Current loop

A current loop is an analog electrical signaling method widely used in industrial instrumentation and process control to transmit measurement data from sensors to controllers or displays over a pair of wires, where the current level—typically ranging from 4 milliamperes (mA) representing the minimum or zero value to 20 mA for the maximum or full-scale value—corresponds directly to a physical such as , , level, or . This approach ensures that the signal remains constant regardless of wire length or resistance, providing robust communication in harsh environments. The 4-20 mA current loop standard emerged in the 1950s as an electronic successor to earlier pneumatic control systems, which used a 3-15 pounds per square inch (psi) pressure signal for similar proportional representation. As electronic components became more affordable and reliable, the current-based system replaced for its lower cost, simpler installation with , and ability to integrate with emerging technologies like programmable logic controllers (PLCs). The "live zero" at 4 mA was specifically chosen to distinguish a functioning signal from faults, such as a broken wire (0 mA) or over-range conditions (above 20 mA). In operation, a current loop forms a series powered by a , usually 24 volts, comprising key components: a transmitter that senses the process variable and modulates the loop current accordingly; wiring that connects devices; and a , such as a input module or indicator, often with a 250-ohm load to convert the current to a measurable voltage via (V = I × R). Transmitters are commonly two-wire types, where power and signal share the same pair, or three/four-wire variants for separate powering; the system adheres to standards like those from the (IEC) for interoperability. This technology offers several advantages, including high immunity to electromagnetic interference (EMI) and voltage drops over distances up to several kilometers, making it suitable for factory floors and remote monitoring. It also enables easy fault diagnostics and requires minimal calibration. However, limitations include the inability to transmit multiple variables per loop without protocols like HART (Highway Addressable Remote Transducer), potential ground loop issues in multi-device setups, and power constraints for low-energy sensors in two-wire configurations. Despite the rise of digital alternatives like or , the 4-20 mA loop remains a foundational standard in industries such as oil and gas, , and HVAC due to its proven reliability and .

Fundamentals

Principle of Operation

A current loop is a two-wire in which information is transmitted by varying the magnitude of a () rather than voltage levels. This approach ensures that the signal remains robust over distances, as the current value encodes the measured variable, such as or . In operation, the flows constantly throughout the entire loop due to Kirchhoff's current law, which states that the entering a equals the leaving it in a closed . Voltage drops occur across individual components and wiring resistances, but the loop adjusts to maintain the set by varying the supply voltage as needed. This constancy preserves , as the does not degrade with wire length or resistance variations. The core relationship governing the loop is derived from Kirchhoff's voltage law: I = \frac{V_s - V_t - V_w}{R_r + R_w} where I is the loop current, V_s is the supply voltage, V_t and V_w are voltage drops across the transmitter and wiring, and R_r and R_w are the corresponding resistances. The most common range for this varying current is 4–20 mA, representing the span from minimum to maximum process values. The signal transmission process begins with a converting a physical into a proportional variation within the . This then propagates through the interconnecting wires to the receiving controller, where it is interpreted by measuring the across a known (via , V = I \times R). At each point in the loop, the signal effectively regenerates because the remains uniform, independent of local voltage fluctuations. Current-based signaling provides inherent noise immunity compared to voltage signals, as the low-impedance path minimizes susceptibility to and allows the signal to traverse long distances without significant degradation. The "live zero" baseline current further enhances reliability by distinguishing valid signals from faults, such as open circuits.

Key Components

A current loop circuit in industrial instrumentation consists of several essential hardware elements that work together to transmit signals reliably over distances. The primary components include a DC power supply, which provides the necessary voltage—typically 24 V—to energize the loop; a transmitter, which converts a sensor's physical input (such as or ) into a proportional signal; a receiver, such as a () or digital indicator, which interprets the current to display or process the measurement; and field wiring, which connects these elements in a series . The transmitter functions as the active regulator, acting as either a or sink to maintain a stable current flow regardless of load variations, while the receiver incorporates a load that converts the current signal back to a measurable voltage using , where voltage V = I \times R_{\text{load}}, allowing for standard analog-to-digital conversion in control systems. This setup ensures the loop operates on the principle of flow, minimizing signal degradation from voltage drops along the wiring. Loop resistance limits are critical to prevent insufficient voltage for proper operation, with the maximum allowable resistance calculated as R_{\max} = \frac{V_{\text{supply}} - V_{\min}}{I_{\max}}, where V_{\min} accounts for minimum voltage drops across components and wiring. For a typical 24 V supply, a standard configuration supports up to approximately 250 Ω total loop resistance, balancing compliance voltage requirements of the transmitter and receiver. Wiring topology influences efficiency and cost, with two-wire loops being the most common due to their simplicity, as they share the power supply lines for both and transmitter powering, reducing cabling needs compared to four-wire loops that use separate pairs for power and signal. In hazardous environments, safety is enhanced through designs that limit current and voltage to levels incapable of igniting explosive atmospheres, typically using barriers with zener diodes and resistors to cap energy below ignition thresholds, preventing sparks or arcs from field wiring faults.

