Dissolved gas analysis (DGA) is a diagnostic used to examine the composition of gases dissolved in the insulating oil of electrical equipment, particularly mineral oil-immersed power transformers, to detect and identify incipient faults such as thermal degradation, partial discharges, and arcing before they lead to equipment failure. This method relies on the principle that electrical and thermal stresses cause the breakdown of oil and cellulose insulation materials, generating specific combustible and non-combustible gases that dissolve into the oil. The primary gases analyzed in DGA include hydrogen (H₂), methane (CH₄), ethane (C₂H₆), ethylene (C₂H₄), acetylene (C₂H₂), carbon monoxide (CO), and carbon dioxide (CO₂), with oxygen (O₂) and nitrogen (N₂) providing context for contamination or sampling issues. These gases are extracted from oil samples using standardized procedures, such as headspace extraction or vacuum methods, and quantified via for precise concentration measurements. Interpretation of results employs various approaches, including key gas analysis, ratio methods (e.g., Rogers or Doernenburg ratios), graphical tools like the Duval Triangle, and trending of gas generation rates to classify fault types and severity. DGA's importance lies in its sensitivity for early fault detection, enabling that extends lifespan, reduces downtime, and enhances grid reliability in the power industry. International standards guide its application, with IEEE C57.104 (2019) emphasizing gas trends, individual gas concentrations using percentile-based limits for normal operation, and generation rates to assess conditions (e.g., concentrations above 35 typically indicate serious arcing faults), while IEC 60599 (2022) focuses on ratio-based fault identification. Regular sampling—often annually or more frequently based on risk—combined with online monitoring systems, has made DGA a cornerstone of health management worldwide.

Overview

Definition and Purpose

Dissolved gas analysis (DGA) is the examination of gases dissolved in the insulating fluids of electrical equipment, such as power transformers, to identify early indicators of internal faults including and arcing. This diagnostic technique involves extracting and measuring these dissolved gases to assess the condition of the equipment. The primary purpose of DGA is to serve as a preventive tool that detects incipient faults, such as partial discharges, overheating, or breakdown, thereby averting catastrophic failures in power systems. By enabling early intervention, DGA supports informed decision-making for equipment and operation, enhancing overall system reliability. At its core, DGA operates on the principle that gases are produced through , electrical, or chemical of the insulating oil and associated materials, which then dissolve into the fluid and can be subsequently extracted for evaluation. This process allows for non-destructive monitoring of equipment health without interrupting service. Key benefits of DGA include its cost-effectiveness and non-invasive nature, which facilitate routine assessments that extend the operational life of transformers and reduce the risk of unplanned outages in electrical networks. As a widely adopted method, it provides actionable insights into potential issues before they lead to significant damage.

