to occur. The target for lower flammability limit is less than ...
  14. [14]
    [PDF] Chapter 3: FLAME SUPPRESSION CHEMISTRY
    The main ramification of the above gas phase inhibition mechanism for fire suppression is that lowering radical concentrations lowers the overall reaction rate ...
  15. [15]
    [PDF] Effective Thermal Fire-Extinguishing Agents: Final Report, NGP ...
    concept of a limiting oxygen index (LOI), which is defined to be the lowest oxygen concentration in air diluted with nitrogen that can support a flame ...
  16. [16]
    Carbon Dioxide as a Fire Suppressant: Examining the Risks | US EPA
    The standard calls for safeguards such as pre-discharge alarms and time delays to ensure prompt evacuation prior to discharge, prevent entry into areas where ...
  17. [17]
    ASSESSMENT OF RESEARCH ON ALTERNATIVES FOR HALON
    Halons suppress fires by both physical and chemical mechanisms. With halons, the bromine atoms are critical to disrupting the radical chains. Other agents that ...
  18. [18]
    [PDF] flame retardant alternatives for hexabromocyclododecane (hbcd)
    HBr + OH• → H2O + Br•. HBr + •O• → OH• + Br•. HBr + H• ↔ H2 + Br•. HBr + RCH2• ↔ RCH3 + Br•. RBr ↔ R• + Br•. Source: Kaspersma, Doumen et al. 2002. 3-5. Page ...
  19. [19]
    Fire Suppression Substitutes and Alternatives to Halon for U.S. Navy ...
    Because of these characteristics, halon 1301 (a total flooding agent) and halon 1211 (a streaming agent) are widely used on board Navy ships, in aircraft, and ...
  20. [20]
    IG-541 inergen fire suppression systems - Gielle Industries
    Inergen is a mixture of 52% Nitrogen, 40% Argon and 8% CO2. However, in the event of a fire, when Inergen is discharged, it mixes with the air present in the ...Missing: mechanism NFPA
  21. [21]
    IG-55 argonite fire suppression systems - Gielle Industries
    IG-55 is a clean agent fire extinguishing system using an inert gas (IG-55) consisting of 50% Nitrogen and 50% Argon and is used in total flooding systems.Missing: details | Show results with:details
  22. [22]
    IG-01 Product Information | MEP Fire
    It is an inert gas consisting of 100% Argon. Gas Specification. The gas specification is usually confirmed ...
  23. [23]
    Inert Gas Fire Suppression | MEP Fire
    IG-55 (Argonite), 50% Argon and 50% Nitrogen ; IG-541 (Inergen), 52% Argon, 40% Nitrogen and 8% CO2 ; IG-100 (Nitrogen), 100% Nitrogen ; IG-01 (Argon), 100% Argon ...
  24. [24]
  25. [25]
    INERGEN 200 Bar System | Fire Suppression System - Ansul
    The INERGEN 200 Bar System is a gaseous clean agent fire suppression system using three gases to suppress fires, suitable for non-conductive areas, and has no ...Missing: 60 seconds
  26. [26]
    [PDF] DS 4-9 Halocarbon and Inert Gas (Clean Agent) Fire Extinguishing ...
    Oct 1, 2018 · 1. IG-541 minimum design concentration for Class B fires, based upon the cup-burner test value specified in NFPA 2001, Standard on Clean ...
  27. [27]
    INERGEN (IG-541) – Clean Agent Gas Suppression System
    This increase in CO2 content to ~3% increases an individual's respiration rate, depth of breathing and the body's ability to absorb oxygen, thus allowing people ...Missing: component | Show results with:component
  28. [28]
    A Comparative Review of IG-541 System Use in Total Flooding ...
    IG-541 is a mixture of three inert gases: nitrogen (52%), argon (40%), and carbon dioxide (8%). IG-01 consists solely of argon, an unblended inert gas.
  29. [29]
    Inert gas fire suppression systems - Gielle Industries
    Inert gas fire suppression systems use argon and nitrogen to reduce oxygen, preventing combustion. They are a safe, natural, and clean way to extinguish fire.