4–20 mA Standard

Signal Characteristics

The 4–20 mA current loop standard employs a current range spanning 4 milliamperes () to 20 to represent the full scale of a (PV), with 4 designated as the live zero corresponding to the minimum or zero process value and 20 indicating the maximum value. This configuration enables straightforward linear scaling to units, such as mapping the current range to 0–100% or 0–100 pounds per () pressure, facilitating precise representation of outputs in industrial control systems. A critical feature of this signal is its inherent fault detection capability, enabled by the live zero. Currents below 3.6 mA typically signal an open , lead break, or sensor failure, while values exceeding 21 mA denote over-range conditions, short circuits, or diagnostic alarms, allowing systems to distinguish between normal operation and anomalies without additional wiring. These thresholds are standardized under NE 43, which extends the operational range slightly to 3.8–20.5 mA for valid signals and 3.6–3.8 mA or 20.5–21 mA for diagnostic indications, enhancing reliability in process monitoring. The relationship between the measured and the process variable is governed by the linear scaling equation: \text{PV} = \text{Zero} + \left( \frac{I_\text{measured} - 4}{16} \right) \times \text{Span} where I_\text{measured} is the current in mA, Zero is the minimum PV, and Span is the full range (maximum PV minus minimum PV). This formula ensures proportional conversion, with the 16 mA span providing the denominator for . Compliance with the 4–20 mA standard is outlined in ANSI/ISA-50.00.01, which defines the DC current signal parameters. While the 4–20 range dominates modern applications for its fault-tolerant live zero, legacy systems occasionally employ variations such as 0–20 (dead zero, lacking inherent failure detection) or 10–50 (higher current for older pneumatic-to-electronic conversions), though these have been largely supplanted due to inferior immunity and diagnostic features.

Active and Passive Configurations

In 4–20 current loops, devices are classified as active (sourcing) or passive (sinking) based on their role in providing or receiving loop . Active transmitters source the current by maintaining a positive relative to the loop , drawing from an internal supply and regulating the loop current directly. These were common in older systems where the transmitter acts as the , necessitating a passive receiver that simply loads the loop without supplying voltage. In contrast, passive transmitters sink the current by connecting the loop return to , relying on an external for operation and pairing with an active receiver that provides the excitation voltage. The sourcing configuration typically connects the power supply positive terminal to the transmitter's positive input, the transmitter's negative output to the receiver's positive input, and the receiver's negative to the power supply negative, forming a series loop where the transmitter drives the current. In the sinking configuration, the power supply positive connects to the receiver's positive input, the receiver's negative to the transmitter's positive input, and the transmitter's negative to the power supply negative (or ground), allowing the receiver to supply power while the transmitter regulates current flow to ground. These setups ensure unidirectional current flow but require careful polarity matching to avoid damage. Compatibility challenges arise when mixing active and passive devices, as mismatched sourcing and sinking can lead to improper powering or no , often necessitating isolators, barriers, or reversal protection diodes to prevent reverse current or loops. For instance, a sourcing transmitter cannot directly with another sourcing without additional circuitry. In modern systems, sinking (passive) configurations are preferred for their flexibility with programmable logic controllers (PLCs), which often feature built-in sourcing outputs, enabling easier integration in distributed control setups. Examples include loop-powered passive transmitters, which derive all power from the 4–20 mA signal itself for simplicity in field installations, versus self-powered active transmitters that use separate excitation for higher performance in noisy environments. Loop operation requires a minimum of 12 across the transmitter to account for its internal compliance voltage plus drops from wiring and receiver load, ensuring reliable regulation even over long distances.