Historical Development

The analysis of gases dissolved in transformer oil emerged from early 20th-century investigations into electrical breakdowns in insulating fluids, with initial observations of combustion gases under electrical stress documented in 1919. By the 1920s, the focus shifted to practical detection, highlighted by the 1921 invention of the Buchholz relay in Germany for collecting gas bubbles in oil-filled transformers during faults. Systematic discussions of gas collection and analysis for failure diagnostics appeared by 1928, laying the groundwork for what would become dissolved gas analysis (DGA) as a tool for identifying incipient faults. DGA was formalized in the and through advancements in analytical techniques, particularly , which allowed for the precise measurement of individual dissolved gases like , , and originating from faults. During this era, methods using mercury pumps were developed between 1966 and 1970, and portable total combustible gas (TCG) detectors were introduced in 1965, enabling utilities to implement DGA for routine monitoring of oil-immersed equipment. Adoption accelerated in the , with the first online monitor commercialized in 1974 by Morgan Schaffer, marking a shift toward proactive fault detection. Influential interpretation frameworks emerged from empirical studies of gases in failed transformers during the . The Rogers ratio method, introduced in 1973 by R.R. Rogers at , utilized ratios such as CH₄/H₂ and C₂H₂/C₂H₄ to diagnose fault types including thermal faults and discharges, drawing on thermodynamic models and extensive failure data. Complementing this, Michel Duval developed the Duval triangle in 1974, a graphical method plotting the relative percentages of (CH₄), (C₂H₄), and (C₂H₂) to classify faults like partial discharges and arcing, validated against hundreds of inspected cases. These approaches, grounded in large datasets from utilities, significantly improved diagnostic accuracy. Standardization in the late and promoted global consistency, with IEC 567 published in 1977 to guide DGA sampling and extraction procedures, followed by ASTM D3612 in 1979 for testing methods. The IEEE Std C57.104, first issued in 1978, provided comprehensive guidelines for interpreting gases in mineral oil-immersed transformers, incorporating ratio-based diagnostics and establishing thresholds for fault severity. These documents, developed through collaboration, facilitated widespread utility adoption and refined DGA protocols. Since the 2000s, DGA has integrated with digital technologies for continuous monitoring, beginning with online multi-gas analyzers in the late 1990s that measured and combustible gases without manual intervention. Advancements in the 2000s included micro devices and headspace techniques standardized in updated IEC 60567, enabling real-time trending of gas levels. By the 2020s, automated DGA systems support initiatives, using non-chromatographic sensors like for and rapid fault localization in large-scale power networks.

Insulating Fluids

Types and Properties

Insulating fluids serve as both electrical insulators and coolants in power transformers, enabling the application of dissolved gas analysis (DGA) to detect faults through dissolved fault gases. The most prevalent type is , a petroleum-derived fluid that dominates due to its proven performance and cost-effectiveness. Other common types include synthetic esters (e.g., pentaerythritol-based), natural esters (vegetable oil-derived, such as soybean-based fluids), and fluids (polydimethylsiloxane-based). Legacy fluids like polychlorinated biphenyls (PCBs), once used for their chemical stability, have been globally phased out since the 1970s due to their , , and carcinogenic effects. Key properties relevant to DGA include high (typically >30 kV for 2.5 mm gap in new fluids) to minimize arcing, thermal stability up to 105–140°C operating s without excessive , and (around 10–12 at 40°C for oils) that affects gas and . These fluids can dissolve fault gases such as (H₂) and (CH₄) up to several hundred ppm under abnormal conditions like partial discharges or low-energy arcing, with influenced by and —higher s increase gas partitioning into the oil . Silicone fluids exhibit lower gas for hydrocarbons compared to oils, while esters show higher for gases like CO₂. Degradation in these fluids arises from oxidation (reaction with oxygen forming acids and sludge), (water-induced breakdown, prominent in esters), and stress ( above 200°C generating hydrocarbons). Mineral oils primarily yield hydrocarbon gases (e.g., CH₄, C₂H₄) under thermal faults, whereas ester fluids produce elevated CO₂ levels—up to 10 times more than mineral oils during oxidation or —along with CO from cellulose interactions. These differences necessitate fluid-specific DGA interpretation to avoid misdiagnosis. Selection of insulating fluids considers (esters have fire points >300°C vs. 140°C for , reducing flammability risks), environmental impact (natural and synthetic esters are >95% biodegradable, minimizing spill hazards unlike persistent mineral oils), and DGA compatibility (mineral oils leverage extensive IEEE baselines, while esters require adjusted ratios due to unique gas profiles). These criteria drive adoption of esters in urban or ecologically sensitive installations despite higher upfront costs.

