Double check valve

A double check valve, also known as a double check valve assembly (DCVA), is a mechanical consisting of two independently acting, spring-loaded s arranged in series within a single body, designed to protect potable supplies from by non-toxic substances through the prevention of reverse flow. Each operates on a , remaining open during normal forward flow but closing automatically when downstream drops below upstream by as little as 1 , providing redundant protection if one fails. The assembly typically includes four test cocks for field testing and verification of functionality, along with shutoff s for isolation during maintenance. Double check valves function primarily in low-hazard applications where back siphonage or could introduce contaminants like , chemicals, or system into the clean supply, but they are not suitable for high-hazard toxic substances, for which reduced pressure zone (RPZ) assemblies are required instead. They are constructed from durable materials such as , , or to withstand pressures up to 175 psi and temperatures from 33°F to 180°F, ensuring reliability in various systems. occurs above ground or in accessible vaults, typically on the discharge side of the meter or at points of use, and requires annual testing by certified personnel to confirm tight shutoff and no leakage. Compliance with standards like 1015 for performance requirements, AWWA C510 for material and design specifications, and approval by the (USC) Foundation for Cross-Connection Control and Hydraulic Research ensures their effectiveness and regulatory acceptance. Common applications include commercial and industrial settings such as irrigation systems, fire protection lines, boilers, food and beverage processing, chemical plants, and (HVAC) systems, where protection of the public is essential without the need for atmospheric venting. These devices play a critical role in cross-connection control programs mandated by plumbing codes and regulations, contributing to overall water safety and quality.

Overview and Purpose

Definition

A double check valve assembly is a mechanical composed of two single, independently acting s arranged in series, including tightly closing shutoff valves at each end and suitable connections, such as test cocks, for verifying the watertightness of each . These assemblies conform to standards like ASSE 1015 or AWWA C510 and are designed to operate under continuous pressure conditions in potable water systems. The s are typically spring-loaded to ensure reliable closure and promote water tightness. Backflow refers to the unintended reverse flow of or other liquids, mixtures, or substances into the distributing pipes of a public system from any source other than its intended source, caused by pressure differentials such as backpressure (higher downstream pressure) or backsiphonage (sudden drop in supply pressure creating a effect). This phenomenon can introduce contaminants from private systems, like irrigation with fertilizers or industrial effluents, into clean potable supplies, posing risks to . The core function of a double check valve assembly is to protect public water systems from by maintaining unidirectional flow and preventing reverse flow due to backpressure or backsiphonage. Unlike a single , which lacks redundancy and can fail due to debris, wear, or without backup protection, the dual-valve configuration ensures that if one malfunctions, the second provides continued safeguarding, making it suitable for applications requiring reliable protection against low-hazard scenarios where higher reliability is essential.

Importance in Water Safety

Double check valves play a pivotal role in safeguarding by preventing contamination in distribution systems, where reverse flow can introduce harmful substances into potable supplies. Backflow occurs through mechanisms such as backpressure or backsiphonage, allowing pathogens, chemicals, or to infiltrate clean lines, potentially leading to widespread illness. Such events underscore the valve's function in creating a physical barrier that isolates potential contaminants, ensuring that remains free from biological hazards like and viruses that could cause outbreaks of diseases such as or E. coli infections. In protecting public health infrastructure, double check valves are essential for maintaining the integrity of potable in both residential buildings and municipal networks, where they serve as a critical line of defense against cross-connections between safe and unsafe water sources. By automatically shutting off flow during reversals, these devices help comply with standards set by organizations like the (AWWA), which recommend their use in low-hazard applications to protect against non-toxic contaminants entering potable water systems. This protection extends to large-scale urban supplies, where failure could affect millions; for example, the valves ensure that irrigation systems or fire suppression lines do not compromise the overall in cities with extensive networks. Their deployment in buildings and municipalities thus upholds the of , reducing the risk of long-term exposure to toxins like pesticides or industrial effluents that might otherwise enter household taps. Failure to install or maintain double check valves can result in severe legal and economic repercussions, including regulatory fines, operational shutdowns, and liability for health-related lawsuits. Under the U.S. , non-compliance with backflow prevention requirements can lead to penalties exceeding $50,000 per violation, as enforced by the Agency (EPA), compelling utilities and property owners to prioritize these devices to avoid costly remediation. Economically, a single contamination event might incur expenses for flushing, public notifications, and medical monitoring, as seen in various municipal cases where backflow incidents have led to multimillion-dollar settlements. These consequences highlight the valves' importance not only for health but also for ensuring fiscal responsibility in water management.

Design and Operation

Components

A double check valve primarily consists of two independently operating, spring-loaded check valves arranged in series within a single body, which provide redundant protection against . These check valves are typically of the or type, where the design features a piston-like element that lifts against tension during forward flow, while types use a tilting or dual-disc mechanism for similar function. Positioned upstream and downstream of the check valves are two tightly closing, resilient-seated shutoff valves, often configured as or valves to allow isolation of for without depressurizing the . Additionally, four cocks—small valved ports—are integrated into , typically positioned with one between the inlet shutoff valve and the first , one between the two , one between the second and the outlet shutoff valve, and a fourth for measuring supply or additional diagnostics, enabling pressure differential measurements to verify functionality. The assembly is constructed from materials selected for durability and in systems, with common choices including lead-free bronze or for the body and internals, for springs and fasteners, and sometimes with coating for larger sizes. or reinforced components may be used in non-wetted parts for cost efficiency and UV . Optional features can enhance usability and monitoring, such as replaceable seats in the check valves for extended , quarter-turn ball valves for quicker shutoff operation, and integrated pressure gauge ports or accessories for real-time system diagnostics.