Historical and Technical Evolution

Origins and

The origins of loops in trace back to the pneumatic signaling era of the and , when the 3–15 standard was established for transmitting measurement and information between instruments and actuators. This pneumatic approach, developed by early instrument manufacturers, enabled feedback in settings but relied on air tubing, which limited transmission distances and increased installation complexity. By the 1950s, the shift to electrical signals addressed these limitations, with companies like Foxboro and Taylor Instruments introducing electronic controllers that utilized current-based transmission for greater range and reliability over wiring. Early electrical instrumentation, including current transmitters, had been advanced in the 1930s by firms such as & Northrup, which specialized in precision measurement devices and laid groundwork for analog signaling in harsh environments. These developments were demonstrated at events like the Instrument Society of America () show in 1958, marking a pivotal transition from pneumatic to electronic systems. The 4–20 mA current loop emerged as the dominant standard in the , supplanting the prior 10–50 mA range due to its reduced power requirements, compatibility with emerging technology, and inclusion of a live zero (4 mA for zero process value) to distinguish valid signals from faults like open circuits. Promoted through activities, this standard gained traction amid the post-World War II automation surge, particularly in chemical and oil sectors, where long-distance, noise-immune signaling was essential for expanding refineries and processing plants. By the , 4–20 mA loops were ubiquitous in industrial automation, supporting the boom in continuous process monitoring. During the 1970s and 1980s, current loops integrated with distributed control systems (DCS), enabling scalable, centralized oversight of complex facilities while leveraging the analog signals' robustness. This era culminated in the mid-1980s development of the HART protocol by Rosemount Inc., which superimposed communication onto the 4–20 mA loop for enhanced diagnostics and without disrupting the analog foundation, solidifying its role in hybrid systems.

Comparison with Other Signals

Current loops, particularly the 4–20 mA standard, offer distinct advantages over voltage-based signals such as 0–10 V in applications, primarily due to their against signal over . Unlike voltage signals, which suffer from caused by wire —limiting reliable transmission to approximately 100 meters in typical setups—current loops maintain because the current remains constant regardless of cable length, allowing accurate transmission up to 1–2 kilometers under optimized conditions like using low-resistance twisted-pair wiring and a 24–36 V supply. This makes current loops preferable for long-distance process monitoring, while voltage signals are simpler and more cost-effective for short runs under 50 meters, requiring fewer components for basic setups like HVAC controls. In comparison to pneumatic signaling systems, which use 3–15 air for transmission, electrical loops provide lower operational costs and faster response times. Pneumatic systems incur higher expenses from generation and specialized tubing (e.g., or ), often making them 2–3 times more costly to install and maintain than wired electrical loops, while loops leverage inexpensive and standard wiring for quicker signal propagation without the low-pass filtering effect of air tubes that slows pneumatic responses. However, pneumatic signals hold an advantage in explosive environments, as they produce no and self-purge with continuous air flow, eliminating the need for explosion-proof enclosures required for electrical loops in hazardous areas like oil refineries. Relative to early digital enhancements like the HART protocol, pure analog current loops lack built-in diagnostics and multi-variable communication capabilities. HART superimposes a low-frequency digital signal (using frequency-shift keying at 1200 bps) onto the existing 4–20 mA analog loop via the same two wires, enabling bidirectional data exchange for device status, calibration, and fault detection without infrastructure replacement—features absent in standalone analog systems, which transmit only a single steady-state value. This hybrid approach improves reliability by cross-verifying analog and digital readings, addressing analog's vulnerability to undetected biases, while preserving compatibility with legacy 4–20 mA controllers. Despite these strengths, current loops exhibit limitations compared to fully or signals, including slower dynamic response and elevated wiring costs. As steady-state signals, analog loops have inherently low (typically <10 Hz), restricting them to slow-varying processes unlike high-speed digital protocols (e.g., Modbus or Profibus) that support real-time updates in milliseconds for rapid control applications. Additionally, while current loops avoid wireless interference risks, their reliance on physical cabling increases installation expenses—often $1–2 per meter for shielded twisted-pair—versus systems that eliminate wiring altogether, though at the potential cost of latency in noisy RF environments.

Applications and Variations

Process Control Loops

In process control systems, current loops, particularly the 4–20 mA standard, play a central role in integrating sensors, controllers, and actuators within proportional-integral-derivative (PID) control architectures. A typical setup involves a field transmitter that senses a process variable (PV), such as temperature or pressure, and converts it into a 4–20 mA current signal representing the PV range (e.g., 4 mA for minimum and 20 mA for maximum). This signal is transmitted to a PID controller, which processes the PV against a setpoint to generate a corrective output, also in the form of a 4–20 mA signal sent to a final control element like a control valve or actuator to adjust the process. Representative examples illustrate this integration. For temperature monitoring, a resistance temperature detector (RTD) sensor, such as a , connects to a transmitter that linearizes the resistance variation into a 4–20 mA output, enabling precise PID control in heating processes. Similarly, in flow control applications, a pressure transmitter measures differential pressure across an orifice plate and outputs a 4–20 mA signal to the controller, which modulates a valve to maintain desired flow rates in pipelines or reactors. Loop tuning in these systems requires careful consideration of electrical parameters to ensure stable and responsive performance. The total loop resistance, including wiring and load impedances, influences the voltage drop across the loop and can affect the transient response time by altering the circuit's time constant, particularly when capacitance is present; excessive resistance may slow the current adjustment, leading to delayed PID corrections. For loops with multiple devices, such as indicators or recorders in series, isolation amplifiers are employed to provide galvanic separation, preventing ground loops and noise interference while maintaining signal integrity across the 4–20 mA range. The 4–20 mA current loop adheres to established industry standards for integration with supervisory control and data acquisition (SCADA) systems, distributed control systems (DCS), and programmable logic controllers (PLCs). In SCADA and DCS environments, these loops serve as analog inputs for remote monitoring and outputs for automated control, with protocols like HART overlaying digital data on the analog signal for enhanced diagnostics. PLCs commonly feature dedicated 4–20 mA input/output modules that interface directly with these loops, supporting PID algorithms natively for real-time process regulation in manufacturing and utilities. A notable case study in an oil refinery demonstrates the reliability of 4–20 mA current loops for level control in harsh environments. In distillation column operations, level transmitters using radar or differential pressure sensors output 4–20 mA signals to a , enabling to adjust feed valves and maintain inventory levels amid high temperatures, corrosive vapors, and vibrations.