Gas Dissolution Mechanisms

In electrical equipment such as transformers, faults generate gases through specific decomposition processes of the insulating materials. of under low-temperature conditions (below 300°C) primarily produces saturated hydrocarbons like (CH4) and (C2H6), while higher temperatures (300–700°C) yield (C2H4) and, at very high temperatures (above 700°C), (C2H2) along with formation. Electrical arcing, involving high-energy discharges, predominantly generates (C2H2) and (H2) due to the cracking of oil hydrocarbons under intense localized heating. Partial discharges, such as effects, result in (H2) as the main gas, with minor amounts of (CH4) and (C2H2) from low-energy of the oil. of cellulose-based , like paper, through produces (CO) and (CO2), reflecting the degradation of cellulosic polymers under thermal stress. These generated gases dissolve into the insulating fluid, primarily mineral oil, following principles of physical solubility. Henry's law governs this process, stating that the partial pressure (P) of a gas above the liquid is proportional to its concentration (C) in the solution, expressed as P = k \cdot C, where k is the Henry's law constant specific to the gas-oil pair. For hydrocarbon gases in mineral transformer oil, solubility generally increases with temperature, contrary to aqueous systems, due to the non-polar nature of the oil, allowing better accommodation of non-polar gases at higher thermal energies; for instance, the solubility of acetylene and ethylene rises notably between 25°C and 90°C. Pressure also enhances solubility, as higher system pressures force more gas molecules into the liquid phase, following the direct proportionality in Henry's law. Fault types produce distinct gas signatures based on energy levels, aiding in understanding dissolution patterns. Low-energy faults, such as corona or partial discharges, generate lighter, more soluble gases like hydrogen and methane, which dissolve readily but may partition variably due to their high diffusivity. High-energy faults, like arcing, produce unsaturated hydrocarbons such as acetylene and ethylene, which exhibit lower solubility coefficients but accumulate significantly under sustained conditions, reflecting the intense decomposition. Once dissolved, gases establish equilibrium dynamics between the oil and any headspace in the equipment. Gases partition according to their Ostwald coefficients, which describe the volume ratio of gas in the headspace to that dissolved in the oil at , influenced by and phase transfer rates. In transformers with a gas , this partitioning allows excess gases to migrate to the headspace, preventing in the oil. Aging of the insulating fluid alters these coefficients, as oxidative increases oil and , reducing the of non-polar hydrocarbons like by up to 20–30% in severely aged oils compared to fresh samples.

Sampling Procedures

Collection Techniques

Collection techniques for dissolved gas analysis (DGA) in insulating oil primarily involve obtaining representative samples that preserve the dissolved gases, adhering to standardized protocols to ensure accuracy and prevent contamination or gas loss. The standard practice for sampling electrical insulating liquids, including those used in transformers, is outlined in ASTM D923, which specifies methods for drawing samples from various points such as valves or drains while maintaining sample integrity. Valve-mounted syringes are a key tool for quick field sampling, typically ranging from 50 to 100 ml in capacity and constructed from to minimize interactions with the oil. These syringes, equipped with three-way valves, attach directly to the transformer's sampling valve via a short , allowing oil to be drawn after initial flushing to remove stagnant material. For transport to laboratories, larger oil sample tubes of 150 to 250 ml, made from with Teflon stopcocks, provide a sealed environment that accommodates volume changes due to temperature fluctuations without gas escape. These tubes often include a side port with a PTFE-lined for subsequent subsampling. Procedures for online sampling, conducted while the is energized, target dedicated sampling valves on the main , ideally at operating temperatures of 60-80°C to reduce gas partitioning into the headspace and maintain . The process begins with verifying positive pressure, followed by flushing the valve and lines with at least 2 liters of oil to eliminate air or contaminants before collecting the sample. Offline sampling, performed during shutdowns, utilizes valves at the bottom, requiring extensive flushing—often 5 to 10 times the dead volume of the valve and tubing—to avoid introducing moisture or external gases that could skew results. In both cases, samples are drawn under controlled conditions to reflect the bulk oil properties of or synthetic insulating fluids. Volume requirements vary by subsequent extraction method: a minimum of 50 ml suffices for headspace analysis, where a portion is equilibrated in a , while vacuum extraction demands at least 100 ml to achieve sufficient gas yield under reduced pressure. For reliable trending of gas concentrations over time, multiple samples (typically 2-3 per event) are recommended from the same location to account for variability. In field applications, portable kits incorporating valve-mounted syringes enable initial screening of key gases using compact analyzers, providing rapid diagnostics at remote sites. Conversely, sealed tubes are preferred for laboratory-bound samples, ensuring precise multi-gas analysis without degradation during transit.

