Transfer switch

A transfer switch is an electrical device designed to transfer a load between two or more power sources, such as the utility grid and a backup generator, ensuring safe isolation of sources and preventing backfeeding into the grid during outages. These switches are essential for maintaining continuous power supply in various settings, including residential, commercial, and industrial applications, by quickly and reliably switching electrical loads without interrupting critical operations. Transfer switches come in two primary types: and . Manual transfer switches require human intervention to operate, allowing users to connect a portable or to selected circuits in a home or facility, thereby providing a cost-effective for occasional power needs while ensuring compliance with safety codes. In contrast, transfer switches (ATS) are self-acting devices that monitor power sources and initiate the transfer without manual input, typically within seconds of detecting a failure, making them ideal for mission-critical environments where downtime must be minimized. Key features of transfer switches include their transition mechanisms—open transition (break-before-make) for standard applications to avoid paralleling sources, and closed transition (make-before-break) for seamless switching in systems requiring uninterrupted power—and compliance with standards such as UL 1008 for construction and performance, Article 700 for emergency systems, and IEEE 446 for recommended practices in applications. They are widely used in hospitals, centers, and facilities to support life-safety and operational continuity, with capacities ranging from small residential units to large models handling thousands of amperes.

Fundamentals

Definition and Purpose

A is an that switches a load between two or more sources, such as the utility grid and a backup generator, ensuring safe operation by preventing into the primary source. This mechanism isolates the sources to avoid hazardous electrical feedback, which could endanger utility workers or damage equipment. The primary purpose of a transfer switch is to provide seamless or minimal-interruption power transfer during outages, thereby maintaining continuity for critical loads. It protects sensitive equipment from power fluctuations and surges, supports uninterrupted operations in essential facilities like hospitals or data centers, and ensures compliance with electrical codes such as the (NEC) Article 702, which mandates transfer equipment to disconnect normal supply conductors and prevent unintended paralleling. Key concepts include source isolation to prevent paralleling of unsynchronized power supplies, which could cause phase mismatches or equipment failure, and load management features that help avoid overloads by selectively energizing circuits based on generator capacity. For instance, transfer switches can handle entire building loads in commercial settings or selectively switch individual circuits in residential applications, such as powering essential appliances during a grid failure.

Historical Development

Transfer switches originated in the early , coinciding with the increasing use of backup generators in settings to ensure continuity during outages. Initial designs were , allowing operators to switch loads between primary and auxiliary sources like generators, primarily for critical applications. By the , these systems had evolved to support higher voltages and currents, reflecting the growing of factories and facilities. The development of automatic transfer switches (ATS) marked a significant milestone in the , transitioning from purely manual operation to self-acting devices that detected power failures and initiated transfers without human intervention. Similarly, the Automatic Switch Company (ASCO) pioneered its ATS in , establishing a foundation for emergency power control that emphasized speed and reliability. G&W Electric introduced automatic transfer switches in 1927, designed for reliable switching in oil-insulated systems up to 15 kV and 400 A. These innovations were driven by post-World War II demands for enhanced power reliability in expanding industrial and commercial infrastructures, where frequent blackouts highlighted the need for seamless backup integration. Further advancements occurred in the mid-20th century, with companies like contributing to ATS evolution through integrated power systems. , building on its heritage dating to 1920, developed transfer switches, with over 80 years of experience by the 2020s. The 1970s energy crises, triggered by oil embargoes, accelerated the adoption of generator-based backup systems, prompting refinements in transfer switch designs to handle variable loads and ensure during supply disruptions. By the , static transfer switches emerged, utilizing thyristors (silicon-controlled rectifiers, invented in 1957) for near-instantaneous switching under 8 milliseconds, commercially available since 1971 to protect sensitive electronics from power anomalies. In the , advancements in enabled faster and more precise switching, with microprocessor-based controls improving and fault detection. By the , the shift to controls became prominent, incorporating features like event logging, remote diagnostics, and integration with systems, as seen in ASCO's 2011 enhancements and ' PowerCommand series. As of 2025, no major paradigm shifts have occurred post-2020, with focus remaining on refining existing and static technologies for enhanced cybersecurity and in applications.

Components

Mechanical Components

The core mechanical components of a transfer switch include contactors and circuit breaker mechanisms that facilitate the opening and closing of electrical circuits between power sources. Contactors, typically constructed as double-throw switches with a single operator, use silver composition main contacts to handle switching actions in open, delayed, or closed transitions, supporting current ratings from 40 A to 3000 A. Circuit breakers, such as molded case or case types, employ pairs of switches operated by a common mechanical linkage to ensure reliable circuit interruption, with power case variants using two-step stored energy mechanisms for higher loads up to 5000 A. These mechanisms are actuated by solenoid-driven operators or mechanical over-center toggles, enabling precise position changes between normal and alternate power sources. Structural elements provide the framework for safe and durable operation, including NEMA-rated enclosures that protect against environmental hazards such as dust, moisture, and . Common enclosure types include NEMA 1 for indoor general purpose, NEMA 3R for outdoor rain protection, NEMA 12 for industrial dust-tight applications, and NEMA 4X for harsh, -resistant environments, often constructed from 12- or 14-gauge with optional finishes. Bus bars serve as robust conductors for load connections, typically silver- or tin-plated to enhance and resist . mechanisms, both and electrical, are integral to prevent simultaneous connection of sources, featuring common linkages in breaker types or Kirk key systems in high-amperage designs. Materials and design emphasize durability and safety, with conductors commonly made from for superior conductivity or aluminum for cost-effective applications in lower-amperage setups. Robust housings incorporate quenching features, such as removable arc chutes with metal plates and insulating baffles, to extinguish arcs during switching in high-voltage scenarios and protect main contacts from damage. High-strength materials insulate power poles, while arcing contacts in larger contactors (rated 600 A and above) make and break first to extend main contact life. These designs integrate briefly with electrical controls for coordinated actuation but prioritize mechanical reliability. Specific facts highlight performance variations, with mechanical life ratings for s often reaching 100,000 operations under load conditions, as verified in UL 1008 testing that requires 6000 cycles for ratings up to 300 A and scales down for higher amperages (e.g., 1000 cycles with current for over 1601 A). Designs differ for low versus high amperage: compact molded case breakers suit loads up to 1000 A with high withstand ratings in insulated housings, while power case or large frames handle up to 4000 A with enhanced stored energy actuators and freestanding enclosures for industrial scalability.