Working Mechanism

In normal forward conditions, the upstream water overcomes the spring-loaded resistance of the first , causing it to open and allow water into the intermediate chamber between the two valves. This pressurizes the chamber, which in turn overcomes the spring force on the second , opening it to permit unrestricted downstream while modulating to match demand and minimize head loss, typically resulting in a of 2-5 across the assembly. Each is spring-loaded with a minimum closing of 1 to ensure closure even under minimal reverse . When backpressure occurs—such as from a downstream exceeding upstream levels—the higher acts directly on the downstream side of the second , causing it to close first and seal against reverse flow. If the increases or the second is compromised, the first closes as well, establishing a robust double barrier that prevents without relying on a . The design also protects against backsiphonage, where a sudden drop in downstream causes both check valves to close automatically due to the spring tension and . The design provides inherent redundancy, as both independently operating check valves must fail for to occur; for instance, if lodges in one valve causing it to stick open, the other maintains the . This configuration ensures continued protection in non-health hazard scenarios, relying solely on the mechanical action of the check valves rather than additional venting.

Types and Variations

Standard Double Check Assembly

The standard double check (DCA), also known as a double check valve (DCVA), is a full-sized designed for permanent installation in lines to protect against from non-health contaminants. It consists of two independently acting, spring-loaded, resilient-seated check valves arranged in series, which provide redundant protection by ensuring that if one valve fails, the other maintains closure to prevent reverse flow. The also includes two tightly closing shutoff valves (such as quarter-turn valves for smaller sizes or OS&Y valves for larger sizes) for isolation, and four cocks (ports) strategically placed for field ing of each check valve's performance without disassembling the unit. These components are housed in a compact, lead-free or body, with the check valves featuring captured spring cartridges and elastomers resistant to chloramine for durability in treated systems. DCAs are available in sizes ranging from 3/4 inch to 10 inches in , accommodating various configurations and rates up to several hundred gallons per minute, depending on the model. They are particularly suited for high- applications requiring continuous operation and regular verification, such as systems, large-scale networks, and commercial water services like pools or processing tanks, where backpressure or backsiphonage could introduce pollutants like or chemicals but not toxic substances. A key advantage of the standard DCA is its ability to undergo in-line testing using pressure gauges connected to the test ports, allowing certified testers to verify integrity and tightness without shutting down the water supply, thus minimizing service disruptions. Additionally, these assemblies are certified under standards like ASSE 1015, , IAPMO, and AWWA C510 for protection against non-health hazard , ensuring compliance in low-risk scenarios while maintaining low pressure loss (typically under 10 ) for efficient system performance.

Dual Check Valve

A dual check valve is a compact, inline featuring two independently acting, spring-loaded s arranged in series within a single housing, engineered to safeguard potable supplies against from backpressure or backsiphonage in low-hazard scenarios. This design ensures that if one fails, the second provides continued protection, maintaining unidirectional flow without the need for additional atmospheric venting in most configurations. Certified to Standard 1024, these valves are optimized for residential and point-of-use applications where space and simplicity are priorities. In contrast to the standard double check assembly, the dual check valve lacks integrated shutoff valves and test cocks, rendering it non-testable in the field and ideal for confined setups. It is manufactured in smaller diameters, typically ranging from 1/4 inch to 1 inch, to accommodate low-volume lines, and frequently incorporates resilient seats—such as —for reliable sealing under intermittent flow conditions. These characteristics make dual check valves a common choice for integration into household appliances like washing machines, where they prevent potential reverse flow from drain lines into the water supply. The primary limitations of dual check valves stem from their simplified construction, which precludes on-site performance and restricts their deployment to non-critical, low-hazard environments without mandatory testing requirements. While the series configuration offers inherent , the absence of verification ports means reliability depends on manufacturer and scheduled replacements rather than routine inspections, making them unsuitable for high-hazard services or installations demanding with testable standards.