Handling and Precautions

Maintaining sample integrity is critical in dissolved gas (DGA) to ensure accurate fault detection in insulating fluids. Post-collection handling protocols emphasize minimizing gas loss, contamination, and degradation through controlled conditions and procedural safeguards. Samples must be stored under refrigerated conditions at 4-10°C in dark, non-porous containers such as syringes or metal bulbs to prevent gas and external influences like or oxygen . This range slows chemical reactions and changes, with a maximum hold time of 30 days recommended before to preserve gas concentrations. transportation to the in insulated, sealed packaging further reduces variability. To avoid contamination, all equipment used in handling must be clean and dry, with sampling lines flushed 5-10 times their volume (typically 1-2 liters depending on system size) prior to collection to eliminate residual fluids or particulates. Air exposure should be strictly limited during transfer, as it introduces oxygen and , skewing ratios and interfering with fault interpretation (e.g., O₂/N₂ > 0.2 indicates ). Safety protocols treat samples as potentially hazardous due to the presence of polychlorinated biphenyls (PCBs) in older equipment; (PPE) including gloves, goggles, and protective clothing is required during handling. Containers must be labeled with collection temperature, date, time, and equipment identification to track and ensure . Common errors that compromise results include overheating the sample during collection (e.g., from hot valves or ), which can cause premature gas evolution and elevate levels of or hydrocarbons. Improper sealing of containers leads to leaks, allowing ingress of atmospheric gases or egress of dissolved ones, often resulting in unreliable data. Adhering to these protocols, often aligned with collection techniques using gas-tight syringes, mitigates such risks.

Gas Extraction Techniques

Headspace Method

The headspace method, designated as Method C in the ASTM D3612 standard, is a gas extraction technique used to liberate dissolved gases from insulating oil samples by establishing equilibrium between the liquid oil phase and a vapor headspace in a sealed . This approach relies on , where dissolved gases partition into the gas phase based on their and the system's conditions, allowing for subsequent sampling of the headspace vapor without direct contact with the oil. The method is widely adopted for its balance of simplicity and reliability in dissolved gas analysis (DGA) of oils. The procedure begins by transferring a precise volume of oil, typically 15–20 mL, into a sealed vial such as a 20 mL glass headspace vial fitted with a septum. The headspace above the oil is purged with an inert gas like argon to eliminate atmospheric contaminants, preventing interference from ambient oxygen or nitrogen. The vial is then heated to 60–80°C, often around 70°C, and agitated or shaken for 20–30 minutes to accelerate equilibration and ensure uniform partitioning of gases into the vapor phase. Once equilibrium is reached, the headspace gas is extracted using a gas-tight syringe for manual sampling or by pressurizing the vial to fill a sample loop in automated systems, preparing it for transfer to analytical instrumentation. This process adheres to ASTM D3612-C guidelines and minimizes sample handling to preserve gas integrity. Key equipment includes vials with PTFE/silicone septa for sealing, a or block to maintain consistent , and an agitator or to promote rapid . For applications, a gas-tight facilitates direct extraction, while setups employ automated headspace samplers such as the TriPlus 500 or Versa systems integrated with gas chromatographs. Recovery efficiency for light, low- gases like (H₂) reaches approximately 90–95%, calculated using partition coefficients that account for the volume ratio and gas-specific at the equilibration . This method offers advantages in simplicity and low cost, making it ideal for field or on-site use where portable analyzers can perform extractions without complex vacuum setups; it excels at detecting volatile hydrocarbons such as H₂ and (C₂H₂), which readily partition into the headspace. Automated implementations enhance throughput, processing up to 120 samples with repeatability under 5% relative standard deviation. However, limitations include reduced extraction efficiency for more soluble gases like (CO₂), where partition coefficients yield lower headspace concentrations (around 50% recovery in equal-volume phases), necessitating correction factors based on , , and gas-specific data to accurately compute oil-phase concentrations. Additionally, variations in volume or incomplete purging can introduce errors, requiring strict adherence to standardized volumes and conditions.

