Solar gain

Solar gain refers to the increase in within a building or structure due to the absorption of solar radiation, primarily through windows, walls, and roofs, where shortwave passes through glazing and is converted to longwave by interior surfaces. This process, akin to the , traps inside by allowing visible and near- radiation to enter while restricting the escape of longer-wavelength emissions from warmed materials. In building design, solar gain is a fundamental aspect of passive , enabling natural heating in colder climates without mechanical systems, though it requires careful control to prevent excessive warming in summer. The physics of solar gain involves the transmission of solar spectrum radiation—peaking in the visible range at approximately 520 W/m² under clear conditions—through transparent materials like , which typically absorbs or reflects only a portion while allowing the rest to heat interior absorbers such as floors or walls. Key metrics include the solar heat gain coefficient (SHGC), which quantifies the fraction of incident solar radiation admitted as heat (ranging from 0 to 1, with lower values indicating better blocking), and the U-factor, measuring conductive heat loss. Effective designs orient apertures (e.g., south-facing windows within 30° of true south) to maximize winter gain while using overhangs, shading, or low-emissivity coatings to minimize summer overheating. Passive solar strategies leveraging solar gain incorporate five essential elements: aperture for collection, absorber surfaces (often dark-colored), (e.g., or ) for storage, distribution via natural or fans, and adjustable controls like vents or blinds. Notable techniques include direct gain, where sunlight heats living spaces directly (utilizing 60-75% of incident radiation); indirect gain, such as Trombe walls (8-16 inch thick behind glazing, with lagging 8-12 hours); and isolated gain via sunspaces. These approaches can reduce heating energy needs by up to 50% in appropriate climates, promoting and , but demand site-specific analysis considering , , and local weather patterns.

Fundamentals of Solar Gain

Definition and Principles

Solar gain refers to the increase in within a building's interior due to the or of solar through its , including elements such as windows, walls, and roofs. This process contributes to heating the indoor either directly or indirectly, influencing overall thermal performance and energy consumption. The basic principles of solar gain distinguish between direct and indirect mechanisms. Direct solar gain occurs when shortwave solar radiation passes through transparent materials like glazing and is absorbed by interior surfaces, converting to within the . In contrast, indirect solar gain involves solar radiation being absorbed by opaque building elements, such as walls, which then transfer to the interior via conduction or re-emit it as . The concept of solar gain emerged in during the mid-20th century, particularly in the post-World War II era, as researchers addressed amid fuel shortages and the rise of . This period saw increased focus on passive solar techniques to optimize heat retention in homes, laying foundational studies for quantifying solar contributions to building loads. Solar gain is quantified using , typically measured in watts per square meter (W/m²), which represents the power of incoming solar radiation on a surface and serves as a key metric for calculating into buildings. The solar heat gain coefficient provides a related measure for specific components like windows.