Applications

Residential and Commercial Plumbing

In residential systems, double check valves are commonly installed at the service line to safeguard potable water supplies from backsiphonage hazards associated with specific fixtures and appliances. For homes equipped with boilers, the mandates protection of potable water connections to steam or hot water boilers using a double check valve backflow prevention assembly to prevent reverse flow of potentially contaminated . Similarly, these assemblies are standard for lawn irrigation systems, where they block the of fertilizers, pesticides, or soil-laden water into the main supply during pressure drops or siphonage events. In setups involving pressure washers connected to service lines, double check valves provide essential protection against backsiphonage from chemical detergents or , ensuring compliance with backflow prevention requirements for hose-end applications. Commercial applications extend these protections to larger-scale building systems, where valves mitigate cross-connection risks in low- to medium-hazard environments. In office and hotels, they are deployed to isolate non-potable uses such as lines or elevated storage tanks, preventing backpressure or backsiphonage that could introduce pollutants into the potable distribution. Restaurants and similar establishments utilize these valves to guard against from dishwashers or equipment, where residual cleaning agents might reverse into the supply under fluctuating pressures. For cooling towers in commercial HVAC systems, assemblies are applied in closed-loop makeup lines to block non-health hazard contaminants, aligning with standards for continuous pressure operations. Sizing and placement of double check valves in residential and commercial settings prioritize , , and code adherence. Residential installations typically use 3/4-inch to 2-inch diameters to match standard service line sizes, ensuring minimal pressure loss while handling typical household demands. These devices are positioned above ground, immediately downstream of the water meter on the private side, in a orientation, with the centerline at least 12 inches above the floor or grade and no higher than 5 feet, to ensure for testing and maintenance while complying with local codes.

Industrial and Municipal Uses

In industrial settings, double check valve assemblies are essential for preventing backflow in processes involving non-health hazard fluids, such as in chemical mixing operations where they isolate tanks and vats to protect potable supplies from . In facilities, these valves are commonly installed in cookers and processing lines to ensure that process does not reverse into the main supply, maintaining and operational integrity. Additionally, in HVAC systems, double check valves facilitate continuous applications by isolating non-potable cooling loops, preventing potential cross-contamination in large-scale environments. For municipal applications, double check valve assemblies safeguard distribution networks by protecting mains from during interconnections with services, ensuring the integrity of potable supplies. They are frequently used in systems connected to hydrants to block reverse flow of non-potable into the distribution system, supporting reliable emergency response without compromising . High-flow double check valve assemblies, available in sizes up to 12 inches, are particularly suited for municipal distribution systems, handling pressures up to 175 psi to accommodate large-volume flows in infrastructure. This scalability ensures effective prevention in high-demand scenarios, such as expansions or tie-ins to networks.

Installation and Maintenance

Installation Guidelines

Proper installation of a double check valve is essential to ensure effective prevention, accessibility for , and compliance with codes. The should be located upstream of any potential sources, such as systems or commercial equipment, to protect the potable . prioritizes horizontal orientation unless the device is specifically listed or approved for vertical , with the bottom of the positioned at least 12 inches above the floor or level to prevent submersion and allow for . Adequate clearance of 12 inches from walls, ceilings, or other obstacles must be provided on all sides to facilitate testing and servicing, while avoiding dead-end lines where stagnation could compromise performance. The location must be readily accessible, indoors if possible to protect against freezing, and in a well-ventilated area away from excessive heat sources. Piping requirements include thorough flushing of upstream lines to remove before , followed by the addition of a strainer immediately ahead of the assembly to protect the , except on lines like fire sprinklers. Unions or flanges should be incorporated at the inlet and outlet connections to enable easy removal for , and the arrow on the body must align precisely with the actual to ensure proper . Shutoff valves are required upstream and downstream to isolate the assembly during servicing. Common installation errors include undersizing the , which can result in excessive drops exceeding 5 and reduced flow rates, and placing the assembly in a vertical orientation without local authority approval, potentially leading to improper seating of the check valves. Additionally, failing to account for or in the piping can damage the assembly over time.

Testing and Maintenance Procedures

Testing of double check valves is typically conducted annually to ensure proper functionality and compliance with backflow prevention standards. The procedure involves using a differential pressure gauge connected to the assembly's test cocks to verify the tightness of both the No. 1 and No. 2 check valves. With the downstream side isolated and at , the gauge measures the pressure differential across each valve; both checks must hold a minimum of 1.0 without leakage to pass. Only certified backflow prevention assembly testers, licensed by relevant authorities such as state departments, are permitted to perform these tests, ensuring accurate results and adherence to protocols like those in AWWA C510. Maintenance routines focus on preventing accumulation and wear that could impair performance. Periodic disassembly is recommended to clean internal components, such as the modules and seating surfaces, by flushing with clean and inspecting for or foreign matter. and o-rings should be replaced every 5-10 years or upon signs of deterioration, using manufacturer-approved repair to restore sealing integrity. For below-grade installations, is essential to protect against freezing; this includes draining the assembly by opening test cocks and shutoff , insulating the enclosure, or using heat tape to maintain temperatures above 32°F. Test and maintenance records must be meticulously documented, including dates, results, tester certifications, and any repairs performed. Standards require retention of these records for at least 5 years to facilitate audits and demonstrate ongoing compliance with regulatory requirements. Failure to maintain proper records can result in non-compliance penalties, underscoring the importance of systematic logging by property owners or designated personnel.