Electrical and Control Components

Transfer switches incorporate various electrical elements to monitor power sources and facilitate safe switching. Voltage and sensors continuously assess the primary and alternate power supplies, ensuring that parameters such as voltage levels (typically above 85-90% of nominal) and frequency stability are within acceptable tolerances before initiating a transfer. transformers provide non-intrusive monitoring of load currents, enabling detection of imbalances or excessive draw without interrupting the . contacts serve as signaling interfaces, transmitting status signals (open/closed) to the for events like source availability or faults. The core of modern transfer switch functionality lies in microprocessor-based controllers, particularly for automatic transfer switches (ATS), which integrate programmable logic to orchestrate the switching sequence. These controllers employ dedicated algorithms to evaluate inputs and execute timed responses, such as programmable for generator warmup ranging from 5 to 30 seconds to allow stabilization before load application. This logic ensures reliable operation by prioritizing source quality over speed, often incorporating self-diagnostics for system health. Advanced features enhance the robustness of these systems. Inrush current limiters, often achieved through delayed or in-phase transfers, mitigate transient surges that could exceed motor starting currents during source changes. Phase checks verify the correct sequence of phases between sources, preventing equipment damage from reversed in three-phase applications. Communication interfaces, such as over , enable remote monitoring and integration with systems for real-time status reporting. Control power for these components is typically supplied by a dedicated 24V source, derived from batteries or rectified inputs, to ensure independence from main power fluctuations and reliable operation during outages. Fault detection circuits are integral, monitoring for ground faults via residual and overloads through current threshold comparisons, triggering alarms or inhibitions to protect connected loads.

Operation

Principles of Operation

Transfer switches operate by continuously monitoring the primary power source, typically the grid, for deviations in electrical parameters that indicate a . In the detection phase, integrated sensors and control logic track voltage and frequency levels. Thresholds for initiating are adjustable, typically set to detect when the utility voltage falls below 85-95% of the nominal value or the deviates by more than ±2-5% from the standard 60 Hz in North American systems, preventing transfers from transient fluctuations while ensuring prompt response to genuine outages. Once a failure is detected, the transfer sequence begins with disconnection from the primary source to isolate the load. This is followed by a programmed delay to allow the alternate source, such as a , to start and stabilize. The switch then connects the load to the alternate source, provided its parameters meet acceptable limits. Transfer must occur within 10 seconds for emergency systems and 60 seconds for legally required standby systems, as per NEC Articles and 701. For closed-transition configurations, synchronization checks verify that the alternate source's voltage, , and align closely with the primary before any paralleling occurs, minimizing disruption. Central to the are the principles of break-before-make and make-before-break. In break-before-make sequences, the switch fully disconnects the load from one source before connecting to the other, ensuring no paralleling but introducing a brief power interruption. Conversely, make-before-break allows momentary paralleling of sources for seamless transfer, though it requires precise to avoid faults. To manage generator capacity limits, especially during high inrush currents from motor startups, load shedding mechanisms may selectively disconnect non-essential loads, prioritizing critical circuits and preventing overload shutdowns. The timing of the is critical for reliability and is governed by the for total delay: t_{\text{delay}} = t_{\text{start}} + t_{\text{stabilize}} where t_{\text{start}} represents the generator cranking time, typically around 10 seconds, and t_{\text{stabilize}} is the stabilization period for voltage and , generally 5-15 seconds, allowing the alternate to reach steady-state conditions before load application.

Manual vs. Automatic Operation

Transfer switches operate in either or modes, each suited to different levels of user involvement and urgency in power source switching. In operation, the transfer is user-initiated through a physical , , or selector switch, requiring direct human intervention to shift the load between the and sources. These switches typically feature a three-position —utility, off, and —to allow safe disconnection and selection, with the response time depending entirely on the operator's promptness and may take from seconds to several minutes or more. Automatic transfer switches (ATS), in contrast, employ self-sensing capabilities via an integrated controller that monitors power sources for outages, automatically starting the and transferring the load without human input. Upon detecting a failure, the ATS initiates the switch in 10 to 60 seconds, encompassing detection, startup, and load transfer, followed by an automatic retransfer to the once it is restored, often with adjustable delays to ensure stability. These systems include exercise timers for scheduling periodic tests, typically weekly, to maintain readiness and prevent issues from disuse. The primary differences lie in and reliability: manual switches are ideal for cost-sensitive, non-critical applications where immediate response is not , as they avoid complex and offer simplicity. switches, however, provide 24/7 reliability for loads, with lower rates due to built-in , continuous , and fail-safes like overrides in models that combine both modes. While minimizes points, automatics enhance overall dependability through proactive features.

Types

Open Transition Transfer Switches

Open transition transfer switches operate on a break-before-make principle, ensuring complete disconnection from the primary power source before connecting to the backup source, thereby preventing any paralleling of the two sources. This mechanism inherently avoids the risk of out-of-phase connections or fault currents that could damage equipment. These switches typically employ contactors or circuit breakers as the primary switching elements, with control logic that sequences the operation to maintain during transfer. The transfer time is generally brief, often completed in 100 milliseconds or less, allowing quick restoration of without requiring voltage or synchronization between sources. No synchronization equipment is needed, simplifying the design and reducing costs compared to systems that permit momentary paralleling. Open transition switches are particularly suited for residential and light commercial applications where brief power interruptions are tolerable, such as in home generators or setups. By fully isolating the backup source during transfer, they prevent into the utility grid, enhancing safety for utility workers and complying with electrical codes. This type represents the most common configuration for non-critical loads in these settings due to its reliability and affordability. For emergency power systems, open transition transfer switches are commonly certified to UL 1008 standards, which verify their performance in legally required standby applications, including withstand ratings for fault currents and operational integrity under load.

Closed Transition Transfer Switches

Closed transition transfer switches operate on a make-before-break , momentarily paralleling the primary and alternate power sources during load transfer to ensure continuous with minimal disruption. This brief overlap, typically lasting less than 100 milliseconds, requires precise of the sources' voltage, frequency, and angle to prevent faults or damage. The process relies on synch-check relays to and verify that the electrical parameters between the two are within acceptable tolerances before allowing the . If the alternate source is unpowered or unavailable, the switch defaults to dead-bus operation, where it first opens the primary source connection before closing to the unenergized bus, avoiding any paralleling risk. These switches feature dual contactors or circuit breakers equipped with electrical interlocks to control the sequential operation, ensuring safe make-before-break action only under synchronized conditions. They are ideal for applications with loads sensitive to even brief interruptions, such as induction motors, which can experience inrush currents or stalling from power dips. With a transfer time under 100 milliseconds—equivalent to fewer than six cycles at 60 Hz—closed transition switches minimize voltage sags and maintain system stability. They are widely deployed in hospitals to critical equipment like ventilators and imaging systems without power loss. demand for these switches is expanding alongside data center growth, driven by needs for uninterrupted power in high-reliability environments.