Long-Distance Transmission

Current loops, particularly the 4–20 mA standard, are well-suited for industrial applications but face limitations when transmitting signals over extended distances due to voltage drops across the wiring. The maximum practical distance typically ranges from 1.5 to 3 km, depending on the wire gauge and loop configuration; for instance, 16 AWG copper wire can support approximately 1 km at 20 mA while maintaining sufficient voltage for loop-powered devices. The primary constraint is the voltage drop caused by the resistance of the cable, which must be calculated to ensure the total loop voltage remains above the minimum required by transmitters and receivers, often around 10–12 V. The total voltage drop V_{\text{drop}} across the round-trip cable length is given by: V_{\text{drop}} = I \times (R_{\text{wire}} \times L \times 2) where I is the loop current (worst-case 20 mA or 0.02 A), R_{\text{wire}} is the wire resistance per unit length (e.g., 13.2 Ω/km for 16 ), and L is the one-way distance in km. This drop, combined with the compliance voltage needs of loop components like the total loop resistance of 250–1100 Ω, must not exceed the power supply voltage minus a safety margin of at least 5 V. To mitigate these limitations and extend transmission beyond 3 km, engineers employ strategies such as using larger wire gauges (e.g., 14 AWG for reduced resistance), inserting repeaters or current boosters to regenerate the signal, or converting to fiber optic links for distances exceeding 10 km, which eliminate electrical noise and voltage drop issues entirely. Environmental factors further complicate long-distance transmission, as cable capacitance and inductance can distort signal rise times, potentially limiting response speeds to below 100 ms for changes in process variables, while electromagnetic interference (EMI) induces noise that grounding and shielding help mitigate. In real-world scenarios, such as remote oil field pipeline monitoring, 4–20 mA current loops reliably transmit pressure and flow data over several kilometers using twisted-pair cabling and boosters, enabling centralized control in harsh environments.

Discrete Control Systems

In discrete control systems, current loops are adapted for binary on/off signaling by assigning distinct current levels within or extending the conventional range to represent logical states. Commonly, 4 mA signifies the off or low state, while 20 mA denotes the on or high state, allowing switches and valves to modulate the loop current based on their position. Alternative configurations employ 0 mA for off and 24 mA for on, particularly in applications requiring a complete absence of current in the inactive mode to minimize power consumption or enable clear fault detection. These adaptations find application in relay drivers, where the current threshold energizes or de-energizes the relay coil to control electrical circuits in automation setups. In manufacturing lines, solenoid valves are actuated via current loops, with the binary signal directing fluid or pneumatic flow for processes like assembly or packaging. Position feedback from limit switches is another key use, where mechanical contacts alter the loop current to report endpoint detection, enabling safe and reliable machine operation without separate power lines. Over direct wiring methods, current loop discrete control provides robust noise rejection, as the signal remains constant regardless of voltage fluctuations or electromagnetic interference along the transmission path. Loop-powered relays further enhance this by offering galvanic isolation, preventing ground potential differences from disrupting the control system and safeguarding sensitive electronics. Standards for implementation include integration with programmable logic controller (PLC) discrete input/output modules, which interpret current thresholds—such as >12 mA for on and <8 mA for off—to convert analog loops into binary logic signals. This approach complies with industrial protocols like those in for programming, facilitating seamless incorporation into existing analog infrastructure. Despite these benefits, current loop-based discrete signaling exhibits slower response times compared to native protocols, limiting its suitability for high-speed switching where sub-millisecond latencies are required. To address multi-state needs beyond , systems pair current loops with position encoders, using the loop for basic on/off while encoders provide finer for intermediate positions.