Standards and Regulations

Certification Standards

Double check backflow prevention assemblies are certified to meet rigorous technical standards that ensure their structural integrity, hydraulic efficiency, and effectiveness in safeguarding potable water supplies. The American Water Works Association (AWWA) Standard C510 specifies requirements for materials, such as corrosion-resistant components suitable for hot and cold water applications, as well as hydraulic performance criteria, including the capacity to operate without damage under a minimum working pressure of 150 psi (1,034 kPa). This standard mandates testing for flow characteristics to minimize head loss while maintaining tight shutoff against reverse flow. Complementing AWWA C510, the American Society of Sanitary Engineering (ASSE) Standard 1015 outlines performance requirements and testing protocols specifically for double check backflow prevention assemblies, emphasizing protection against both backpressure and backsiphonage in continuous or intermittent pressure conditions. These protocols include field-simulated tests to verify that the two independently acting check valves, along with shutoff valves and test cocks, function reliably without allowing contaminants into the water system. The certification process entails validation by third-party laboratories accredited by organizations like , which conduct comprehensive evaluations to confirm adherence to these standards. Assemblies must demonstrate pressure ratings typically ranging from 150 to 300 , depending on and application, to handle common municipal and pressures without . Flow coefficients (Cv values) are assessed to ensure efficient throughput, often exceeding 100 for larger sizes, while endurance testing verifies durability under varying pressures as required by the standards. Key performance metrics focus on backflow containment, requiring each to hold a minimum differential with no measurable leakage during hydrostatic and dynamic tests, effectively reducing reverse flow to negligible levels under simulated conditions. This ensures the assembly's reliability in and municipal settings where certified devices are mandated for cross-connection .

Regulatory Requirements

In the United States, the Environmental Protection Agency (EPA) recommends double check valve assemblies (DCAs) for backflow prevention in low- to moderate-hazard cross-connections, such as those in systems, lines, or feeds involving non-toxic substances, to safeguard potable water under the . State and local plumbing codes, which often adopt the (UPC) or International Plumbing Code (IPC), mandate DCAs specifically for moderate-hazard applications where backpressure or backsiphonage could introduce contaminants without posing immediate health risks. These codes require installation downstream of the water meter for applicable services, with enforcement varying by jurisdiction but consistently emphasizing protection against non-health hazards. Annual testing of DCAs is a standard requirement across most U.S. plumbing codes to verify the integrity of both check valves and shut-off mechanisms, typically conducted by certified testers using differential pressure gauges under no-flow conditions. The UPC, for instance, specifies testing procedures in Section 603.4.2 to ensure compliance, with records maintained by property owners and submitted to water utilities. Failure to test annually can result in service disconnection, underscoring the regulatory focus on ongoing reliability. Internationally, regulatory frameworks for double check valves mirror U.S. approaches but are implemented through national or regional standards. In the , under the (Water Fittings) Regulations 1999, double check valves are mandated for fluid category 3 risks (moderate potential, such as from agents), requiring WRAS approval to confirm performance against and backsiphonage. Similarly, in the and parts of the , KIWA certification under BRL-K629 governs double check valves for fluid class 2 (low to moderate hazards), ensuring they meet EN 13959 standards for safety. However, these devices are banned in high-hazard scenarios (fluid class 4 or category 4/5), where reduced pressure zone assemblies are required instead to prevent any risk of toxic . Compliance variations exist globally, including in some U.S. jurisdictions where permits are required for DCA installations exceeding 2 inches in diameter to ensure proper sizing, clearance, and integration with building plumbing systems. Local authorities, such as those in , enforce these through plumbing trade permits, often mandating pre-installation approvals for larger assemblies to align with site-specific hazard assessments.

History

Early Development

The concept of the double check valve emerged in the early as a response to the limitations of single check valves in preventing , with initial designs incorporating two check valves for added dating back to around 1906. These early configurations aimed to address risks in systems, where reverse flow could introduce into potable supplies due to changes or siphonic action. By the and , post-World War I heightened awareness of cross-connections in expanding municipal networks, prompting further innovation in backflow prevention. Development accelerated in the United States during the 1930s, particularly in , where engineers began creating rudimentary backflow preventers featuring dual check valve arrangements to provide layered protection against non-health-hazardous contamination. These devices evolved from earlier single-valve attempts, which had proven unreliable, and were influenced by growing concerns over urban . Patents and prototypes from this era focused on simple inline dual-valve setups integrated into service lines, marking the foundational shift toward standardized backflow arrestors. Initial designs suffered from several limitations, including the absence of spring-assisted mechanisms, which relied instead on or basic weights for valve closure, leading to frequent sticking in low-flow scenarios. Metal-to-metal seating in these early models was prone to and debris buildup, compromising tight seals and necessitating frequent manual inspections. Soft seating materials, such as , were introduced around 1906 but remained rudimentary in implementations, often failing under variable pressures common in nascent urban systems.

Key Milestones

In the 1950s, the double check valve emerged as the primary for non-health hazard applications, incorporating spring-loaded check valves for reliable operation under varying pressures and receiving formal endorsement through the (USC) Foundation for Cross-Connection Control and Hydraulic Research, which granted its first approval to a double check valve model in October 1948. These advancements addressed earlier limitations in valve responsiveness and durability, facilitating widespread adoption in and municipal water systems. During the 1970s and 1980s, significant enhancements included the integration of test cocks for field verification of valve tightness and resilient (rubber or ) seats to improve sealing against and , as standardized in the American Society of Sanitary Engineering () 1015 performance requirements published in 1974. These modifications were driven by growing recognition of risks, exemplified by incidents such as the 1970 chemical contamination at in , where a cross-connection led to entering the potable supply and causing illness. From the 2000s onward, double check valves underwent material upgrades to meet stricter health standards, particularly the lead-free requirements under revisions to the (SDWA) effective January 4, 2014, which limited lead content in wetted surfaces of plumbing products to a weighted average of 0.25 percent. Manufacturers responded by transitioning to alloys like dezincification-resistant and NSF/ANSI 372-certified components, ensuring compliance while maintaining performance in potable water applications. Standards continued to evolve, with the latest revision of ASSE 1015 occurring in 2021.