Physics of Solar Radiation Absorption

Solar radiation reaching Earth's surface consists of electromagnetic waves spanning a broad spectrum, primarily divided into (UV), visible, and () components. The UV portion occupies wavelengths from approximately 100 to 400 , carrying about 5% of the total and contributing to photochemical reactions but limited heat due to atmospheric . Visible light spans 400 to 700 , accounting for roughly 43% of the , and is responsible for illumination while also adding to thermal effects through by materials. The component, from 700 to 1 mm, dominates with about 52% of the and is the primary contributor to heating, as it directly excites molecular vibrations in surfaces, converting to . The absorption of solar by building materials follows fundamental principles of , governed by Kirchhoff's law, which states that for a in , the ε at a given equals the absorptivity α, or ε(λ) = α(λ). This implies that materials which efficiently absorb at certain wavelengths also emit strongly at those wavelengths when heated. For any incident , the fraction absorbed (α), transmitted (τ), and reflected (ρ) sum to unity: α + τ + ρ = 1. In opaque building materials like walls or roofs, transmissivity τ is zero, simplifying to α + ρ = 1, meaning absorbed directly heats the surface while the rest is reflected away. These properties vary by wavelength; for instance, many construction materials have high absorptivity in the IR range, enhancing solar heating. Once absorbed, the converts to and transfers through the building via three primary modes: conduction, , and . Conduction occurs within solids, described by Fourier's law, where the q is proportional to the negative :
\mathbf{q} = -k \nabla T
here, k is the thermal conductivity of the material, and ∇T is the ; this mode dominates in transferring from the sun-warmed outer surface inward through walls or roofs. involves exchange between the surface and surrounding air, driven by or forced flow, and is significant near windows or vents where warmed air rises and circulates. , meanwhile, includes both the incoming solar absorption and the subsequent long-wave emission from heated surfaces, following the Stefan-Boltzmann law, where net radiative loss depends on surface and ; in solar gain, this mode recirculates within enclosed spaces. These processes collectively determine how absorbed raises indoor temperatures.
The total solar gain Q_solar through a building element can be quantified as the product of the surface area A, incident I, and the effective :
Q_{\text{solar}} = A \times I \times (\tau + \alpha \times f)
where τ is the transmissivity (direct passage of ), α is the absorptivity, and f is the inward-flow fraction of absorbed that enters the space (typically 0.5 to 0.84 depending on material thickness and , as absorbed partitions between indoor and outdoor sides). This equation captures both transmitted and absorbed contributions to internal heating, excluding conductive losses from temperature differences.
The intensity of solar radiation on a surface is further modulated by the angle of incidence θ, the angle between the incoming rays and the surface normal. According to the cosine law, the effective irradiance is reduced as I_effective = I × cos θ, where I is the direct normal ; at θ = 0° ( incidence), cos θ = 1 for maximum energy capture, but oblique angles (e.g., θ = 60°) yield only 50% intensity, significantly lowering absorption on vertical walls during low-sun periods. This angular dependence is critical for understanding diurnal and seasonal variations in solar gain.

Solar Gain Through Building Elements

Properties in Glazing and Windows

The properties of glazing and windows play a critical role in determining solar gain through , primarily via optical transmittance and thermal re-radiation effects. Key metrics include the , g-value, and solar heat gain coefficient, each quantifying aspects of how incident solar radiation interacts with transparent building elements. The (SC) is defined as the ratio of solar heat gain through a glazing system under standard conditions to the solar heat gain through a reference 1/8-inch (3 mm) clear glass pane. Typical SC values range from 0.5 to 1.0, with clear single glazing around 0.83–0.87 and reductions achieved through tinting or reflective coatings that lower solar transmittance and . For instance, tinted glazings can decrease SC by absorbing more short-wave radiation, thereby limiting the heat entering the interior. Although SC was historically used in building standards, it has largely been supplanted by more precise metrics like the solar heat gain coefficient in modern codes such as the International Code (IECC). The g-value, also known as the solar factor or total transmittance, represents the fraction of incident that is admitted through the glazing on a scale from 0 to 1, encompassing both directly transmitted and that absorbed and re-emitted inward. A g-value of 1.0 indicates full , as with ideal clear , while values near 0 denote complete blockage. It directly relates to overall transmittance and is equivalent to the divided by 0.87 for reference clear . The solar heat gain coefficient (SHGC) provides a comprehensive measure of solar gain, defined as the ratio of total solar heat gain entering the interior through the —via direct transmission, , and inward re-radiation—to the incident solar radiation. It is calculated according to standards like ANSI/NFRC , which involve heat balance modeling for the entire product (including frame and glazing) under specified conditions such as 75°F (24°C) interior and 90°F (32°C) exterior temperatures. NFRC ratings ensure comparability, with SHGC values typically ranging from 0.2 to 0.8 depending on glazing configuration. Low-emissivity (low-e) coatings on glazing surfaces selectively reduce () transmission while allowing visible , thereby lowering SHGC by minimizing the re-radiation of absorbed . Double glazing, consisting of two panes with an air or gas-filled space, typically yields an SHGC of around 0.70 for clear configurations, which can drop to 0.25–0.30 with low-e coatings and gas fill due to suppressed and enhanced of long-wave . Triple glazing further reduces SHGC compared to double, often to 0.20–0.40 in low-solar-gain setups with multiple low-e layers and or krypton fills, providing better control in cooling-dominated climates. A key distinction exists between SHGC and U-value: the former quantifies solar-driven heat gain through and , while the U-value measures non-solar conductive and convective heat loss, with lower U-values indicating better independent of solar input. In contemporary building codes like the IECC, SHGC is the primary metric for solar gain compliance, with allowable values varying by climate zone (e.g., ≤0.40 in hot regions), whereas may serve only as an alternative calculation basis in limited cases.