Integration with Two-Way Radios

Current loops integrate with systems to enable wireless transmission of analog data in remote supervisory and (SCADA) environments, extending the reach of wired instrumentation beyond practical cabling limits. In typical setups, 4–20 mA signals from field s are digitized by interface hardware and modulated onto carriers, commonly in VHF (148–174 MHz) or UHF (380–520 MHz) bands, for reliable propagation over distances up to several miles in line-of-sight conditions. This approach is particularly suited for applications in isolated sites, such as oil fields or rural infrastructure, where two-way radios facilitate bidirectional data flow for monitoring and . Interface devices, such as radio modems and I/O converters, serve as the bridge between current loops and radio transmission by sampling the 4–20 mA signal at high resolution (e.g., 16–24 bits) to preserve accuracy, then encoding it for RF before transmission. At the receiving end, compatible modems demodulate the signal and reconstruct the proportional current output, often using opto-isolated drivers to maintain loop integrity and . Examples include the Synetcom WISE 4-20 series, which supports up to eight 4–20 mA channels over licensed VHF/UHF frequencies, and Raveon Technologies' Current Loop Output (CLO) modules, which replicate the wirelessly with minimal distortion. These devices typically employ (FSK) or spread-spectrum techniques for robust data encoding. In utility applications, current loop integration with two-way radios supports remote monitoring of levels or in systems, where 4–20 mA transducers transmit data via VHF/UHF links to central stations, reducing the need for extensive wiring in expansive or rugged terrains. Similarly, in operations, these systems enable equipment and sensor , such as status or , over radio networks that align with existing infrastructure for worker safety and operational efficiency. For instance, radios like the SCADALink SR900 transmit single or multiple 4–20 mA channels alongside discrete signals, achieving ranges exceeding 20 miles in open-pit scenarios. Early protocols for current loop radio integration relied on analog radios with direct 4–20 inputs, where the signal was frequency-modulated onto the carrier for simple, low-bandwidth transmission, though susceptible to noise. Modern implementations favor digital protocols, such as RTU over radio modems, incorporating (FEC) and cyclic redundancy checks to maintain signal fidelity in noisy environments, ensuring measurement accuracy within ±0.1% even over multipath VHF/UHF channels. Systems like Motorola's MOTOTRBO with extensions further enhance this by overlaying data on digital voice channels, supporting integrated alarm and control functions. Key challenges in this integration include introduced by analog-to-digital , , and processes, which can add 50–200 of delay, potentially impacting time-sensitive loops in dynamic applications. Additionally, battery-powered current loops paired with portable two-way radios, common in mobile mining or field utility setups, demand low-power designs—such as those drawing under 40 mA in receive mode—to achieve extended operation, often up to several years on batteries, while avoiding signal degradation from power fluctuations.