Comparisons with Other Devices

Versus Single Check Valves

A single check valve consists of one internal mechanism that permits fluid flow in one direction while preventing reverse flow, making it suitable for low-risk applications such as discharge lines where could cause inefficiency or minor flooding but poses no threat to potable water supplies. These devices are prone to failure from lodging in the valve seat, which can allow unintended if the sole barrier is compromised. In contrast, a double check valve incorporates two check valves in series, providing a redundant barrier that significantly lowers the overall risk of occurrence. A 1993 field study reported a test of approximately 1.6% for double check valve assemblies, compared to an estimated 4% for single check valves, effectively reducing the probability of complete failure to levels below 0.1% assuming operation of each valve. However, more recent data indicate higher failure rates, such as 10-15% after one year in some systems and up to 42.5% in 2021 residential tests, varying by device age, location, and . This dual design is particularly advantageous for moderate-hazard scenarios, such as commercial irrigation systems or lines handling non-toxic contaminants, where regulations mandate higher reliability to protect public water systems from potential pollution. Despite these benefits, double check valves introduce drawbacks relative to their counterparts, including higher initial costs due to the added complexity and materials, and greater loss across the assembly. Double check valves typically exhibit higher pressure drops than single check valves under normal operating flows, which can impact system efficiency in high-flow applications.

Versus Reduced Pressure Zone Assemblies

A reduced pressure zone (RPZ) assembly provides enhanced backflow protection compared to a double check valve by incorporating two independently operating check valves along with a hydraulically dependent situated between them. This activates to discharge water to the atmosphere should the in the intermediate zone fall to or below atmospheric levels, effectively preventing the entry of contaminated water into the potable supply during scenarios like or . In contrast, a valve lacks this relief mechanism, relying solely on the dual check valves to block reverse flow; if both checks fail under high-hazard conditions—such as exposure to , chemicals, or effluents—contaminated water could potentially infiltrate the system without detection or automatic . This limitation renders double check valves unsuitable for toxic risks, where the absence of a venting capability increases vulnerability, although they remain effective for containing non-toxic pollutants. Selection between the two depends on the hazard level of the application: valves are appropriate for low- to moderate-risk, non-health-threatening uses like systems or residential services without chemical additives, with simpler maintenance requirements. RPZ assemblies require installation at least 12 inches above ground to allow drainage and are essential for high- environments such as commercial facilities, hospitals, or sites handling pesticides to comply with standards against severe .