Solar Gain in Opaque Components

Solar gain in opaque building components occurs when solar radiation is absorbed by non-transparent surfaces such as walls and roofs, leading to into the building interior via conduction. The extent of absorption depends on the material's solar (α_s), which represents the fraction of incident solar radiation absorbed by the surface. For common building materials, α_s values typically range from 0.4 to 0.6 for light-colored and 0.25 to 0.4 for white paint, with darker surfaces exhibiting higher due to lower reflectivity. This absorbed heat raises the surface , creating a that drives conductive heat flow through the material, influenced by its thermal properties. The transfer of this absorbed heat into the building is delayed by the of the opaque component, which stores energy and reduces the immediacy of internal temperature fluctuations. High thermal mass materials, such as , exhibit significant time lags—often several hours—between peak solar exposure and peak indoor heat gain, thereby attenuating diurnal temperature swings. Transient heat gain through opaque elements can be modeled using methods, such as solutions to the heat conduction equation, which account for thermal mass effects and time lags. Insulation plays a critical role in modulating this heat gain by increasing the overall thermal resistance (R-value), which not only reduces the steady-state conductive flow but also extends the time lag when paired with internal thermal mass, shifting peak gains to off-peak periods. For instance, concrete walls with high R-value insulation (e.g., R-20 or higher) can significantly dampen internal temperature variations compared to low-mass assemblies. In terms of orientation, south-facing walls in the northern hemisphere experience 20-30% higher annual solar exposure than east- or west-facing equivalents due to optimal alignment with the sun's path, amplifying potential heat gains; roofs, being horizontal, receive more diffuse but intense midday radiation. Ventilation behind exterior cladding, such as in rainscreen systems, mitigates this by promoting convective cooling of the absorbed heat before it conducts inward, potentially reducing surface temperatures by several degrees Celsius, depending on wind speed and cavity design. Modern advancements include the incorporation of phase-change materials (PCMs) into opaque components, which absorb solar heat via storage during phase transitions (e.g., ), thereby reducing peak internal loads. PCM-enhanced walls can decrease heat gain by 20-50% in various climates by storing excess energy during the day and releasing it nocturnally, offering a dynamic alternative to traditional mass.

Impacts of Solar Gain on Buildings

Thermal Comfort and Energy Use

Solar gain serves as a free heat source in cold climates, where it can contribute significantly to meeting winter heating needs through passive solar design. In northern U.S. regions, south-facing glazing can provide net positive heat gains that offset 50-75% of seasonal heat losses in many cases, effectively reducing reliance on mechanical heating systems. The integration of solar gain with heating, ventilation, and air-conditioning (HVAC) systems enhances overall energy savings by balancing gains against losses. The net energy gain from solar input is calculated as ΔE = Q_solar - Q_loss, where Q_solar represents the absorbed solar radiation and Q_loss encompasses conduction, , and infiltration losses through the . This approach allows for optimized HVAC operation, as excess solar heat reduces the demand for auxiliary heating, potentially lowering total building energy use in heating-dominated climates when paired with storage. Solar gain influences primarily through its effect on (MRT), a key parameter in the Predicted Mean Vote (PMV) model, which predicts occupant thermal sensation on a scale from -3 (cold) to +3 (hot). Elevated MRT due to solar radiation increases the operative temperature, potentially leading to discomfort in overheated conditions. In office buildings within temperate zones, unmanaged solar gain can elevate cooling demands, as demonstrated in simulations where unshaded glazing amplifies peak loads during transitional seasons. Adaptive comfort models, such as those in Standard 55, accommodate variations in naturally ventilated spaces by permitting wider indoor temperature ranges based on outdoor conditions—without compromising occupant satisfaction, provided running mean outdoor temperatures remain moderate. This supports energy-efficient design by expanding the acceptable comfort band in buildings relying on , reducing mechanical cooling needs while maintaining PMV within neutral ranges.