Vacuum Extraction Methods

Vacuum extraction methods represent a foundational approach in dissolved gas analysis (DGA) for extracting dissolved gases from insulating oils, particularly in settings where high precision is required. This technique, standardized as Method A in ASTM D3612, involves subjecting the oil sample to a high to liberate the dissolved gases through in multiple stages. The process achieves near-complete extraction by applying levels as low as 10^{-3} torr (1.33 \times 10^{-3} mbar), ensuring the removal of non-condensable gases such as (H_2), oxygen (O_2), (N_2), (CO), (CO_2), and light hydrocarbons (such as , , , and ). The core procedure utilizes a Toepler pump system, traditionally employing mercury displacement to collect and compress the evolved gases without atmospheric contamination; however, mercury-free alternatives using or other mechanisms are increasingly used to mitigate health and safety risks associated with mercury toxicity. In this setup, the oil sample is introduced into a sealed glass vessel, where an initial rough is applied to evacuate air and begin . Subsequent fine extraction stages involve repeated cycles of application and gas collection, with the Toepler transferring the gases into a storage volume. To separate non-condensable gases from and other condensables, freezing traps cooled to temperatures as low as -196°C (using ) are employed, allowing permanent gases to pass through while capturing interfering vapors. This multi-stage process typically yields a total gas recovery efficiency exceeding 95%, often approaching 100% for the Toepler variant, making it highly reliable for . Essential equipment includes vacuum racks—elaborate, glass-sealed assemblies often configured for of multiple samples—along with mechanical vacuum pumps capable of achieving the required low pressures, manometers for measurement, and cold traps for vapor separation. These rack systems facilitate simultaneous handling of several oil samples, enhancing throughput while maintaining to prevent cross-contamination. The collected non-condensable gases are then measured manometrically before transfer to for . Vacuum extraction is preferred in controlled laboratory environments for its superior precision and ability to handle all relevant gas types, including reactive species like CO and CO_2, which may be underrepresented in simpler techniques. Compared to headspace methods, it offers greater extraction efficiency but requires more specialized equipment and operator expertise.

Analytical Methods

Gas Chromatography

Gas chromatography (GC) serves as the primary analytical technique for separating and identifying the extracted gases in dissolved gas analysis (DGA) of insulating oils from electrical equipment such as transformers. The process begins with the injection of the gas sample, typically obtained from headspace or vacuum extraction methods, into a heated port of the GC system where it vaporizes. An inert carrier gas, such as helium or argon, then transports the vaporized components through the chromatographic column, where separation occurs based on the differing affinities of the gas molecules for the stationary phase versus the mobile phase. Argon is often preferred over helium for thermal conductivity detection due to enhanced sensitivity for hydrogen. Column configurations in DGA-GC are tailored to achieve effective separation of key gases, commonly employing packed or columns in a dual-channel setup. columns, such as 5Å packed variants (e.g., 2 m × 1/8 inch), separate non-hydrocarbon gases like , oxygen, and by molecular size exclusion. Porous columns (e.g., 3 m × 1/8 inch, 80/100 ) handle , , and light hydrocarbons, with backflushing used to vent higher hydrocarbons and prevent column overload. This multi-column approach ensures comprehensive resolution within a single run, typically under isothermal or temperature-programmed conditions around 50–100°C. Detection in DGA-GC relies on thermal conductivity detectors (TCD) and flame ionization detectors (FID) to quantify separated components by measuring peak heights or areas. TCDs, operated at temperatures like 200°C with filaments at 300°C, provide universal response for permanent gases such as H₂, O₂, and N₂, leveraging differences in thermal conductivity relative to the carrier gas. For hydrocarbons and carbon oxides, FIDs at 300°C, often equipped with a methanizer to convert CO and CO₂ to methane, offer high sensitivity to organic compounds while TCD handles inorganics in parallel channels. Calibration of the system ensures accurate quantification, using certified gas mixtures diluted in the carrier gas or oil matrices with concentrations ranging from 10 to 1000 for assessment. Response factors are calculated from multiple points, verifying with coefficients typically exceeding 0.999, and applied to convert peak areas to gas concentrations in the original oil sample. Modern DGA-GC systems incorporate automation for efficiency, including autosamplers that process up to 120 vials with simultaneous incubation, reducing manual intervention and enabling high-throughput analysis in about 20–30 minutes per sample. Hybrid GC-mass spectrometry (GC-MS) configurations extend capabilities for trace-level detection and compound confirmation in complex samples, though standard GC suffices for routine DGA.