  30. [30]
    [PDF] FM-200™ Properties, Uses, Storage, and Handling - Chemours
    Chemours has developed environmentally preferred agents, such as hydrofluorocarbon (HFC) 227ea, to protect critical facilities against fires, as HFCs offer.
  31. [31]
    [PDF] 3M™ Novec™ 1230 Fire Protection Fluid
    The boiling point of Novec 1230 fluid is 49.2⁰C, meaning this product has a much lower vapour pressure than other clean agents, which are gases at ambient ...
  32. [32]
    [PDF] hfc-227ea clean agent - DATA SHEET
    HFC-227ea extinguishes a fire by a combination of chemical and physical mechanisms. HFC-227ea does not displace oxygen and therefore is safe for use in ...<|separator|>
  33. [33]
    [PDF] Halon Alternatives Extinguishment Pathways
    HBr, formed by bromine combining with a hydrogen atom, can react with a second hydrogen atom to form a much less reactive hydrogen molecule, regenerating the ...
  34. [34]
    Comparison of Fire Suppression Systems: FM-200 vs Novec 1230
    Global Warming Potential (GWP). 1. 3500. Global Environmental Warranty on Agent (Years). 20 Years. None. Subject to Phase-Down under EU F-Gas Regulation. No.
  35. [35]
    GWP 101: Global warming and the impact of hfc-based clean fire ...
    Oct 9, 2018 · FM-200 (HFC-227ea) has a GWP value of 3220 – does that mean it has a large impact on global warming? The facts provide a clear answer of no, as ...
  36. [36]
    FM-200 Fire Suppression Systems - Firetrace
    FM-200™ removes the heat or free radicals, which interferes with the fire triangle's chemical reaction to extinguish the fire. Clean agent fire suppression ...
  37. [37]
    Clean Agent Fire Suppression Update - SFPE
    For over half a century from 1910 to the late 1960s, when a clean, dry, gaseous fire-extinguishing agent was required, carbon dioxide was the choice, ...
  38. [38]
    Hydrofluorocarbons and the Kigali Amendment to the Montreal ...
    At the time , HFCs were thought to be acceptable substitutes for ozone layer-depleting chlorofluorocarbons (CFCs). In 2016, the international community, led by ...
  39. [39]
    Historical Agreement on HFCs reached in Kigali
    Oct 15, 2016 · “The Kigali Amendment is the most significant climate mitigation step the world has ever taken, and brings us closer to staying below 1.5°C,” ...
  40. [40]
    VESDA Aspirating Smoke Detection - Ansul
    VESDA Detection is an aspirating smoke detection solution that is able to accommodate a broad range of environments and applications.
  41. [41]
    NFPA 2001 Guidelines for Clean Agent Fire Suppression Systems
    Among clean agents, inert gas is the most environmentally friendly with zero Ozone Depletion Potential (ODP) and GWP. Novec 1230 stands out for its low GWP, ...
  42. [42]
    Clean Agent Fire Suppression Systems - ORR Protection
    Jun 24, 2021 · In 2012, NFPA 2001, which is a standard on clean agent fire extinguishing systems increased the safety factor required for Class C fires. A ...
  43. [43]
    AUTOPULSE AP-4001 Addressable Fire Alarm Control Panel - Ansul
    Features · 4,064 available addresses · 1500 software zones · NFPA 72 compliant smoke sensitivity test built-in · 4,000 event history buffer ...
  44. [44]
    [PDF] HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM - Hochiki
    Hochiki HFC-227ea is suitable for use on Class A, Class B, and ... It contains no chlorine or bromine and fully complies with NFPA 2001 and ASTM D6064.
  45. [45]
    [PDF] Standard on Clean Agent Fire Extinguishing Systems
    NFPA® codes, standards, recommended practices, and guides (“NFPA Standards”), of which the document contained herein is one, are developed through a ...
  46. [46]
  47. [47]
    [PDF] Procedures and Guidelines for Access and Safely Performing Work ...
    Fire Suppression Systems a. A clean agent HFC-125 (ECARO -25) gaseous fire suppression system is used in the datacenter of the SRCF. HFC-125 can safely ...