Soft Loading Transfer Switches

Soft loading transfer switches represent an advanced variant of closed-transition systems designed for controlled paralleling between a and the source, enabling a gradual ramped load transfer to minimize disruptions during power source changes. In this mechanism, the is synchronized with the in terms of , voltage, and , allowing a brief paralleling period where both sources share the load before the utility is disconnected. This process begins with the generator assuming an increasing portion of the load at a controlled rate, typically ramping up over several seconds, until it fully supports the demand, at which point the utility breaker opens and the generator breaker closes. The core process of soft loading emphasizes inrush suppression through techniques, particularly during retransfer from to , to prevent voltage dips and sudden surges that could affect sensitive . As power restores, the remains paralleled but gradually offloads to the , with current regulators ensuring the occurs without exceeding safe thresholds, over several seconds. This controlled sharing avoids the abrupt load shifts common in simpler transitions, thereby maintaining power quality and stability. Design features of soft loading transfer switches incorporate specialized paralleling gear, such as automatic synchronizers and microprocessor-based controllers, alongside protective relays that monitor synchronization parameters and detect faults to ensure safe operation. These relays provide overcurrent, undervoltage, and reverse power protection during the paralleling phase, complying with standards like IEEE 1547 for grid interconnection to facilitate seamless interaction with distributed energy resources. By reducing mechanical stress on generators through gradual loading—avoiding sudden torque spikes that can shorten engine life—these switches are particularly suited for large commercial and industrial setups, such as data centers and hospitals, where reliable power management and generator exercising without utility interruption are critical.

Static Transfer Switches

Static transfer switches (STS) utilize solid-state devices, primarily silicon-controlled rectifiers (SCRs) or thyristors, to enable rapid switching between power sources without mechanical components. These devices form bidirectional switches that conduct current in both directions when triggered, allowing for seamless in a of an electrical . Unlike mechanical alternatives, STS eliminate arcing and wear, providing reliable operation for critical loads. The operation of an STS involves dual conductive paths, one for each power source, where high-speed gating circuits monitor voltage, frequency, and to detect anomalies in the preferred source. Upon detection of a fault, such as undervoltage or loss, the system commutates the load current by turning off the SCRs in the failing path and activating those in the alternate path, achieving transfer times of 4 to 8 milliseconds—typically a quarter to half cycle at 60 Hz. A mechanism ensures automatic retransfer to the preferred source once it stabilizes, prioritizing it as the default for normal operation. Design features of include advanced control logic with high-speed gates for precise source selection and commutation, often integrated with redundant microprocessors for . Heat dissipation is managed through air-cooling systems, such as fans for higher-current models or cooling for lower ratings, to handle the load from SCR conduction losses. Current ratings typically range from 150 A to 4000 A, supporting three-phase configurations up to 600 V, with overload capacities exceeding 150% for short durations. STS are particularly suited for and environments, where even brief power interruptions can cause significant , ensuring continuity for servers and networking equipment. The technology's adoption is expanding alongside infrastructure deployments, which drive increased capacity and demand for ultra-reliable , contributing to market growth projected at a 5.4% CAGR from 2025 to 2032. Compared to types, STS require minimal maintenance due to the absence of , with hot-swappable components and front-access designs facilitating service without system shutdown.

Applications

Residential and Home Use

In residential settings, transfer switches are essential for safely connecting portable or small standby s, typically rated from 5 to 20 kW, to a home's electrical system during power outages. These setups often feature manual transfer switches or basic automatic transfer switches (ATS) that link the generator to a subpanel dedicated to essential circuits, such as lighting, refrigerators, freezers, and pumps, ensuring the 's limited is not exceeded. For instance, load center transfer switches can power 8 to 16 critical circuits, allowing selective backup without affecting the entire home. Installation of residential transfer switches commonly involves interlocked breakers, which mechanically prevent the utility and breakers from being on simultaneously, or external power inlet boxes for portable connections via extension cords. These methods require professional to comply with the () Article 702, which mandates transfer equipment for optional standby systems to avoid unintended interconnections between power sources, ensure adequate capacity for connected loads, and include audible/visual indicators and signage for safe operation. 702 specifically applies to non-mandatory residential backup systems, emphasizing grounding, wiring, and documentation to mitigate hazards like backfeeding the grid. The primary benefits of residential transfer switches include cost-effective outage management by enabling seamless power transfer to hardwired appliances, such as water heaters or well pumps, while eliminating the dangers of extension cords and overloads. They integrate reliably with home standby generators, like those from , where models such as the HomeLink switch support 8-10 essential circuits for quick manual activation during blackouts. As of 2024, approximately 14% of U.S. households have backup generators, with transfer switches serving as a standard safety component in these installations to protect utility workers and home electronics. Average installation costs range from $400 to $2,500, covering the unit, labor, and any necessary subpanel modifications, making them an accessible option for homeowner preparedness.