Overheating and Cooling Loads

Excessive gain can lead to overheating in when peak causes internal temperatures to rise above acceptable comfort levels, typically exceeding 28–32°C during occupied hours. This occurs as shortwave passes through transparent elements or is absorbed and re-radiated as heat by opaque surfaces, overwhelming natural ventilation or capacity. In such scenarios, the combined effects of direct solar transmission, absorbed heat, and limited heat dissipation elevate indoor air and surface temperatures, particularly in spaces with high glazing ratios or low . A key concept in assessing overheating from solar gain on external surfaces is the sol-air temperature, which represents the equivalent outdoor temperature accounting for both air temperature and solar radiation effects. The formula is T_{\text{sol-air}} = T_{\text{air}} + \frac{\alpha_s I}{h_o}, where T_{\text{air}} is the ambient air temperature, \alpha_s is the solar absorptance of the surface, I is the incident solar radiation intensity, and h_o is the external surface heat transfer coefficient (typically 20–30 W/m²K). This metric helps quantify how solar radiation amplifies heat transfer into the building envelope, simulating the thermal stress as if it were solely due to higher air temperatures. Cooling loads attributable to gain are calculated differently for and opaque elements. For windows and glazing, the cooling load is approximated as Q_{\text{[solar](/page/Solar)}} = \text{SHGC} \times A \times I_{\text{[peak](/page/Peak)}}, where SHGC is the heat gain coefficient (ranging from 0 to 1, indicating the fraction of incident radiation admitted), A is the area, and I_{\text{[peak](/page/Peak)}} is the incident (often 800–1000 W/m² at midday). This method captures both transmitted and absorbed-re-radiated heat entering the space. For opaque components like walls and roofs, the Cooling Load Temperature Difference (CLTD) method is used: Q = U \times A \times \text{CLTD}, where U is the overall heat transfer coefficient, A is the surface area, and CLTD is a tabulated value (from standards like ASHRAE) adjusted for sol-air temperature, time of day, orientation, and thermal lag, typically ranging from 10–40°C under conditions. These calculations inform HVAC sizing and reveal how gain can contribute significantly to total cooling loads in sunny climates. Several risk factors exacerbate overheating from solar gain. Building orientation plays a , with east-facing facades experiencing intense morning solar peaks that heat interiors rapidly after overnight cooling, and west-facing ones suffering afternoon peaks when ambient temperatures are already high, leading to prolonged discomfort. Urban heat island (UHI) effects further amplify solar impacts by elevating local air temperatures 2–5°C above rural areas—equivalent to a 10–20% intensification of solar-driven heat gain due to reduced , trapped , and higher effective sol-air temperatures in dense cityscapes. Historical events underscore the consequences of unmanaged solar gain in overheating scenarios. During the energy crises, triggered by oil embargoes, pre-air-conditioned buildings in the U.S. and revealed vulnerabilities to solar overheating, as high glazing and poor shading in mid-century designs drove excessive heat buildup, prompting early adoption of passive solar controls and energy codes to mitigate cooling demands without mechanical systems. More recently, the , with temperatures 20–30% above average, significantly increased cooling needs across the continent, with electricity demand for surging in affected regions like , exacerbating blackouts and highlighting solar gain's role in amplifying during extremes. Recent events, such as the record-warm 2024 in and the 2025 heatwave, have similarly driven electricity demand increases of up to 14% due to heightened cooling needs, further emphasizing the growing risks from solar gain in warming climates. Climate change projections indicate worsening overheating risks from solar gain, particularly in mid-latitude regions like . By 2050, under moderate emissions scenarios, mid-latitude cities could see 20–50% more annual overheating hours (defined as >28°C indoors) due to intensified radiation patterns, longer exposure periods, and UHI synergies, potentially doubling cooling demands in non-retrofitted buildings. This underscores the need for adaptive to counter rising sol-air equivalents and peak intensities in warming climates.