  48. [48]
    Protecting Racks with FIRESCI DLP and ILP Clean Agent Systems
    Jul 7, 2025 · Common Fire Risks in Modular Data Centers · Electrical faults in server racks or power distribution units (PDUs) · Battery overheating and thermal ...
  49. [49]
  50. [50]
    Fire Protection in Telecommunications
    Learn how ORR Protection Systems can help protect telecom systems. See how our fire sprinklers, suppression systems, and support can help.Telecommunications Resources · The Orr Difference · Suppression Clean Agent<|separator|>
  51. [51]
    Fighting Fires in Data Centers - Facilities Management Insights
    May 1, 2007 · Until the mid 1990s, one substance was used to protect most data and telecommunications centers from smoke and fire damage: Halon 1301. Unlike ...
  52. [52]
    FIRE SUPPRESSION FOR COMBUSTION TURBINES IN ...
    Its advantages comprise the lack of any residue, low cost and its electrically nonconductive properties. Its disadvantage is its asphyxiation hazard. The ...
  53. [53]
    Complete Fire Protection Solutions for the Aviation Industry - Ansul
    ANSUL provides airports, hangers, and runways with the fire suppression technology they need to contain and control potentially catastrophic fires.
  54. [54]
    [PDF] Fire Suppression & Cultural Property - National Archives
    Museum fire control ca. 1978. No sprinklers in exhibits. Halon ... Novec™ 1230 (halogenated). Page 12. Staff training with clean agents. Page 13 ...
  55. [55]
    [PDF] Archives and Museums | Torvac Solutions
    SAPPHIRE clean agent systems contain 3M™ Novec™ 1230 fire protection fluid, an effective fire suppressant designed for special hazard, high value applications.
  56. [56]
    [PDF] 3M™ Novec™ 1230 Fire Protection Fluid
    When discharged through a nozzle from a properly designed system, Novec 1230 fluid will rapidly vaporize and evenly distribute throughout the protected space.
  57. [57]
    Carbon Dioxide Fire Suppression Systems on Commercial Vessels
    Feb 24, 2010 · Carbon dioxide systems work by flooding a protected space with CO2, thereby depriving a fire of the oxygen it needs to burn. Unfortunately, when ...
  58. [58]
    Offshore Applications - FireFlex systems
    Designed to withstand harsh marine conditions, integrated fire protection cabinets are built with corrosion-resistant materials and weatherproof enclosures, ...
  59. [59]
    Fire Extinguisher Standards for HealthCare Facilities
    Nov 30, 2023 · Three types of non-magnetic extinguishers that have been developed that are suitable for use in an MRI room are clean agent FK-5-1-12, carbon ...
  60. [60]
    [PDF] 10 Fire Protection (FP) – Special Areas Design
    Both pre-action and Gas suppression can be provided in the same room, with the gas ... In operating theatres, audio alarms and strobe lighting shall be removed ...
  61. [61]
    [PDF] A Risk Assessment Approach for Selecting a Replacement for Halon ...
    Halon 1301 fire suppressant systems are currently installed on the Collins class submarines, the Anzac class and FFG-7 frigates, however it is RAN policy to ...
  62. [62]
    Military Facilities | Extintech | Next Generation Fire Protection
    Automatic Gaseous Fire Suppression Systems ... These systems are specially designed and installed for various military zones such as ammunition storage, vehicle ...<|control11|><|separator|>
  63. [63]
    Fire Suppression Substitutes and Alternatives to Halon for U.S. Navy ...
    The Navy is shifting to non-halon fire extinguishing systems for its next-generation, new-design aircraft, and the proposed Joint Strike Fighter (JSF) will use ...Missing: submarines | Show results with:submarines
  64. [64]
    [PDF] Oxygen Deficiency Hazard associated with Hypoxic Fire ... - EIGA
    This information sheet applies to Hypoxic Fire Suppression Systems using nitrogen injection to generate and maintain the atmosphere for their stated purposes.