Detection and Quantification

In dissolved gas analysis (DGA) of insulating oils, primarily used for transformers, the standard gases measured include nine key species: (H₂), oxygen (O₂), (N₂), methane (CH₄), carbon monoxide (CO), carbon dioxide (CO₂), ethane (C₂H₆), ethylene (C₂H₄), and acetylene (C₂H₂). These gases are quantified in parts per million () by , equivalent to microliters per liter (μL/L) at standard conditions. Typical baseline concentrations for total dissolved combustible gases (TDCG, excluding O₂, N₂, and CO₂) are below 720 in healthy equipment, with 90th percentile individual levels such as H₂ up to 100 and CO₂ up to 10,000 indicating normal operation per IEEE C57.104-2019. Quantification occurs post-extraction through gas chromatography (GC), where gases are separated and detected, followed by peak area integration compared to calibration standards of known concentrations. Detection limits vary by gas and method but are typically around 1-5 ppm for H₂, 5-10 ppm for CO, and 10-40 ppm for CO₂, enabling reliable measurement of trace fault indicators. Overall measurement uncertainty is approximately ±5-15% for laboratory GC analyses, depending on the instrument and sample handling. Interferents such as atmospheric O₂ and N₂, often introduced via leaks or sampling, are accounted for by calculating their ratio; values near 0.21 (air composition) prompt subtraction from total readings to isolate generated gases. Moisture contamination can elevate CO₂ readings by accelerating cellulose degradation, necessitating dry sampling conditions and separate water content analysis. For ongoing assessment, DGA relies on serial measurements over time to track gas generation rates, typically expressed in ppm per year; increases exceeding the 95th percentile rates (typically >200-500 ppm/year for TDCG depending on conditions) signal potential issues requiring further investigation per IEEE C57.104-2019. This trending approach, recommended in IEEE C57.104, uses at least three to six samples spanning 4-24 months for robust rate estimation.

Fault Interpretation

Types of Faults

Dissolved gas analysis (DGA) identifies various faults in oil-immersed transformers by examining the concentrations of dissolved gases such as (H₂), (CH₄), (C₂H₆), (C₂H₄), and (C₂H₂), which form due to or electrical stresses. These faults are broadly categorized into and electrical types, with additional indicators for overheating and partial discharges in . Severity is assessed using total combustible gas (TCG) levels, where concentrations exceeding 720 of TCG (sum of H₂, CH₄, C₂H₆, C₂H₄, and C₂H₂) signal the need for further investigation, and gas ratios help gauge fault energy levels. Thermal faults arise from overheating of the insulating oil or solid , producing distinct gas profiles based on temperature ranges. At low temperatures below 300°C, (CH₄) dominates as the primary gas. In the medium range of 300–700°C, (C₂H₄) becomes prominent alongside CH₄. High-temperature faults above 700°C generate significant (C₂H₂) and elevated C₂H₄, often accompanied by formation. When is involved in thermal faults, (CO) and (CO₂) are additionally produced, with CO₂ typically in higher proportions during aging or low-to-medium heating. Electrical faults manifest through discharges or arcs in the , yielding specific gas signatures. Partial discharges, such as effects, are indicated by high levels of H₂ and CH₄. Low-energy sparking produces moderate C₂H₂ with elevated H₂ and CH₄. Arcing, involving high-energy discharges, results in substantial C₂H₂ and C₂H₄ concentrations. Other fault indicators include oil overheating, which elevates C₂H₆ and C₂H₄ due to without solid involvement, and partial discharges in materials, characterized by H₂ spikes. These profiles, as outlined in standards like IEEE C57.104-2019 and IEC 60599, enable early detection of incipient issues before major failures occur.