Commercial and Industrial Applications

In commercial settings such as office buildings and hotels, automatic transfer switches (ATS) are widely deployed to ensure continuity of essential operations during power outages, typically supporting load capacities ranging from 100 kW to 1000 kW. These systems automatically detect utility power failure and switch to backup generators within seconds, powering like HVAC systems, elevators, lighting, and security equipment to minimize disruptions to business activities. For instance, in multi-story office complexes, ATS units rated at 100-1000 A, typically handling loads from tens to hundreds of kW depending on voltage and , facilitate seamless transitions, preventing financial losses from in revenue-generating environments. Emerging uses include backup for EV charging stations and , supporting reliable power for and data demands as of 2025. In applications, particularly factories and facilities, closed-transition and static transfer switches are preferred to avoid any interruption that could halt lines and cause equipment damage or delays. Closed-transition switches, also known as "make-before-break" types, briefly parallel the utility and backup sources during transfer, ensuring zero downtime for sensitive machinery such as assembly robots or conveyor systems. Static transfer switches (STS), utilizing , switch loads in milliseconds—often under 4 ms—making them ideal for high-reliability needs where even brief outages could result in significant losses, as seen in automated environments. Transfer switches in these sectors often integrate with load banks for periodic testing and bypass mechanisms to enable without operational interruptions. Load banks simulate real-world electrical loads during generator exercises, verifying system performance and preventing issues like in diesel engines, which is crucial for industrial reliability. Bypass switches allow the main ATS to be isolated for servicing while routing power through an alternate path, ensuring continuous operation— a standard practice in facilities requiring 24/7 uptime, such as manufacturing plants. Notable examples include hospitals, where UPS-linked static transfer switches provide redundant power paths to critical systems like life-support equipment and operating rooms, automatically between UPS outputs or s to maintain uninterrupted supply. In the sector, transfer switches paired with auto-start capabilities ensure that stores and shopping centers keep point-of-sale systems, , and operational, automatically initiating backup power upon outage detection to avoid impacts from closures. The commercial and industrial sectors represent a substantial portion of the transfer switch , driven by the need for reliable in mission-critical operations. Global market analyses indicate that in these areas is growing steadily, with the overall transfer switch valued at approximately USD 2.6 billion in 2024 and projected to expand at a 6% CAGR through 2034, fueled by expansions in commercial . Additionally, rising e-commerce activities have increased the need for robust backup systems in warehouses, contributing to segment growth as facilities scale to handle higher and 24/7 logistics demands.

Integration with Renewables and Smart Grids

Transfer switches play a crucial role in integrating sources, such as photovoltaic (PV) systems and battery storage, with the by enabling seamless switching between these distributed energy resources (DER) and utility power. In typical setups, an automatic transfer switch (ATS) detects grid outages and shifts loads to inverters or battery backups, ensuring continuous power supply without manual intervention. For instance, devices like the PWRcell 100 Amp ATS are designed specifically for whole-home integration with and storage systems, facilitating the transition from grid-tied operation to off-grid mode during disruptions. A key safety feature in renewable-integrated transfer switches is anti-islanding protection, which prevents DER from energizing downed power lines and endangering utility workers. This is achieved through rapid disconnection of the renewable sources from upon detecting abnormal conditions, such as voltage or deviations, as mandated by standards like IEEE 1547-2018. The standard requires DER interconnections, including those involving transfer switches, to cease energizing within two seconds of an outage to avoid unintentional islands. In practice, hybrid systems incorporate relays or controls in the ATS to monitor and isolate inverters and batteries, ensuring compliance and enhancing system reliability. Advancements in technology have led to IoT-enabled transfer switches that provide real-time monitoring and remote control via mobile apps, optimizing in renewable setups. These intelligent ATS units communicate with smart meters and inverters to track power flows, status, and conditions, allowing users to performance and receive outage alerts. Furthermore, demand-response capabilities enable these switches to participate in stabilization efforts, such as peak shaving, by automatically shedding non-essential loads or prioritizing renewable sources during high-demand periods. For example, FranklinWH's smart transfer switch integrates with home systems to support utility-directed load control, reducing strain on the while maximizing renewable utilization. Design adaptations for renewables include hybrid ATS configurations that pair directly with inverters for , supporting bidirectional power flow and grid export from excess production. These systems comply with IEEE 1547 by incorporating features like ride-through capabilities, allowing brief grid disturbances without disconnection to improve stability. The market for renewable-compatible transfer switches is driven by global net-zero emission goals, with the overall transfer switch sector projected to grow at a 5.4% CAGR from 2025 to 2033, fueled by increasing adoption of and storage integrations. In applications, such switches enhance off-grid resilience by isolating segments of the network during outages, enabling self-sustaining operation on local renewables and batteries for critical facilities like remote communities or data centers.

Safety, Standards, and Maintenance

Safety Features and Considerations

Transfer switches incorporate several built-in safety features to protect users, equipment, and the . and electrical interlocks are essential components that prevent unintended paralleling of power sources, such as and power, which could lead to damaging fault currents or system instability. technologies, including arc-resistant enclosures and rapid fault interruption mechanisms, help reduce the risk of explosive releases during switching operations, particularly in high-voltage applications. Ground-fault protection relays detect and interrupt imbalanced currents to ground, preventing potential shocks or fires in fault conditions, as recommended in standards like NFPA 70. Despite these protections, certain risks remain associated with transfer switch operation. Backfeed occurs when generator power inadvertently energizes the utility grid, posing hazards to line workers who may assume de-energized lines during outages; transfer switches mitigate this by isolating sources, but improper installation can still enable it. Overloads from undersized s can cause voltage instability, overheating, and fire risks, as the transfer switch may attempt to handle loads exceeding the source's , leading to or . To address these hazards, transfer switches employ designs that prioritize utility power as the default source, automatically reverting upon its restoration to avoid prolonged reliance on potentially unstable generators. Enclosures are typically rated for (e.g., NEMA types) to shield against accidental contact, while mandatory warning labels alert users to hazards like backfeed risks, as required by codes such as Article 702.7. For life-safety systems, Article 700 mandates the use of listed transfer switches to ensure reliable emergency power transfer without compromising critical loads like egress lighting or fire alarms.

Industry Standards and Regulations

Transfer switches must comply with established industry standards to ensure safety, reliability, and interoperability in power systems. In , UL 1008 serves as the foundational standard for transfer switch equipment, specifying requirements for construction, performance, and testing of automatic, manual, and bypass-isolation transfer switches rated up to 1000 volts AC. This standard mandates rigorous evaluations, including endurance testing at 100% rated load for a specified number of transfer cycles to verify long-term operational integrity under full load conditions. Compliance with UL 1008 is essential for listing and , confirming that the entire assembly withstands electrical stresses without failure. For synchronization in closed-transition applications, IEEE C37.95 provides guidance on protective for utility consumer systems, addressing coordination between sources to prevent out-of-phase switching that could damage equipment. This outlines relay settings and practices to achieve safe paralleling during brief overlap periods, typically limited to 100 milliseconds. Internationally, IEC 60947-6-1 governs transfer switching equipment using contactors, defining classifications based on short-circuit withstand capability and operational categories (e.g., AC-31B for circuits). It requires testing for making and breaking capacities, ensuring of supply with minimal interruption, and applies to devices up to 1000 volts AC. Regulatory frameworks further enforce these standards. In the United States, the (NEC) Articles 700, 701, and 702 delineate requirements for emergency systems (Article 700), legally required standby systems (Article 701), and optional standby systems (Article 702), mandating dedicated transfer equipment, selective coordination, and automatic operation within 10 seconds for critical loads. Non-compliance with NEC provisions can result in fines up to $50,000 per violation in certain jurisdictions, alongside potential shutdowns or legal liabilities. For exports to the , the Low Voltage Directive 2014/35/EU harmonizes safety requirements for electrical equipment operating between 50 and 1000 volts AC, necessitating and conformity assessments that incorporate standards like IEC 60947-6-1. Recent updates emphasize integration with modern power systems. The IEEE 2030 series, with recent updates such as IEEE 2030.4-2023, addresses interoperability, including guidelines for distributed energy resources (DER) and transfer switch roles in microgrids, promoting bidirectional power flow and . Cybersecurity has gained prominence for IoT-enabled transfer switches, with the 2023 NEC (section 110.3(A)(8)) requiring assessments and protocols to mitigate vulnerabilities in networked controls, aligning with broader NIST frameworks for security. These evolutions ensure transfer switches support renewables and digital grids while upholding interlocks.