  65. [65]
    OSHA Technical Manual (OTM) - Section II: Chapter 3 - OSHA
    Feb 11, 2014 · Oxygen concentrations below 12 percent will bring about unconsciousness rapidly and without warning, and are considered IDLH. Oxygen enriched ...Missing: suppression | Show results with:suppression
  66. [66]
    [PDF] Carbon Dioxide as a Fire Suppressant: Examining the Risks
    This document examines the risks of using carbon dioxide as a fire suppressant, including its extinguishing mechanism, effectiveness, and life safety ...
  67. [67]
    [PDF] BULLETIN 15-1 - NJ.gov
    It is possible, however, to suffer anoxia or asphyxiation from breathing higher levels of CO2. Elevated blood and tissue levels of CO2 are termed hypercapnia ...
  68. [68]
    Hydrogen Fluoride - NCBI - NIH
    Thus, mild symptoms of lower airway irritation occur at exposures as high as 2.9 ppm, and more marked symptoms may occur in some people exposed at higher ...Missing: FM- | Show results with:FM-
  69. [69]
    Gas fire-suppression system damages servers. Correlation between ...
    A sound of around 130 dB is enough to generate enough vibrations to move the heads of HHDs. Dutch bank ING found the hard way that the noise generated by a ...
  70. [70]
    [PDF] High Pressure CO2 Fire Protection Systems
    In addition to its smothering action, the reduction in temperature due to its rapid expansion will provide some suppression caused by the cooling effect ...
  71. [71]
    [PDF] Argon fire extinguishing systems - the simple solution
    The NFPA have now included Argon in their Fall '95. Report on Proposals of their NFPA 2001 document with oxygen concentrations down to 12% for occupied ...
  72. [72]
    [PDF] FM-200 Fire Suppression Agent - ORR Protection
    NOAEL. (No Observable Adverse Effect Level). 9.00%. LOAEL. (Lowest Observable Adverse Effect Level). 10.50%. Table 1. FM-200 Physical Properties. Table 2. FM- ...Missing: suppressant | Show results with:suppressant
  73. [73]
    [PDF] DuPont™ FM-200® (HFC-227ea) Fire Extinguishing Agent
    The threshold cardiac sensitization, lowest observed adverse effect level (LOAEL) for FM-200® is 105,000 ppm. (10.5%) and the no observed adverse effect level ( ...
  74. [74]
  75. [75]
    Ozone-Depleting Substances | US EPA
    Mar 25, 2025 · chlorofluorocarbons Gases covered under the 1987 Montreal Protocol and used for refrigeration, air conditioning, packaging, insulation, solvents ...
  76. [76]
    Formation and detection of hydrogen fluoride gas during fire fighting ...
    Risk of HF exposure has also been reported from the thermal decomposition of hydrofluorocarbon (HFC)-based fire suppression systems and during lithium-ion ...
  77. [77]
    Why Inert Gas Fire System is Environmentaly Friendly | Rotarex
    Feb 13, 2017 · Inert gases are environmentally neutral, with zero ODP (ozone depletion potential) and zero GWP (global warming potential). When using inert gas ...
  78. [78]
    Suppression of propane cup-burner flame with HFO-1336mzz(Z ...
    In comparison, hydrofluoroolefins (HFOs) are more environmentally benign with low GWP and ALT values [9–11], but the fire-suppressing performance of HFOs is ...
  79. [79]
    Halons Program | US EPA
    Sources of recycled halons include stockpiles and recovered agent from cylinders collected from decommissioned systems both in the United States and abroad.Missing: benefits | Show results with:benefits
  80. [80]
    Gaseous fire-extinguishing systems - ISO 14520-1:2023
    In stock 2–5 day deliveryThis document specifies requirements and gives recommendations for the design, installation, testing, maintenance and safety of gaseous firefighting systems.
  81. [81]
    [PDF] Regulation (EU) No 517/2014 of the European Parliament and of the ...
    Apr 16, 2014 · Regulation (EU) No 517/2014 concerns fluorinated greenhouse gases, aiming to reduce emissions by 72-73% by 2030 and 70-78% by 2050, and ...