References

  1. [1]
    What Is a 4-20 mA Current Loop? | Fluke
    ### Summary of 4-20 mA Current Loop
  2. [2]
    The fundamentals of 4...20 mA current loops - PR electronics
    Rating 4.0 (1,730) A 4-20 mA current loop connects process signals to a controller, using a 4-20 mA range to reflect a process range, regulated by a loop transmitter.Missing: history | Show results with:history
  3. [3]
  4. [4]
    The basics of 4-20mA current loop transmitters - EDN Network
    May 5, 2016 · The history of 4-20 mA current-loop transmitters began when pneumatic signals were used to control actuators and represent proportional ...<|control11|><|separator|>
  5. [5]
    4-20 mA Current Loop Fundamentals, System Design, and Setup
    ### Summary of 4-20 mA Current Loop Principles
  6. [6]
    [PDF] Introduction to the Two-Wire Transmitter and the 4-20mA Current Loop
    In two-wire 4-20mA control loops, we use 2-wire transmitters to convert various process signals representing flow, speed, position, level, temperature, pressure ...
  7. [7]
    Basics of 4-20mA Current Loop | Instrumentation Tools
    Apr 10, 2019 · There are mainly four components: · A DC power supply; · A 2-wire transmitter; · A receiver resistor that converts the current signal to a voltage; ...
  8. [8]
    [PDF] Troubleshooting 4-20 mA Current Loops - Minco
    Calculate maximum allowable loop resistance using the formula: Loop Resistance (maximum) = Vsupply - 7V. 0.020A. For example, a 24V power supply would give a ...<|separator|>
  9. [9]
    4-20mA Max. Load Resistance, Min. Tx and Power Supply Calculator
    This tool will calculate the maximum load resistance, minimum power supply or transmitter supply that can be used, in order for a 4 to 20mA current loop circuit ...
  10. [10]
    Intrinsic Safety | Engineering - Eaton
    Intrinsic safety (IS) is an electrical design approach that prevents explosions from occurring by ensuring that the energy transferred to a hazardous area is ...
  11. [11]
    Intrinsic Safety - OMEGA ENGINEERING
    The basic design of an intrinsic safety barrier uses Zener Diodes to limit voltage, resistors to limit current and a fuse. A Hazardous Area may contain ...
  12. [12]
    ISA50, Signal Compatibility of Electrical Instruments
    To develop standards for signals used in process measurement and control, to transmit information between subsystems or separated elements of systems.Missing: loop | Show results with:loop
  13. [13]
    Functional Safety of 4/20mA Networks - EZ Spotlight - EngineerZone
    Jan 12, 2021 · Figure 5 - 4/20mA currents according to NAMUR standard NE-43. Other standards such as those from ISA 50, IEC 60381-1 and IEC 61131-2 define ...Missing: characteristics | Show results with:characteristics
  14. [14]
    Namur NE43 - DIVIZE industrial automation
    14-day returnsOct 11, 2021 · Namur NE43 specifies a sensor fault is signaled by extending the range of the 4-20mA signal. When the loop current is below 3,6 mA or above 21 ...
  15. [15]
    4-20mA Scaling Calculator - Electrical Engineering Center
    The 4-20mA calculator converts physical measurements to current (4-20mA) and vice-versa, and calculates the percentage of the 4-20mA signal's span.Missing: detection ISA- 61131
  16. [16]
    [PDF] Compatibility of Analog Signals for Electronic Industrial Process ...
    1 The standard current input signal shall be 4 mA to 20 mA, dc (a 16 mA span). 3.3.2 The standard voltage input signal shall be 1 volt to 5 volt dc (a 4 volt ...
  17. [17]
    4-20mA Current Loops - mbedded.ninja
    Mar 10, 2016 · ISA S50.1. The ISA S50.1 standard initially defined both 4-20mA and 10-50mA as possible current ranges. However, the 10-50mA was then later ...4-20ma Current Loops · Types · Namur Ne43
  18. [18]
    [PDF] Ultrasonic Level Transmitter Model LU30 Owner's Manual - Flowline
    The LU30-50_3 is a sourcing transmitter which provides inter- nal 4-20 mA ... The LU30-50_4 is a sinking transmitter which requires external. 4-20 mA ...
  19. [19]
    Sink vs Source in relation to 4-20mA loop | GEO Pressure Systems Inc.
    In 4-20mA loops, a source supplies power (e.g., PLC output card), while a sink receives power (e.g., PLC input card).Missing: active configurations
  20. [20]
    [PDF] Smart Wireless THUM Adapter | Emerson
    An active loop exists when the wired device is supplying the power to the 4-20. mA loop. It is important to verify if the wired device is operating in active or.
  21. [21]
    History of 3-15 psi, 10-50 mA, and 4-20 mA signals - Inst Tools
    Sep 19, 2020 · Before 4-20 mA the signals were 3-15 psi and 10-50 mA. These signals all have a “live zero” (3 psi, 10 mA, and 4 mA) rather than a “dead ...Missing: S50. variations
  22. [22]
    [PDF] Measuring and Control History
    In 1908, Taylor Instruments made a significant contribution to the control industry by installing two experimental tube system type temperature recorders in a ...
  23. [23]
    [PDF] M&C technology history - Automatic control (LTH)
    Leeds & Northrup in 1981 introduced the positioning using fiber optics. first self-tuning automatic controller. Honeywell in 1982 introduced its UDC 500.