Installation, Maintenance, and Testing

Proper installation of a transfer switch begins with careful site selection to ensure adequate ventilation and accessibility, as the device generates heat during operation and requires a dry, temperature-controlled environment away from extreme conditions to prevent overheating or corrosion. According to the National Electrical Code (NEC), wiring must comply with Article 702 for optional standby systems, including proper conductor sizing, grounding, and conduit usage; for three-phase systems, a four-pole transfer switch may be necessary to handle neutral switching when separate grounding is required at the generator site to avoid objectionable current flow. Installation should always be performed by a licensed professional electrician to meet NEC requirements and ensure safety, as improper setup can lead to electrical hazards or code violations. Maintenance of transfer switches involves routine checks to preserve reliability, starting with monthly visual inspections for signs of wear, loose connections, or contamination on wiring and components. Annual under simulated conditions verifies full operational integrity, while mechanical parts, such as actuators and contacts, require every two years or as specified by the manufacturer to reduce and extend . Modern transfer switches often include logging features that track over 10,000 transfer cycles, aiding in . Professional service contracts typically cost $200-500 annually, covering inspections, testing, and minor repairs to maintain warranty compliance. Testing protocols ensure the transfer switch responds correctly during emergencies, beginning with simulated power loss transfers to confirm seamless switching between sources. Timing verification is critical, particularly for automatic transfer switches (ATS) in critical applications, where the total transfer time must be under 10 seconds as per NFPA 110 Level 1 requirements to minimize downtime for life-safety systems. Continuity checks using a multimeter across poles and connections detect faults like open circuits or poor contacts, with resistance values compared against manufacturer baselines to ensure reliable performance. With proper upkeep, transfer switches have a recommended lifespan of 20-30 years, though actual longevity depends on usage frequency and environmental factors.