Strategies for Managing Solar Gain

Shading and Control Techniques

External shading devices, such as overhangs, vertical fins, and louvers, are fixed or adjustable structures positioned outside building envelopes to intercept solar radiation before it reaches glazing surfaces, thereby reducing solar heat gain coefficient (SHGC) values. Overhangs are particularly effective for south-facing windows in the , blocking high-angle summer sun while allowing lower-angle winter sun to penetrate for passive heating. Vertical fins provide shading for east- and west-facing windows, mitigating low-angle morning and afternoon radiation, while louvers offer directional control through slatted designs that can be fixed or pivoted. A common design approach for overhang depth on south-facing windows to achieve summer control involves calculations based on and sun angles to approximate shading during peak summer months. Internal shading devices, including blinds, curtains, and solar control films, are installed inside buildings to absorb or reflect solar that has already passed through glazing, though they are generally less effective than external options because occurs after the radiation enters the . Horizontal or vertical blinds with reflective slats can redirect light and reduce direct beam penetration, while curtains and drapes with light-colored, insulating backings block up to 33% of summer heat gain on sunlit windows. Roller shades, especially those with low-emissivity or cellular designs, can reduce SHGC depending on fabric openness and color, with cellular variants achieving up to 60% reduction in solar heat gain when tightly fitted. Solar control films applied to interior glass surfaces reflect infrared , further lowering effective SHGC without significantly altering visible . Dynamic shading systems enhance control by automating adjustments to solar exposure, using sensors to track solar angles, , and indoor conditions for real-time optimization. Automated louvers or motorized external shades pivot or retract based on photocell or inputs, maintaining consistent shading while maximizing daylight. Electrochromic glass represents an advanced integration, where low-voltage application modulates ion flow in thin films to vary solar (τ) from approximately 0.1 (tinted state) to 0.6 (clear state), reducing SHGC from 0.41-0.46 to 0.09-0.12 and cutting cooling loads by 25-58% compared to static low-e glazing. These systems often incorporate software for predictive control, aligning with and data to minimize use. Vegetative shading, such as deciduous trees planted strategically to the south, east, or west of buildings, offers seasonal control by providing dense foliage cover in summer to block solar gain—reducing it by approximately 30% through direct shading of walls and windows—while leafless branches in winter permit passive solar heating. This natural approach not only lowers cooling energy demands but also enhances biodiversity and urban microclimates, with studies confirming average 30% air-conditioning savings in shaded residences.

Integration in Passive Solar Design

Passive solar design harnesses solar gain to provide heating and in buildings without mechanical systems, relying on architectural elements to capture, store, and distribute . Direct gain systems allow to enter living spaces through large south-facing windows, where it is absorbed by materials such as floors or walls, which store the heat and release it gradually over time. Indirect gain approaches, like Trombe walls, position a thermal mass wall behind glazing to absorb solar radiation without direct exposure to the interior, with vents facilitating convective to adjacent rooms. Isolated gain configurations, such as attached sunspaces, collect solar energy in a separate enclosure connected to the main building, enabling controlled heat distribution while providing additional usable space. Optimizing gain in passive designs involves balancing window-to-wall ratios (WWR) to maximize winter collection while minimizing losses, with optimal ratios of 10-20% recommended for cold climates to achieve net energy benefits from glazing. plays a critical role in stabilizing indoor , governed by the equation \Delta T = \frac{Q_{\text{[solar](/page/Solar)}}}{m c}, where \Delta T is the change, Q_{\text{[solar](/page/Solar)}} is the input, m is the mass of the material, and c is its ; this relationship ensures that sufficient mass moderates diurnal swings by absorbing excess daytime and releasing it at night. Shading techniques, integrated into the overall , further refine this balance by preventing unwanted summer gains. In , standards exemplify effective gain integration, requiring space heating energy demand not to exceed 15 kWh/m²/year, a target achieved through optimized glazing with high solar heat gain coefficients (around 50%) and airtight envelopes that leverage winter contributions to minimize auxiliary heating needs. Design tools like EnergyPlus enable precise modeling of these systems by simulating radiation, interactions, and overall building performance under varying climates. Guidelines from the National Fenestration Rating Council (NFRC) inform window selections by rating solar heat gain coefficients (SHGC), promoting high values (closer to 1) for passive heating in cold regions, while the Institute provides certification criteria emphasizing -optimized envelopes with U-values ≤0.80 W/(m²K). Bioclimatic design extends passive solar principles to hot climates by prioritizing from solar gain while minimizing thermal loads, using elements like light shelves on south-facing facades to reflect sunlight onto ceilings for deeper interior penetration without direct heat entry. External light shelves, often with reflective surfaces and seasonal adjustability, reduce solar heat gain factors to as low as 0.1 compared to 0.4 for internal versions, enhancing occupant comfort and cutting cooling demands in regions like .