  82. [82]
    Fire Extinguishing System Unit Testing and Certification - UL Solutions
    UL offers safety and performance testing for fire extinguishing systems that are designed, installed and maintained according to National Fire Protection ...
  83. [83]
  84. [84]
    Fire Suppression Systems - dco.uscg.mil - Coast Guard
    This allows for complete manual control of the fixed gas fire extinguishing system by the operator of the vessel. Marking instructions required by 46 CFR ...Missing: offshore | Show results with:offshore
  85. [85]
    SNAP Substitutes by Sector | US EPA
    Dec 19, 2024 · SNAP Substitutes by Sector · Adhesives, Coatings, and Inks · Aerosols · Cleaning Solvents · Fire Suppression and Explosion Protection · Foam Blowing ...
  86. [86]
    Labeling Containers of HCFC Fire Suppression Agent | US EPA
    May 16, 2025 · Learn more about the Class II ODS container labeling requirements for HCFC-123 starting in 2020. Fact Sheet: Labeling Fire Suppression Containers (pdf)Missing: gaseous | Show results with:gaseous
  87. [87]
  88. [88]
    [PDF] Regulatory Alert - IAEG
    Jul 15, 2021 · Penalties for non-compliance include fines and imprisonment up to 2 years. Penalties for non-compliance include fines up to $200,000. N/A.<|control11|><|separator|>
  89. [89]
    The History of Kidde Fire Safety Since 1917
    1917 – Kidde takes ownership of the Rich patent for the use of carbon dioxide for suppression of large fires, particularly aimed at ship fires. 1918 ...
  90. [90]
    A Brief History of the Fire Extinguisher
    The carbon dioxide (CO2) extinguisher was invented (at least in the US) by the Walter Kidde Company in 1924 in reaction to Bell Telephone's request for an ...
  91. [91]
    [PDF] Chapter 2: HISTORY OF FIRE SUPPRESSION IN AIRCRAFTi
    CO2 fire suppression systems for engine compartment protection included the C-46, C-47, B-17, B-26, and the B-45 aircraft. During World War II the German ...
  92. [92]
    NKTECH Business Areas - High pressure gas - Halon 1301
    It was developed in 1954 by a joint venture between the U.S. Army and Dupont, and is an effective gas fire suppression system in the 1960s. It has been. Halon ...<|separator|>
  93. [93]
    [PDF] Chapter 1: Introduction
    During the 1960s and 1970s, two of the compounds tested emerged as commercial successes. ... In 2000, the systems and banks were estimated to contain about 90 ...
  94. [94]
    [PDF] STATUS OF INDUSTRY EFFORTS TO REPLACE HALON FIRE ...
    Mar 16, 2002 · During the halon era (late 1960's to late 1980's), two halons emerged as the market leaders: halon 1301 for total flooding systems and halon ...
  95. [95]
    About Montreal Protocol - UNEP
    Adopted on 16 September 1987, the Protocol is to date one of the rare treaties to achieve universal ratification. The Montreal Protocol phases down the ...
  96. [96]
    Common Types Of Suppression Systems Explained
    INERGEN® was developed in the 1980s by Torbjørn Laursen after conducting various tests and making a thorough study of human respiratory physiology. Agent Used: ...
  97. [97]
    FM-200 Clean Agent - Suppression Systems, Inc.
    The first clean agent brought to the market in 1994 was Dupont™ FM-200®. Introduced as an alternative to the ozone-depleting Halon agents, FM-200® received ...Missing: date | Show results with:date
  98. [98]
    With 3M™ Novec™ 1230's Patent Expired, What Does That Mean ...
    Sep 29, 2021 · We discuss how to assess alternatively sourced FK-5-1-12, clean agents, in light of 3M's Novec 1230 patent expiring.Missing: 2005 | Show results with:2005
  99. [99]
    Next-Gen Fire & Gas Systems: Hybrid Solutions Combining AI, IoT ...
    May 6, 2025 · Hybrid fire and gas safety systems powered by AI, IoT, and robotics are transforming industrial safety by enabling faster threat detection, ...Missing: 2020s | Show results with:2020s