References

  1. [1]
    What Is a Double Check Valve: Understanding Its Importance
    Aug 30, 2024 · A double check valve is a kind of backflow prevention device that avoids polluted water from flowing back to clean water supply.Missing: definition engineering
  2. [2]
  3. [3]
    Products Compliant to ASSE Standards - Watts
    Watts products compliant with ASSE standards include vacuum breakers, water pressure reducing valves, dual checks, backflow preventers, and double check valve ...
  4. [4]
    AWWA C510-17(R21) Double Check Valve Backflow Prevention ...
    The purpose of this standard is to provide the minimum requirements for double check-valve backflow prevention assemblies for potable water applications, ...
  5. [5]
    USC List of Approved Backflow Prevention Assemblies
    Each approved backflow prevention assembly is listed by the type of assembly, manufacturer's name, model, size, edition of the manual under which the assembly ...
  6. [6]
    Product Standards - ASSE International
    These devices shall consist of two independently acting check valves biased to a normally closed position. An atmospheric port shall be located between the ...
  7. [7]
    Rule 3745-95-01 - Ohio Administrative Code | Ohio Laws
    (2) "Double check valve assembly" means an assembly composed of two single, independently acting, check valves including tightly closing shutoff valves located ...
  8. [8]
  9. [9]
    [PDF] Potential Contamination Due to Cross-Connections and Backflow ...
    Sep 27, 2001 · Backflow prevention assemblies include pressure vacuum breakers (PVBs), spill resistant vacuum breakers (SVBs), double check valve assemblies ( ...
  10. [10]
    Backflow Preventer vs. Check Valve: What's the Difference? - QRFS
    Apr 28, 2020 · Two main types of backflow preventers are utilized in fire protection systems. Double Check Valve (DCV) backflow preventers are common in ...
  11. [11]
    Double Check Valve Assemblies - Watts
    Stainless Steel Double Check Valve Backflow Preventer Assembly, Post Indicator Valve x OSY Shutoff Valve. Ames Fire & Waterworks. 2000SS.007 · LF007 · LF709 · 757
  12. [12]
    AWWA C510-17(R21) Double Check Valve Backflow Prevention ...
    This standard describes the double check-valve backflow prevention assembly for potable water applications. The assembly shall be capable of withstanding a ...Missing: definition | Show results with:definition
  13. [13]
    Types of Check Valves and Their Industrial Applications
    Jun 1, 2025 · Dual disc check valves are fast acting, self-actuating check valves designed with two centrally pivoted, semi-circular discs. The valves are ...
  14. [14]
    Watts LF007 Series 1" Lead-Free Bronze Double Check Valve ...
    30-day returns1" Lead-Free Bronze Double Check Valve Backflow Preventer Assembly, Quarter Turn Shutoff, Single Top Entry, NPT Connections, Modular Design
  15. [15]
    Febco® 6" LF850 Double Check Valve Assembly - Brooks Equipment
    Known as the Master Series, the LF850 is an epoxy coated, ductile iron body with bronze check assemblies. Two cover design with replaceable seats. No special ...
  16. [16]
    FAQ - Backflow Prevention Assemblies: How They Work - BAVCO
    The PVB consists of an inlet and outlet shut off, two test cocks, a check valve, and an air inlet component. The normal flow of water goes from the upstream ...
  17. [17]
  18. [18]
    The Double Check Valve Device Assembly – Rate of Flow and ...
    Jul 2, 2019 · According to the Flow Rate Chart, a 3-inch DCVA in a static state with a 0 GPM flow rate will have a pressure loss of approximately 4.0 PSI.
  19. [19]
    How Dual Check Valves Work: Residential Backflow Prevention Guide
    A dual check valve works by using two separate check valves in series that only allow water to flow in one direction, preventing contaminated water from flowing ...
  20. [20]
    Backflow Preventer Types - NFPA
    Oct 28, 2022 · A double check valve detector assembly is the same as a DCVA, but it also includes a bypass for the installation of a water meter to monitor for ...
  21. [21]
    DC vs RPZ Backflow Preventers | The Key Differences - Safe-T-Cover
    Nov 17, 2023 · A designer may specify one of 2 types of backflow prevention devices. First, the Double-Check Valve Assembly. This is often shortened to DC ...
  22. [22]
    [PDF] 2” Double Check Valve (DC) Backflow Preventer DC4A | DCLF4A
    The Double Check Valve (DC) device consists of two independently-acting, spring-loaded check valves. Two resilient seated shut-off valves and four test cocks ...
  23. [23]
    LF719QTS 3/4 - Watts
    ... ball valves with tee handles, NPT end connections, lead free bronze strainer, screw driver slotted test cocks ... Double Check Valve Assembly. Body Finish ...Missing: resilient | Show results with:resilient
  24. [24]
    Apollo 1 1/4" 4A Series Double Check Valve Assembly
    In stock Free deliveryApollo 1 1/4" 4A Series Double Check Valve Assembly. SKU: 4ALF ... Apollo ball valves w/ SS handles & nuts standard; Top-mounted test cocks for easy testing ...
  25. [25]
  26. [26]
  27. [27]
    [PDF] dam-12-cccp-student-guide.pdf
    Feb 23, 2017 · A double check valve assembly (DC/DCA/DCVA) is two single check valves coupled within one body and furnished with four test cocks and two ...
  28. [28]
  29. [29]
  30. [30]
    [PDF] Backflow Prevention and Cross-Connection Control - Ohio.gov
    The double check valve assembly is very useful, and when properly maintained, reliable means for backflow protection from aesthetically objectionable or ...
  31. [31]
    ASSE Standard 1024-2017: Dual Check Backflow Preventers
    A dual check backflow preventer is an apparatus used to keep water potable. It has two independently acting check valves.Missing: definition | Show results with:definition
  32. [32]
  33. [33]
    [PDF] Dual Check Valve (DuC) Backflow Device - City of Fort Walton Beach
    May 5, 2014 · The Dual Check Valve backflow preventer device is a mechanical device designed to prevent backflow into the residen al water system, it consists ...Missing: definition | Show results with:definition