References

  1. [1]
    [PDF] Transfer switch 101 - Eaton
    Transfer switches are responsible for quickly and safely transitioning all electrical power consumed by the circuit, equipment, or systems connected to the ...
  2. [2]
    Automatic transfer switches (ATS) fundamentals - Eaton
    An automatic transfer switch (ATS) is a self-acting, intelligent power switching device governed by dedicated control logic.
  3. [3]
    What is a Transfer Switch? Types and Applications | Cummins Inc.
    One key consideration is how the switch is triggered. There are three main types of triggering mechanisms: manual, non-automatic and automatic. What are manual ...
  4. [4]
    [PDF] Transfer Switches: What to Specify and Why | Cummins
    Sep 14, 2021 · This course is intended to provide participants with an overview of performance-based requirements related to transfer switches. Participants ...
  5. [5]
    What Is a Transfer Switch and Why Is It Important for Your Generator?
    Dec 28, 2024 · Enhanced Safety: By preventing backfeeding, a transfer switch eliminates the risk of electrical hazards for utility workers and your household.
  6. [6]
    Use Caution When Using Back-Up Generators - Safe Electricity
    A permanently installed standby generator must have an approved transfer safety switch to avoid feeding electricity back into the electrical system outdoors, ...
  7. [7]
    What Is an Automatic Transfer Switch - Thompson Power Systems
    A transfer switch is a device that connects equipment to backup power when a primary power source fails.
  8. [8]
    Optional Standby Generator Systems: A Practical Guide to NEC ...
    Jun 23, 2025 · All optional standby systems require transfer equipment, whether the system is portable or permanently installed. Here's what the NEC requires:.
  9. [9]
    [PDF] Transfer switch solutions ( en - ABB
    Available safety features include mechanical isolation of unsynchronized power sources, manual emergency operation, and protection from current-carrying.
  10. [10]
    Understanding transfer switch operation - Consulting
    Dec 3, 2015 · Transfer equipment shall be designed and installed to prevent inadvertent, simultaneous connection of primary and secondary supplies of power.Missing: unsynchronized | Show results with:unsynchronized
  11. [11]
    The Basics of Selecting Transfer Switches | Wolter Inc
    A transfer switch is a device used for transferring power from one source to the other. The two sources can be defined as being similar sources of power (two ...Introduction · Determining The System... · Ways Transfer Switches...
  12. [12]
    Choosing The Right Transfer Switch For Your Home
    Safety: The use of a transfer switch provides protection from backfeeding. · Code Compliance: Many local building codes require transfer switches for generator ...Missing: prevent | Show results with:prevent
  13. [13]
    Antique automatic transfer switch? 1920s - Mike Holt's Forum
    Sep 1, 2022 · Hi All, A partner of mine saw a de-commissioned automatic transfer switch a while back, and now I'm trying to find more info online, ...
  14. [14]
    History - G&W Electric
    1920 – 1960. Introduced manual oil switches in 1922, automatic transfer switches in 1927 and introduced an oil fused cutout designed for protection of 5 kV ...
  15. [15]
    100 Years of Power Source Switching & Controls - Schneider Electric
    Since 1925, the Automatic Transfer Switch has been the cornerstone of ASCO's commitment to reliability and expertise. ASCO has pioneered advancements in ...
  16. [16]
    Cummins adds to their line of UL1008 transfer switches with the ...
    Mar 13, 2023 · With more than 80 years of experience, the PowerCommand® B-Series continues Cummins' rich history in power transfer control. More than a ...
  17. [17]
    Cummins Power Generation turns 100
    Mar 2, 2020 · Cummins celebrates 100 years in Power Generation. It all started with the incorporation of Onan Corporation in 1920 – a family owned business founded by David ...
  18. [18]
    The 1973 Oil Crisis: Three Crises in One—and the Lessons for Today
    Oct 16, 2023 · The 1973 oil embargo shook the global energy market. It also reset geopolitics, reordered the global economy, and introduced the modern energy era.Missing: switches | Show results with:switches
  19. [19]
    advances in high speed solid-state transfer switches for critical ...
    While the STS has been commercially available since 1971, advances in the sensing of power anomalies and in the control of SCRs have provided enhanced power ...Missing: thyristors | Show results with:thyristors
  20. [20]
    X-Series Transfer Switch Series | Cummins Inc.
    Apr 29, 2021 · The control displays the current active fault, fault occurrences and time-ordered history of the 256 previous faults with respect to Real Time ...
  21. [21]
    [PDF] Low-voltage contactor type transfer switches design guide - Eaton
    Estimated Transfer Switch Life Expectancy. Transfer. Switch Rating. (Amperes). 52 Transfer/Retransfer Operations per Year. With Current. (Years). Without ...
  22. [22]
    What are the key components of a Transfer Switch Mechanism?
    Feb 23, 2022 · Key components include electrical contacts, solenoid-driven operators, arc chutes, arcing contacts, main contact shafts, pole cover, and ...Missing: mechanical | Show results with:mechanical
  23. [23]
    Design Guide for bus bars - Mersen
    Common materials used are copper, aluminum, and a variety of copper alloys. The material chosen, the mechanical constraints and the electrical performance ...<|separator|>
  24. [24]
    [PDF] Automatic transfer switch (ATS)— contactor-based - Eaton
    Contactors rated 600A and above include separate moveable arcing contacts that will make first and break last . 400A Arc Chute. Separate Arcing Contacts Extend ...
  25. [25]
    Monitoring relays | Phoenix Contact
    EMD monitoring relays can be used to monitor overvoltage, undervoltage, overcurrent, undercurrent, phase failure, phase sequence, phase asymmetry, power factor, ...
  26. [26]
    [PDF] Design and development of a low cost automatic transfer switch ...
    The controller is configured with generator cool down timer, generator warm up timer, loss of power delay timer, generator fail to start timer, generator crank ...
  27. [27]
    [PDF] Automatic transfer switch controller, ATC-300+ operation ... - Eaton
    Transfer is defined as a change of the load connection from the source 1 to the source 2 power source, except when specifically used as “Transfer to Neutral”. ...
  28. [28]
    [PDF] TRANSFER SWITCH DETAILS - Woodstock Power
    1. 11BE. Adds the following features to the Group G controller: (1) Serial RS-485 Modbus. Communications (2) Multi-Schedule Engine Exerciser (3) a 300 Entry ...
  29. [29]
    ATL610 | Automatic transfer switch controllers - LOVATO Electric spa
    Automatic transfer switch controller for 2 power sources, three phase control, with LCD display, 110…240VAC supply and 12-24VDC, expandable. Product type ...
  30. [30]
    [PDF] White Paper Basic Control of Automatic Transfer Switches
    This paper describes how controllers monitor voltage, frequency, and phase angle differences between Normal and Emergency power sources, and explains how timing ...<|control11|><|separator|>
  31. [31]
    Load Shedding for Generator Cutover and Peak Shaving - LynTec
    In a standard emergency generator installation an automatic transfer switch (ATS) is responsible for sensing a commercial power failure, starting the generator ...
  32. [32]
    ASCO Power Technologies ASCO Series185 Automatic Transfer ...
    Wait approximately 10 seconds for the transfer to generator time delay. This fixed delay allows the generator output to stabilize before a load is applied to it ...
  33. [33]
    [PDF] Closed Transition Soft Load Transfer Switches - Eaton
    Jan 4, 2001 · Following an adjustable time delay to allow the generator to stabilize (TDNE), the generator bus will be synchronized to the utility across the ...<|control11|><|separator|>