  24. [24]
    Boom Times | Science History Institute
    Jul 29, 2013 · After the war Hercules turned itself into a chemical producer, one whose products eventually spanned specialty chemicals, petrochemicals, ...
  25. [25]
    A 1978 Perspective on Control Systems Future - ISA Interchange
    The first big project involved “modernizing” a refining unit originally built in the early 1950s with pneumatic instruments and communications. At the end of ...
  26. [26]
    [PDF] A Basic Guide to the HART Protocol - Texas Instruments
    The HART protocol uses the 4-20mA loop to send digital signals between a smart transmitter and a host for control, monitoring, or safety.
  27. [27]
    Signal Standards in Industrial Instrumentation: From Analog Loops ...
    The 4-20 mA current loop stands as the most enduring and widely implemented analog signaling standard in the history of industrial automation. Its elegant ...<|control11|><|separator|>
  28. [28]
    How Far Can a 4-20mA Signal Be Transmitted? - Just Measure it
    However, in optimized conditions with low resistance wires, higher supply voltage, and proper shielding, the signal can travel over 1,500 meters (4,921 feet).Missing: attenuation | Show results with:attenuation
  29. [29]
    Different Types of Analog Sensors & How To Choose One | Veris
    Oct 5, 2021 · Analog signal types remain the standby in process controls and industrial automation. Here's how to choose between 0 - 10V or 4 - 20mA ...Missing: comparison | Show results with:comparison
  30. [30]
    Why Industrial Automation Uses 4-20 mA Current Signals Instead of ...
    The 4-20 mA signal offers a better signal-to-noise ratio compared to voltage-based systems. Since current signals are less affected by electrical noise, the ...
  31. [31]
    Advantages and Disadvantages of Pneumatic Instruments - Inst Tools
    Jan 9, 2019 · One decided advantage is the intrinsic safety of pneumatic field instruments. Instruments that do not run on electricity cannot generate ...
  32. [32]
    Basics of Pneumatic Instruments - Overview | Textbook - Control.com
    Loop diagrams of pneumatic control systems documented each bulkhead fitting where an instrument signal ... Advantages and Disadvantages of Pneumatic Instruments.
  33. [33]
    [PDF] An End User Functional Comparison of HART® and FOUNDATION ...
    The main differences frequently cited are HART is a hybrid protocol compatible with the installed base of 4–20 mA instruments, while FOUNDATION fieldbus is ...
  34. [34]
    News - Article: The Hart Communication Protocol - NOVUS Automation
    Mar 26, 2019 · In point-to-point mode, a single loop of current is established communicating a HART device and the monitoring system. The primary variable ...
  35. [35]
  36. [36]
    Best practice in transmitting sensor analog signal over longer ...
    Jan 13, 2020 · I'm looking for best practices for transmitting an analog sensor signal over long distances to a microcontroller such as the Arduino running at 3.3v or 5v.Transmit digital signals over long distances using current (voltage to ...Will there be any effects on a signal in a long wire?More results from electronics.stackexchange.com
  37. [37]
    4-20 mA Process Control Loops - Inst Tools
    Mar 4, 2021 · 4-20 mA Process Control Loops used for carrying sensor ouput like flow, level, pressure and temperature. Also provides power supply to field ...
  38. [38]
    [PDF] Implementing a 4 mA to 20 mA Current Loop on TI DSPs
    Use of 4-mA to 20-mA (4−20 mA) current loops has become the standard in the process-control industry due to their increased resistance to noise compared to.
  39. [39]
    The Science of 4 to 20 mA Current Loops - Application Note - BAPI
    A 4 to 20mA current loop is a robust sensor signaling standard, emulating pneumatic signals, where current proportional to a measured parameter flows through ...
  40. [40]
    How to Select a 4-20mA Isolator - 8400850 | Acromag
    Bucking Power Supplies is when two or more devices want to supply the power to the 4 to 20 mA loop. If you insert an isolator that is passive on the input ...<|control11|><|separator|>
  41. [41]
    [PDF] Control Valve Sourcebook — Refining - Emerson Global
    This sourcebook helps understand refining processes, valve locations, and valve performance issues, and provides general guidelines for control valve ...
  42. [42]
    [PDF] Designing 4 to 20 mA Current Loops | BAPI
    1,600 feet of 22-gauge twisted pair wire is actually 3,200 feet long – 1,600 feet out and 1,600 feet back.Missing: distance | Show results with:distance
  43. [43]
    Current Loop voltage drop calculator - DIVIZE industrial automation
    Jan 6, 2022 · Current loop voltage drop calculator for calculating and verifying power supply in 4-20 mA current loop systems.
  44. [44]
    Designing 4 to 20 mA Current Loops - Application Note - BAPI
    This document describes how to manage the voltage drops in a 4 to 20 mA current loop, and how to determine the proper power supply voltage for the loop.
  45. [45]