  34. [34]
    2018 to 2021 Uniform Plumbing Code Changes, Part 3 | phcppros
    Apr 2, 2021 · Potable water connections to steam or hot water boilers shall be protected from backflow by a double check valve backflow prevention assembly, ...
  35. [35]
    How to choose and install a backflow prevention assembly
    The double check valve assembly (DCVA) is commonly used to protect against backflow hazards that do not pose a health risk. They may be used under continuous ...Missing: mechanism | Show results with:mechanism
  36. [36]
    The Importance of Backflow Preventers for Restaurants
    Aug 1, 2022 · Double Check Valves (DCVs): Suitable for low to medium-hazard situations, like fire suppression systems. Reduced Pressure Zone (RPZ) devices ...<|control11|><|separator|>
  37. [37]
    makeup water system connected to water supply for closed chiller ...
    Aug 22, 2014 · To prevent back flow I have been going through some document on the internet, but I noticed that there is a requirement for a double check valve ...
  38. [38]
    [PDF] Series 007 Double Check Valve Assembly 1⁄2 - Watts
    • Low pressure drop. • No special tools required for servicing. • Tee ... Maximum Working Pressure: 175 psi (12.1 bar). Standards. ASSE Std. 1015, AWWA ...Missing: mechanism | Show results with:mechanism<|control11|><|separator|>
  39. [39]
    How deep to install double check valve assembly
    Sep 27, 2019 · In most, if not all, cases any "safety device" with an open vent, which your double check may have, must be installed at least 12"ABOVE the ground.
  40. [40]
    The role of check valves in water lines - Hawle
    For example, in a water treatment plant, check valves prevent treated water from flowing back into the untreated water reservoir. Preventing drainage. When ...
  41. [41]
  42. [42]
    774-DOSY 12 - Backflow Preventers - Watts
    This 12 inch lead free double check valve backflow preventer assembly is designed to prevent the reverse flow of contaminated water of non-potable quality.
  43. [43]
  44. [44]
    Guidelines for Designing Backflow Prevention Assembly Installations
    These guidelines reflect accepted design considerations based on experience in implementing cross connection control programs and policies.
  45. [45]
    Double Check Valve Backflow Prevention Assembly - UpCodes
    A double check valve backflow prevention assembly shall be installed as follows: The assembly shall be installed in a horizontal position only.Missing: uniform applications
  46. [46]
    [PDF] Model 350, 350A (R), 350DA & 350ADA (R) Model 450 - Zurn
    Before installing a Model 350/450 Series Backflow Preventer, flush the line thor- oughly to remove all debris, chips and other foreign matter.<|control11|><|separator|>
  47. [47]
    [PDF] Installation, Operation, Maintenance and Parts Manual for Backflow ...
    Series 2000DCA (Double Check Valve Assembly) is used to prevent backflow of aesthetically objectionable but not toxic contaminants into the main water supply.Missing: manufacturer | Show results with:manufacturer
  48. [48]
    [PDF] Installation, Maintenance, & Repair Series 2000B/LF2000B - Watts
    Pipe lines should be thoroughly flushed to remove foreign material before installing the unit. A strainer should be installed as shown, ahead of backflow ...
  49. [49]
    [PDF] INSTALLATION, OPERATION & MAINTENANCE MANUAL Double ...
    II. INSTALLATION. 1. The DCV must be installed in an accessible location to facilitate periodic field testing and maintenance.
  50. [50]
    [PDF] Test Procedures for Double Check Valve and ... - American Backflow
    [AWWA C510 Sec. 4.3.2.1]. Test Objective, Method and Reporting Requirements: To test check valve #1 and check valve #2 for tightness in the direction of flow ...
  51. [51]
    [PDF] Test Procedure for Double Check Valve Assembly
    Test involves measuring static pressure drop across each check valve using a differential pressure gauge. The pressure drop must be 1.0 psid or greater.
  52. [52]
    Certified Backflow Testers - New York State Department of Health
    Below is a current list of New York State certified backflow prevention device testers by county. For more information on contacting any of these individuals, ...
  53. [53]
    [PDF] MAINTENANCE MANUAL INDEX DOUBLE CHECK ASSEMBLIES ...
    After draining procedure has been completed on the backflow prevention assembly, position all ball valve shut-offs and test cocks in a half open/half closed. ( ...
  54. [54]
    Backflow Freeze Protection | Essential Guide - Safe-T-Cover
    Made of metal and often installed below-grade, DCVs can crack or malfunction if water is left inside the assembly during a freeze. DC-v-RPZ. Reduced Pressure ...
  55. [55]
    [PDF] 2015 International Plumbing Code (amended) Backflow/Cross ...
    In addition, all records shall be kept by the owner of the backflow prevention device or method for at least 5 years and, upon specific request, shall be made ...Missing: retention period<|control11|><|separator|>
  56. [56]
    Best Practices for Maintaining Backflow Compliance Records
    Most places want you to keep backflow test reports, repair invoices, and maintenance records for at least 3 to 5 years. Sometimes it's longer, depending on your ...
  57. [57]
    C510-97: AWWA Standard for Double Check Valve Backflow ...
    This standard covers hot and cold water double check valve backflow prevention assemblies. All assemblies shall be designed to operate at a minimum temperature ...
  58. [58]
    ASSE Standard #1015-2021 - ASSE International Webstore
    $$45.00The purpose of Double Check Backflow Prevention Assemblies (DC) is to keep polluted water from flowing into a potable water distribution system.
  59. [59]
  60. [60]
    [PDF] Backflow Prevention Products - Emco Waterworks
    Backflow prevention products include double check valve assemblies, double check detector assemblies, reduced pressure zone assemblies, reduced pressure ...