  34. [34]
    Manual vs. Automatic Transfer Switch: Which One Should You Install ...
    Reliability: Automatic switches are more reliable because they offer more sophisticated monitoring, while manual switches check for fewer points of failure. ...
  35. [35]
    Power Outage! How Long it Takes for a Generator to Start
    Jun 4, 2018 · The entire transfer process from the detection of a power outage to the generator supplying power can take anywhere from 10 to 20 seconds.
  36. [36]
    How to set the engine exerciser on Series 300 Transfer Switch with ...
    Aug 5, 2021 · Provides seven individually programmable exercise schedules. Duration or Run Time can be set up to 24 hours. Exercise Parameters Parameters ...
  37. [37]
    Choosing Between Automatic and Manual Transfer Switches for ...
    Nov 13, 2024 · Transfer switches are available in two main types: Automatic Transfer Switches (ATS). Manual Transfer Switches (MTS). Each of these types ...
  38. [38]
    What are the different ASCO ATS transition modes?
    Aug 18, 2021 · In this Open Transition mode, switching mechanisms operate in a “break-before-make” sequence. The switching contact positions and the ...
  39. [39]
    Brand Feature: Specifying the Right Transfer Switch - Facilitiesnet
    Open-Fast-Transition No Sync are typically completed in 100ms or less. Typical applications for this mode are resistive loads. Automatic hard-closed transition:.
  40. [40]
    Automatic Transfer Switches: Everything You Need to Know - EIYU
    Jun 20, 2025 · Open transition is the most common type used in residential and light commercial systems. When the utility fails, it disconnects from the load ...
  41. [41]
    What is a Transfer Switch? | Schneider Electric United States
    A transfer switch is a device designed to transfer electrical loads between power sources, such as utility power and generator power.
  42. [42]
    The Ultimate Guide to Automatic Transfer Switches (ATS) - GRL FUSE
    Aug 13, 2025 · Load Transfer: Once the generator reaches the correct voltage and frequency—a process that typically takes 10-30 seconds—the ATS opens the ...
  43. [43]
    Contactor type automatic transfer switches - Eaton
    Eaton's automatic transfer switches (ATS) are UL 1008 listed for use in emergency, legally required, COPS or standby power systems and designed to transfer ...
  44. [44]
    ATYS UL 1008 Non-automatic transfer switch - from 100 A to 1200A
    The ATYS UL 1008 is a durable, non-automatic transfer switch for safe power transfer, with open transition, failsafe interlock, and manual operation.
  45. [45]
    Considerations when installing a Closed Transition Transfer Switch
    Aug 29, 2023 · Most utilities will approve a CTTS with an overlap condition of less than 100ms, provided comprehensive design documentation is submitted and ...Missing: threshold typical
  46. [46]
    [PDF] Magnum Closed Transition Soft Load Transfer Switches - Eaton
    Transfer switches are used to protect critical electrical loads against loss of power. The Source 1 power source of the load is backed-up by a Source 2 power ...
  47. [47]
    Should transfer switch be equipped with contactors or circuit breakers?
    Nov 7, 2024 · Figure 1 – Automatic transfer switch, contactor type. Advantages ... For many applications, including emergency, critical operations ...
  48. [48]
    [PDF] Automatic Transfer Switch, Bypass Isolation, Contactor Type ... - Eaton
    All switching devices are 100% rated, Underwriters Laboratories. (UL) 1008 listed, and are built and tested in an ISO 9002 certified facility to applicable NEMA ...<|control11|><|separator|>
  49. [49]
    Data Center Switch Market Size, Share | Report [2035]
    According to recent estimates, the number of data centers is expected to grow by 15% annually, necessitating the deployment of advanced switching solutions.
  50. [50]
    [PDF] Guidelines for ATS selection - Incal
    Advantages of closed-transition transfer switches with active synchronizing include: • Synchronizing is more accurate and power transfers occur more rapidly. • ...
  51. [51]
    Keep an Open Mind About Closed Transition - Power Engineering
    May 1, 2007 · Closed transition transfer momentarily parallels distributed generation and utility power when both sources are hot. The transfer switch ...
  52. [52]
    [PDF] Paralleling switchgear - Kohler
    The load is without power for the duration of the open-transfer time delay. ExAMPLE open transfer from generator power to utility power after a power outage.
  53. [53]
    Static Transfer Switches (STS) for Data Centers - LayerZero
    Rating 4.9 (27) A Static Transfer Switch (STS) is a fast, solid-state device that automatically switches power between two or more sources without interrupting the load. It ...Missing: 8ms | Show results with:8ms
  54. [54]
    [PDF] Eaton® WaveStar Static Transfer Switch 150A-1600A
    When evaluating low inrush algorithms, the peak current during transfer is the most critical measure of performance. The Eaton PDI VSS method provides the ...
  55. [55]
  56. [56]
    Automatic Transfer Switch Buyer's Guide - How To Pick the Perfect ...
    You cannot run a home standby generator without an automatic transfer switch (ATS). Learn all about automatic transfer switches in our buyer's guide.
  57. [57]
  58. [58]
    Why a Generator Needs a Transfer Switch - Consumer Reports
    Jan 11, 2024 · A transfer switch will let you power things on your circuit breaker panel, including hardwired appliances like a water heater or well pump.Missing: residential | Show results with:residential
  59. [59]
    Optional Standby Systems - UpCodes
    Article 702 Optional Standby Systems​​ Additionally, it specifies the use of transfer switches, documentation requirements, and the necessity for audible and ...
  60. [60]
  61. [61]
    2025 Generator Transfer Switch Installation Cost - HomeGuide
    Apr 5, 2023 · The cost to install a generator transfer switch is $400 to $2,500 on average for the unit and labor. An automatic transfer switch costs $400 to ...
  62. [62]
    Industrial Transfer Switches and Controllers | 100-1000A SE Rated
    The Power Series Transfer Switch line features 3 different platforms with multiple technologies to offer the most flexible solutions up to 5,000 AMPs. All ...
  63. [63]
    Automatic Transfer Switch (ATS) Comprehensive Guide
    Jun 5, 2025 · Commercial Applications. Office buildings use ATS to protect essential equipment. They protect computers and security systems. Automatic ...Switching Mechanism · Types Of Ats · Key Performance Indicators...
  64. [64]
    Transfer Switches in the Real World: 5 Uses You'll Actually See (2025)
    Oct 8, 2025 · Office complexes and retail centers use transfer switches to keep essential systems operational during outages. This includes lighting, security ...
  65. [65]
    Managing risks, benefits with closed transition transfer switches
    Jan 7, 2014 · Here are best practices for closed transition transfer switches when two live sources are connected together.
  66. [66]
    Static Transfer Switch vs Automatic Transfer Switch Explained
    Closed transition modes are popular because they switch power smoothly. ... Factories depend on ATS to keep production going and prevent equipment damage.Missing: halts | Show results with:halts
  67. [67]
    How Static Switches Ensure Uninterrupted Operations
    Nov 6, 2024 · Static switches play an essential role in ensuring this continuity by facilitating a seamless transfer of electrical loads from one power source to another.The Need For Power... · How Static Switches Ensure... · Applications Of Static...Missing: history | Show results with:history
  68. [68]
    Generator Load bank | Testing And Verifying Power Equipment
    Electrical load bank testing for generators. Portable or permanent load banks for testing, verifying and exercising critical backup power generator systems.