References

  1. [1]
    Passive Solar Homes | Department of Energy
    Passive solar design takes advantage of a building's site, climate, and materials to minimize energy use.
  2. [2]
    None
    ### Summary of Solar Gain Explanation from the Document
  3. [3]
    Passive Solar Design - Sustainability - Williams College
    Passive solar design refers to the use of the sun's energy for the heating and cooling of living spaces by exposure to the sun.
  4. [4]
    Passive Solar Building Design - InterNACHI®
    Passive solar building design is a strategy by which a building's windows, walls and floors can be designed to collect, store and distribute solar energy.Missing: definition | Show results with:definition
  5. [5]
    Solar Gain - an overview | ScienceDirect Topics
    Solar gain is defined as the increase in thermal energy within a space due to solar radiation, which can significantly contribute to the total internal heat ...
  6. [6]
    Solar gain in buildings - Designing Buildings Wiki
    Oct 7, 2022 · Solar design (or passive solar design) is an aspect of passive building design that focusses on maximising the use of heat energy from solar ...
  7. [7]
    Solar Housing Is Actually Kind of Retro! - JSTOR Daily
    May 27, 2021 · The domestic fuel scarcity of World War II led to innovation in home heating—especially passive solar technology.
  8. [8]
    A conversion guide: solar irradiance and lux illuminance - Extrica
    Dec 4, 2020 · The standard for measuring solar irradiance utilizes the units of watts per meter squared (W/m2). Irradiance meters are both costly and limited ...
  9. [9]
    Solar Spectrum Explained: Sunlight, Radiation & Energy Loss
    The energy distribution of the solar spectrum is approximately 5% UV, 43% visible and 52% infrared. In summary, the sunlight varies because of solar ...Missing: breakdown | Show results with:breakdown
  10. [10]
    6.8 Kirchhoff's Law explains why nobody is perfect. | METEO 300
    Kirchhoff's Law states that at any given wavelength, an object's emissivity ε is equal to its absorptivity, that is: ε(λ)=α(λ) [6.7]
  11. [11]
    Fourier's Law, Heat Transfer by Conduction, Convection and Radiation
    Using Fourier's law of thermal conduction, heat is transferred through a material in a specific proportion to its negative gradient of temperature.
  12. [12]
    Fourier Conduction - an overview | ScienceDirect Topics
    Heat transfer can be by radiation (Stefan-Boltzman law), conduction (Fourier's Law) and by convection (Newton's law of cooling). Due to small temperatures ...
  13. [13]
    3.3. Cosine Effect | EME 812: Utility Solar Electric and Concentration
    When the incident ray is not perpendicular to the surface (which is often the case with fixed-tilt systems), the angle of incidence is not zero (q ¹ 0), and ...
  14. [14]
    Energy Performance Ratings for Windows, Doors, and Skylights
    The lower the U-factor, the more energy-efficient the window, door, or skylight. Solar heat gain coefficient (SHGC) is the fraction of solar radiation ...
  15. [15]
    [PDF] A Method for comparing the thermal performance of windows - MIT
    SC is the shading coefficient, defined as the ratio of the solar heat gain through a glazing system under a specific set of conditions to the solar gain ...
  16. [16]
    Solar heat gain coefficient (SHGC) - Thermal Windows
    The solar heat gain coefficient has replaced the shading coefficient as the standard indicator of a window's shading ability.
  17. [17]
    [PDF] Residential Provisions of the 2018 IECC
    Where more than 1 replacement fenestration unit is to be installed, an area-weighted average U- factor, SHGC or both of all replacement fenestration units can ...
  18. [18]
    Performance Value Terms | Guardian Glass
    Solar Factor or Total Solar Energy Transmittance or g-value (g%) is the total solar radiation transmitted by the glass. Shading Coefficient (sc) is Solar Factor ...
  19. [19]
    [PDF] NFRC 200-2023[E0A5E0A6] - National Fenestration Rating Council
    Solar Heat Gain Coefficient (SHGC):. The ratio of the solar heat gain entering the space through the fenestration product to the incident solar radiation. Solar ...
  20. [20]