  61. [61]
    [PDF] Field Test Procedure for ASSE 1015 (DC) Assemblies Using 5-Valve ...
    Test Results: Record gauge value. If differential reading holds steady at 1 psid or higher, record #2 check valve as tight.
  62. [62]
    P2902.3.6 Double-Check Backflow Prevention Assemblies - UpCodes
    Double-check backflow prevention assemblies shall conform to ASSE 1015, AWWA C510, CSA B64.5 or CSA B64.5.1. Double-check detector fire protection backflow ...<|control11|><|separator|>
  63. [63]
    [PDF] Cross-Connection Control Manual, February 2003
    Maximum protection is achieved against backsiphonage and backpressure conditions utilizing reduced pressure principle backflow preventers. These devices are ...
  64. [64]
    2021 Uniform Plumbing Code - IAPMO
    3 Hose Connection Backflow Preventer. 603.3.4 Double Check Valve Backflow Prevention Assembly (DC). 603.3.5 Pressure Vacuum Breaker Backflow Prevention ...
  65. [65]
    CHAPTER 6 WATER SUPPLY AND DISTRIBUTION
    Dual check backflow preventers shall conform to ASSE 1024 or CSA B64.6.<|control11|><|separator|>
  66. [66]
    Cross-Connection Control and Backflow Prevention
    Sep 10, 2025 · Information for public water systems and their customers on identifying potential cross connections and preventing contamination from backflow into drinking- ...
  67. [67]
    Commercial Backflow Testing: Your Annual Compliance Checklist
    A certified technician performs these tests by checking the backflow prevention device's valves and pressure levels. The process needs to happen every year ...
  68. [68]
    Double check valves - Water Regs UK Limited
    A double check valve is rated by the Regulators as suitable backflow protection against both back siphonage and back pressure for contamination risks no greater ...Missing: EU WRAS KIWA
  69. [69]
    Kiwa Watermark Certification and Testing for Backflow Prevention ...
    Kiwa Watermark prevents pollution by backflow, ensuring compliance with Dutch and international standards for drinking water distribution. It is important for ...Missing: WRAS | Show results with:WRAS
  70. [70]
    § 51.116 Installation Guidelines and Requirements for Backflow ...
    All assemblies larger than two (2) inches shall have a minimum of twelve (12) inches on the backside, twenty-four (24) inches on the test cock side, and the ...
  71. [71]
    Backflow assembly installation requirements | Portland.gov
    Jul 25, 2025 · Backflow prevention assemblies must be those approved by OHA. Plumbing trade permits must be obtained from Portland Permitting & Development.
  72. [72]
    History of the backflow device - Informit
    The double check valve, as it has become known around the world continued to evolve. Manufacturers started to use lead weights to close the check valve.
  73. [73]
    A Brief and Interesting History of Backflow Prevention - The Florida ...
    May 18, 2023 · The very first backflow preventers were developed and implemented throughout Los Angeles in the 1930s. These devices featured a pressure vacuum ...
  74. [74]
    History of Cross Connection Control | Backflow Solutions, Inc.
    Nov 27, 2018 · Beginning in 1930, rudimentary pressure vacuum breakers were being designed and developed in the Los Angeles area. Double check assemblies ...
  75. [75]
    What is a Cross Connection Control and Backflow Preventer?
    Feb 27, 2019 · 1930 - The first pressure vacuum breakers and early backflow preventers begin to be developed mostly in Los Angeles. Watch the video below for a ...Missing: 1920s | Show results with:1920s
  76. [76]
    The Evolution of Backflow Prevention Design
    Sep 30, 2020 · Specifically, backflow preventers have evolved because the way we use water evolves dramatically, from gravity systems to pressurized systems.
  77. [77]
    [PDF] Evaluation of backflow prevention devices: a state-of-the-art report
    ... A.S.S.E. 1015. °. Also specifies but without a test procedure: - shock and water hammer. - hydrostatic test on all barriers. - 12 months field performance. - no ...Missing: endurance | Show results with:endurance
  78. [78]
    Flomatic Valves Meet Lead Free Standards
    This law reduces lead content from 8 percent to 0.25 percent the amount of lead allowed in “lead-free” plumbing fixtures that touch drinking water. This is ...
  79. [79]
  80. [80]
  81. [81]
    [PDF] Backflow Protection for Residential Sprinkler Systems
    Reported failure rates of backflow preventers recommended for low hazard and high hazard cross connections (Double Check Valve Assemblies - DCVA and Reduced ...
  82. [82]
    Double Check Valve Assembly: A Key Player in Backflow Prevention
    Jun 6, 2024 · The double check valve assembly is a popular choice for backflow prevention due to its reliability and low maintenance requirements. The two ...
  83. [83]
    Double Check Valve Assembly (DCVA) - Evan Supply
    The DCVA features two positive seating check modules and is a testable device for moderate hazard water system containment.
  84. [84]
    The Difference Between a Check Valve and a Double Check Valve
    Sep 10, 2025 · A double check valve consists of two independent check valves in series, providing redundant backflow prevention.Missing: definition engineering
  85. [85]
    Double Check Valve vs. Single Check Valve: Which is Best for You?
    Oct 25, 2024 · : The main role of a single check valve is to prevent backflow. ... Provides lower protection against backflow compared to a double check valve.Missing: failure rate
  86. [86]
    Plan Submission Requirements & Details | City of Bloomington ...
    Apr 12, 2024 · What is the difference between a double check valve backflow preventer and a reduced pressure zone backflow preventer (RPZ)? RPZ backflow ...
  87. [87]
    RPZ vs Double Check Valve Backflow Preventers | Key Differences ...
    The main difference is that an RPZ offers a higher level of protection by using two check valves plus a pressure relief valve. A double check valve relies on ...