    [PDF] Technical Bulletin PART I – ALL ABOUT 4-20mA CURRENT LOOPS
    As loop current increases, the wiring and receiving device voltage drops will increase so the transmitting device must decrease its voltage drop to compensate.
  46. [46]
    16 port / channel 4 - 20 mA Analogue Current to Fiber Optic ...
    This series of devices adopts large-scale FPGA design and adopts original technology to support 1~16 channels of analog signals (current/voltage) to fiber relay ...
  47. [47]
    8 Tips to reduce EMI effects on instrumentation signals
    Rating 4.0 (230) 4...20 mA signals are highly immune to electrical noise. Unlike voltage signals, 4-20 mA signals will not attenuate over a long distance, (within limits).Missing: capacitance | Show results with:capacitance<|control11|><|separator|>
  48. [48]
    [PDF] Why wireless?
    Pipeline monitoring covers long distances, multiple measurements and ... A wide range of sensor types are compatible, including 4 - 20mA, 1 - 5V, Modbus, HART,.
  49. [49]
    [PDF] DAC161S997 16-Bit SPI-Programmable DAC for 4-20 mA Loops
    0-24 mA Loop. +. -. LOOP. SUPPLY. LOOP. RECEIVER. S. P. I. 80k. IDAC. ƩΔ DAC. 16 ... Due to the stability considerations of the current control loop, the minimum ...
  50. [50]
    8-Channel Isolated 0-24 mA current sourcing D/A Board with Built-In ...
    Each DNxAO-318-024 channel provides an output range of 0-24 mA (sourcing) and is capable of up to 400 Ohms. For applications requiring a sinking output please ...
  51. [51]
    [PDF] REMOTE MOUNT SOLENOID DRIVER (4-20 mA Input Version)
    A current sensing circuit maintains output current regardless of changes in input voltage and coil resistance. The user can adjust maximum and minimum current.
  52. [52]
    SEM1636 Loop Powered, Dual Relay Output Signal Conditioner
    The SEM1636 monitors a (4 to 20) mA loop and provides two independent change over relay contacts set to trip at any point within the (4 to 20) mA range.
  53. [53]
    Understanding Discrete & Analog I/O - Library.Automationdirect.com
    Sep 15, 2014 · Usually there is a threshold for detection, where the 0-24VDC module will detect anything over 22VDC as the ON signal and anything below 2VDC as ...Missing: loop | Show results with:loop
  54. [54]
    BMXAMM0600 - analog non isolated high level IO module, Modicon ...
    0...24 mA 0...20 mA output 0...24 mA 4...20 mA output. Fallback mode ... * The current loop is self-powered by the output and does not request any ...
  55. [55]
    PLC Evaluation Board Simplifies Design of Industrial Process ...
    Output modules may have current outputs, voltage outputs, or a combination. A classical solution that uses discrete components to implement a 4 mA to 20 mA loop ...
  56. [56]
    UHF/VHF Data Telemetry/Scada Radio system
    SCADA / telemetry radios can be in licensed microwave wireless (UHF, VHF, 900MHz MAS, and with licensed WiMax 2.5GHz or with 700MHz LTE) or unlicensed wireless ...
  57. [57]
    Rugged 4-20 mA Spread Spectrum Modbus Radio Modem - Synetcom
    WISE 4-20 is a comprehensive line of industrial grade, frequency hopping spread spectrum and remote radio telemetry modems with unified I/O features for ...
  58. [58]
    Wireless 4-20mA Current Loop Output (CLO) - Raveon Technologies
    A 4-20 mA current loop is a very common method to convey the sensor data acquired for analog sensor data transmission.
  59. [59]
    I/O Enabled VHF/UHF Data Radio Modem - STI Engineering
    Features · I/O support (4 x Analogue 4-20mA, Digital 0-5V or Relay dry contact) · Frequency Range VHF (148 MHz – 174 MHz) & UHF (380MHz – 520MHz) · 5 Watt transmit ...
  60. [60]
    SCADALink SR900 SensorRadio – Wireless 4-20ma
    SCADALink SR900Wireless transmitter transmits a single 4-20mA signal and 2 Discrete signals to matching Sensor Radio Receiver at ranges up to 20+ Miles.
  61. [61]
    Your SCADA Project | Raveon Technologies
    The GPIO will mimic the sensor a long ways away to this modem with Current Loop Output CLO that will output the 4-20mA signal in.Missing: onto | Show results with:onto
  62. [62]
    [PDF] MOTOTRBO XPR 7550/XPR 7580 Color Display Portable User Guide
    Class B Digital Device. As a personal computer peripheral, this device complies with Part 15 of the FCC Rules. This device complies with.
  63. [63]
    Low Latency Radio System Design Considerations - EE Times
    Jan 20, 2021 · Designing radios for latency sensitive applications can be a challenge and there are many design trade-offs that need to be considered.Missing: 20mA | Show results with:20mA
  64. [64]
    SCADALink RIO900 Wireless I/O Telemetry Radio
    With current draw of < 0.5W (20 ma at 24VDC and 40 ma at 12VDC) in RX mode the RIO900 has some of lowest power draws for SCADA radios. The RIO900 combined ...Missing: way | Show results with:way
  65. [65]
    Industrial IoT Long Range Wireless 4-20mA Current Loop Receiver
    $$274.95 to $306.95This Industrial IoT Wireless 4-20mA Current Loop Receiver is powered by just 4 AA batteries and an operational lifetime of 500,000 wireless transmissions, a 10 ...Missing: portable radios