  69. [69]
    [PDF] BYPASS ISOLATOR SWITCHES USED IN POWER GENERATION ...
    When the generator is isolated by another switch from the load circuitry during testing, a Bypass isolator switch switches the generator's ATS to the load bank ...
  70. [70]
  71. [71]
    Static Transfer Switch (STS) - SOCOMEC USA
    Static switches in UPS systems are smart and easy-to-integrate devices that operate automatically when a power outage occurs to ensure permanent power ...
  72. [72]
    8 Types Of Automatic Transfer Switch And Their Uses - Radin
    Aug 12, 2025 · Common Applications · Light Commercial Power Panels: Used in small office buildings and retail shops. Supports basic lighting and equipment loads ...2. Closed Transition Ats · 6. Static Transfer Switch... · 8. Circuit Breaker Type Ats<|separator|>
  73. [73]
    Transfer Switch Market Size, Growth Analysis 2025-2034
    The global transfer switch market was valued at USD 2.6 billion in 2024 and is estimated to grow at a CAGR of 6% from 2025 to 2034, driven by the rising ...Missing: 5G | Show results with:5G<|control11|><|separator|>
  74. [74]
    Transfer Switch Market Size, Industry Share | Forecast [2025-2032]
    Transfer Switch Market report summaries detailed information by top players as GE, Generac Power Systems, Siemens, Briggs & Straton, among others.
  75. [75]
    Transfer Switch Market | Global Market Analysis Report - 2035
    Aug 14, 2025 · Transfer Switch Market was worth USD 3.1 billion in 2025, and is predicted to grow to USD 5.5 billion by 2035, with a CAGR of 6.0%.
  76. [76]
  77. [77]
    [PDF] Prevention of Unintentional Islands in Power Systems with ... - NREL
    • Anti-islanding (non-islanding protection) – The use of relays or controls to prevent the continued existence of an unintentional island. Terms. Page 4. 4.
  78. [78]
  79. [79]
    [PDF] Anti - islanding Tech Brief | FranklinWH
    A positive feedback is utilized to prevent islanding. How does FranklinWH do it? Franklin Home Power (FHP) system includes a smart transfer switch, referred to ...<|separator|>
  80. [80]
    Automatic Transfer Switch: From Basic to Intelligent Control
    Mar 3, 2025 · An ATS is a self-acting, intelligent device that ensures uninterrupted power supply to electrical systems by automatically transferring the home loads.
  81. [81]
    Transfer Switch Market Size, Growth and Forecast 2025-2033
    $$1,820,000,000.00The global transfer switch market size was valued USD 1.82 Billion in 2024 to reach USD 2.91 Billion by 2033 at a CAGR of 5.4% during 2025-2033.Missing: e- | Show results with:e-
  82. [82]
    Microgrid Interconnection - Mayfield Renewables
    Aug 14, 2025 · Therefore, using a transfer switch and connecting the PV and ESS to the terminal that would typically house the generator would eliminate the ...
  83. [83]
    [PDF] Microgrids for Energy Resilience: A Guide to Conceptual Design ...
    Some transfer switches have the capability of. “fast” transfer of sources from the diesel generator to the grid in a “seamless” fashion, when both sources ...
  84. [84]
    Arc flash reduction method | Electric hazards | Arc fault - Eaton
    Bypass isolation automatic transfer switch (ATS). Improve safety and reduce arc-flash hazards, including dedicated wireway and safety barriers isolating ...
  85. [85]
    Why you should never back-feed your electric panel with a generator
    Sep 4, 2025 · Why backfeeding is dangerous: · Electrocution risk: Utility workers repairing lines may assume the lines are de-energized. · Fire and equipment ...
  86. [86]
    What Effects Will an Overload of an Automatic Transfer Switch Have ...
    Jul 11, 2025 · An overloaded ATS can cause unstable power switching, voltage sags, reduced lifespan, fire risk, and increased operating costs.Missing: ground | Show results with:ground
  87. [87]
    [PDF] EATON ATC-300+/900 Breaker Based Transfer Switch
    All Feature 26 monitoring and protection functions are “fail- safe” operations. ... All vertical design ATS equipment enclosures and power panels are of the same ...
  88. [88]
    Generator interlock / Transfer Switch Caution Labels NEC Article 702.7
    In stock Free deliveryGenerator interlock / Transfer Switch Caution Labels NEC Article 702.7. SKU: ACC-S1. Caution label: This label is required for all standby or portable ...
  89. [89]
    [PDF] National Electrical Code - LightAlarms
    Automatic transfer switches, rated 600 VAC and below, shall be listed for emergency system use. (d) Use. Transfer equipment shall supply only emergency loads.
  90. [90]
    UL 1008 | UL Standards & Engagement
    Jul 13, 2022 · 1.1 This standard applies to the following types of transfer switches ... a) Automatic transfer switches;. b) Manual or non-automatic transfer ...
  91. [91]
  92. [92]
    IEC 60947-6-1:2021
    Mar 16, 2021 · IEC 60947-6-1:2021 applies to transfer switching equipment (TSE), to be used in power systems for ensuring the continuity of the supply.
  93. [93]
    National Electrical Code Articles 701 and 702 Legally Required and ...
    Dec 2, 2020 · There must be a transfer switch so that the service and the alternate source of power cannot operate simultaneously. · Signage is required to ...
  94. [94]
    Electrical Safety Penalties and Sanctions
    Class C Violations. Penalty: Fine between $2,000 to $5,000 plus one year probated suspension up ... not in compliance with the National Electrical Code adopted by ...Missing: 50000 | Show results with:50000
  95. [95]
    Evolving IEEE Standards Foster a More Sustainable Power Grid
    Mar 22, 2024 · The IEEE 2030™ series aims to accelerate smart grid design, development, and deployment, in the context of a large penetration of DER based ...
  96. [96]
    NEC 2023 | Electrical Safety | Cybersecurity - Eaton
    The NEC 2023 cybersecurity requirements are great step forward to standardize cybersecurity and safety across the entire electric industry.
  97. [97]
    A Comprehensive Guide of Installing a Transfer Switch - CSQ Electric
    Avoid placing it in cramped or hard-to-reach areas. * Ventilation and Temperature: Install the switch in a well-ventilated area away from extreme temperatures ...Safety Precautions · Tools And Materials Needed · Installation Process
  98. [98]
    [PDF] Owner's Manual Automatic Transfer Switch - Generac
    marked on the exterior of the transfer equipment. For. NEC compliance, verify the required short-circuit current rating of the transfer switch before ...
  99. [99]
    Effective Ways to Maintain a Transfer Switch - Leddy Power Systems
    Apr 14, 2023 · A transfer switch should undergo monthly and annual testing to confirm its proper operation. ... Regular visual inspections, cleaning, and ...
  100. [100]
    Best Practices for Automatic Transfer Switches Operation and ...
    An automatic transfer switch (ATS) is a device that allows safe transfer of electricity from a primary source, usually an electric-utility grid, to a backup ...Missing: definition | Show results with:definition
  101. [101]
    TA16D4S1254TPE - Automatic Transfer Switch - Schneider Electric
    Specifications ; Switch: 800 V · Controller: 500 V · Switch: 8 kV. Controller: 6 kV · 125 A · With mechanical interlocking · 10000 cycles.
  102. [102]
  103. [103]
    Transfer Switch Testing and Maintenance Guide - Articles
    Aug 14, 2016 · A minimum time delay of 5 minutes should be provided for the unloaded running of the EPS prior to shutdown to allow for engine cool down (NFPA ...
  104. [104]
    Power Switch: What Does NFPA 110 Say About Transfer Switches?
    An automatic transfer switch (ATS) is used to transfer load to the EPS during a power outage – and back again, once power returns.
  105. [105]
    What is the life expectancy of automatic transfer switch?
    Nov 21, 2024 · The life expectancy of an automatic transfer switch (ATS) is generally around 20 to 25 years under normal operating conditions.