    ANSI/NFRC 200: Determining Fenestration Product Solar Heat Gain ...
    The NFRC 200 procedure calculates SHGC and VT for summer conditions of 75ºF (24ºC) interior temperature and 90ºF (32ºC) exterior temperature. End Result: The ...
  21. [21]
    Windows and Glazing | WBDG - Whole Building Design Guide
    In climates with significant air conditioning loads, specify windows with low SHGC values (< 0.40). ... Soft-coat Low-e Double Glass w/Argon gas fill (PPG Sungate ...
  22. [22]
    Heat & UV Control with LOW-E Coatings - AGNORA
    A double-glazed IGU with Low-E and argon fill can drop that value to 0.25–0.30, depending on the configuration. Triple-pane systems with Low-E on multiple ...
  23. [23]
    Triple Low-E Glazing - NFRC Consumer Guide to Windows
    In this case there are three glazing layers and two low-E coatings, ½” argon gas or ¼” krypton gas fill between glazings, and low-conductance edge spacers.
  24. [24]
    Surface Radiation Absorptivity - The Engineering ToolBox
    Red clay brick, 0.94. Snow, ice granules, 0.33. Steel, galvanized (zink oxide), 0.65. Steel, galvanized weathered, 0.8. White paint, 0.25 - 0.4. My Short List.
  25. [25]
    Table of absorptivity and emissivity of common materials and coatings
    LO/MIT I/II products are low emissivity, non thickness dependent coatings. Solec. White paint, 0.23 - 0.49, U of Miss. Solec SOLKOTE selective surface paint ...
  26. [26]
    [PDF] 4.401 Lecture 12 Thermal Mass and Heat Flow
    As the thermal mass increases, the indoor temperature follows increasingly longer outside DBT trends. ❑ For a theoretical 1.6 m thick concrete envelope the lag ...
  27. [27]
    Numerical computation of time lags and decrement factors for ...
    The times it takes for the heat wave to propagate from the outer surface to the inner surface is named as “time lag” and the decreasing ratio of its amplitude ...
  28. [28]
    Managing Enclosure Heat Flows | WBDG
    To achieve high-performance exterior walls over typical ranges of WWR, opaque walls should have a minimum effective thermal resistance value of R-25 and windows ...
  29. [29]
    A Quantitative Look at Solar Heat Gain - GreenBuildingAdvisor
    Jan 1, 2018 · This article explores the viability of passive solar and solar-tempered space heating in northern US regions and metro areas.
  30. [30]
    Application of Ventilated Solar Façades to enhance the energy ...
    These facades actively regulate airflow and temperature within the building envelope by leveraging solar heat gains, functioning as dynamic heat exchangers.
  31. [31]
    Optimizing PCM-Integrated Walls for Potential Energy Savings in ...
    Depending on the climate, optimized PCMs in U.S. building walls can provide reduction in the annual heat gain in the range of 3.5%–47.2% and the annual heat ...
  32. [32]
    Solar heat gain factors and heat loss coefficients for passive ... - OSTI
    Aug 1, 1994 · The concept of solar heat gain factor has been introduced for calculating the net energy gain of passive heating elements and other ...Missing: ΔE = Q_solar -
  33. [33]
    Passive Solar Systems for the Promotion of Thermal Comfort ... - MDPI
    ... solar heat gains by approximately 70–90% and winter heat loss by 10–30%. Moreover, photosynthesis reduces the carbon footprint of cities [96]. However ...Passive Solar Systems For... · 3. Discussion · 3.1. Bioclimatic...
  34. [34]
    CBE Thermal Comfort Tool for ASHRAE-55
    The calculation of PMV comfort zone is based on all the psychrometric variables, with PMV values between -0.5 and +0.5 according to the standard.
  35. [35]
    [PDF] ANSI/ASHRAE/IES Standard 90.1-2022: Energy Savings Analysis
    New commercial buildings meeting the requirements of Standard 90.1-2022 that were analyzed in the quantitative analysis exhibit national average savings5 from ...Missing: unmanaged | Show results with:unmanaged
  36. [36]
    Adaptive Comfort Model - Center for the Built Environment
    The Adaptive Comfort Model is a standard for thermal comfort in naturally ventilated buildings, adopted in ASHRAE Standard 55, and is a global standard.
  37. [37]
    Full article: Overheating in buildings: lessons from research
    Nov 30, 2016 · Thus, they lack the thermal mass necessary to ameliorate the large temperature swings caused by summertime internal and solar gains. In ...Why Is Overheating A Problem... · When Is A Building... · How Widespread Is...Missing: sol- | Show results with:sol-
  38. [38]
    Sol-Air Temperature - Mypdh.engineer
    Sol-air temperature is the equivalent outdoor air temperature that gives the same heat flow as solar radiation and convection/radiation with the environment.Missing: mechanisms | Show results with:mechanisms
  39. [39]
    [PDF] HVAC Made Easy: A Guide to Heating & Cooling Load Estimation
    See 1997 ASHRAE Fundamentals, Chapter 24 or 2001 ASHRAE. Fundamentals, chapter 25. ... 16) Heating load: The heating load is a rate at which heat is added to the ...
  40. [40]
    None
    Summary of each segment:
  41. [41]
    Building Orientation | Sustainability Workshop
    Solar heat gain on the east side can be acceptable or even useful, because it happens in the morning after the cooler night; but solar heat gain on the west ...
  42. [42]
    Urban heat mitigation through improved building energy efficiency
    We found that improved energy efficiency reduces indoor and outdoor exposure to heat while climate change increases both.
  43. [43]
    The 1970's Energy Crisis Shined a Spotlight on Facility Management
    Apr 5, 2024 · Buildings in the '70s were not energy efficient. Facility managers showed the country how to reduce energy use and save money.
  44. [44]
    [PDF] Impacts of summer 2003 heat wave in Europe
    The severe heat wave began in Europe in June 2003 and continued through July until mid-August, raising summer temperatures 20 to 30% higher than the ...
  45. [45]
    Overheating and energy use in urban office buildings in a warming ...
    Dec 19, 2022 · Heating demand reduces by at least 36% in the 2050s but electricity consumption and summertime space conditioning will increase by at least 13% ...
  46. [46]
    Sun Control and Shading Devices | WBDG
    Well-designed sun control and shading devices can dramatically reduce building peak heat gain and cooling requirements and improve the natural lighting quality.
  47. [47]
    Energy Efficient Window Coverings
    In cooling seasons, cellular shades can reduce unwanted solar heat through windows by up to 60%, reducing the total solar gain to 20% when installed with a ...Missing: contribution | Show results with:contribution
  48. [48]
    [PDF] How Electrochromics Improve Health, Productivity, and Efficiency
    However, modeling and field tests show that a window whose SHGC can vary from 0.15 to 0.40, a range attainable by today's commercially available electrochromic ...
  49. [49]
    [PDF] Improved estimates of tree-shade effects on residential energy use
    Tree-shade reduces solar radiation, altering building cooling and heating. A method using lookup tables and tree frequency estimates these effects.
  50. [50]
    Optimization of Window-to-Wall Ratio for Buildings Located ... - MDPI
    In colder climates, the solar heat gain can dominate the transmission losses through windows, which decreases the heating demand in winter periods. On the ...
  51. [51]
    Passive House requirements - Passivhaus Institut
    The Space Heating Energy Demand is not to exceed 15 kWh per square meter of net living space (treated floor area) per year or 10 W per square meter peak demand.Missing: gain | Show results with:gain
  52. [52]
    EnergyPlus
    EnergyPlus is a whole building energy simulation program that engineers, architects, and researchers use to model both energy consumption.Missing: passive | Show results with:passive
  53. [53]
    National Fenestration Rating Council | NFRC is the leader in energy ...
    Solar Heat Gain Coefficient measures a how much solar heat a product allows in. Low numbers resist solar heat, high numbers allow solar heat. Range: 0-1. Air ...Certified Products Directory · About · Contact Us · NFRC Products DirectoryMissing: formula | Show results with:formula<|separator|>
  54. [54]
    [PDF] Del 2.4.4 Guide for bioclimatic design - Smart Cities Marketplace
    South-facing glass is relatively easy to shade with an overhang during the summer to minimize solar heat gain. Light shelves also can work well with the higher ...