Diagnostic Techniques

Diagnostic techniques in dissolved gas analysis (DGA) involve systematic interpretation of gas concentrations to identify and classify incipient faults in oil-immersed electrical equipment, such as power transformers. These methods rely on established algorithms and graphical tools to correlate gas levels with fault types like (), thermal faults, and arcing, enabling . Common approaches include ratio-based methods, key gas analysis, and dynamic trending, each providing complementary insights into fault severity and progression. Ratio methods compare concentrations of key hydrocarbon gases to diagnose specific fault mechanisms. The Rogers ratio method, developed in the 1970s, uses three primary ratios—CH₄/H₂, C₂H₆/CH₄, and C₂H₂/C₂H₄—to classify faults; for instance, a CH₄/H₂ ratio greater than 0.1 often indicates degradation above 300°C. This technique simplifies fault identification by assigning numeric codes based on ratio ranges, though it may overlook low-level PD if hydrogen is not dominant. The Duval Triangle method employs a ternary diagram plotting the percentages of CH₄, C₂H₂, and C₂H₄ relative to their sum, dividing the plot into regions for PD (high CH₄), faults (high C₂H₄), and high-energy arcing (high C₂H₂). Validated through extensive field data, it achieves high accuracy for mineral oil transformers, with fault regions defined by boundaries like 23% CH₄ for PD separation. The Doernenburg ratio method extends this by incorporating four ratios—CH₄/H₂, C₂H₆/CH₄, C₂H₄/C₂H₆, and C₂H₂/C₂H₄—along with absolute gas thresholds to confirm faults; ratios falling within designated bands signal faults or discharges only if gases exceed baseline limits. The key gas method focuses on the dominant gas exceeding predefined thresholds to pinpoint fault types, as outlined in IEEE Std C57.104. For example, elevated C₂H₂ levels typically indicate arcing, while high H₂ suggests ; thresholds such as 100 ppm for H₂ or 35 ppm for C₂H₂ (exceeding Condition 1 limits) trigger condition assessments. This approach provides a straightforward initial but benefits from integration with ratio methods for , as single-gas dominance can vary with fault . Advanced diagnostic techniques leverage computational models to integrate multiple DGA parameters for enhanced accuracy. Expert systems employing process gas ratios and concentrations through if-then rules that handle uncertainty, combining outputs from methods like Rogers and Duval to yield probabilistic fault diagnoses. These systems, often implemented in software, improve consistency by weighting inputs dynamically and reducing contradictory interpretations from traditional techniques. Trending analysis monitors the rate of gas concentration increases over time to assess fault activity and urgency. According to IEEE guidelines, a doubling of total combustible gases in less than one month signals an active fault requiring immediate action, while slower rates (e.g., 65-180 days) indicate moderate concern. This method uses sequential DGA samples to calculate generation rates, accounting for factors like oil volume and ; however, false positives can arise from or sampling errors, necessitating verification through repeated testing.

Applications and Standards

Primary Applications

Dissolved gas analysis (DGA) is primarily applied in the of power , where it serves as a key diagnostic tool for detecting incipient faults in units rated at 132 and above. Routine offline DGA testing is typically conducted annually for these transformers to identify early signs of degradation, while online DGA systems are deployed for critical assets to enable continuous surveillance of gas levels such as , , and . Incipient faults constitute 70-80% of transformer faults, and this approach enables their early detection, including partial discharges and overheating, thereby preventing escalation to catastrophic failures. Beyond power transformers, DGA extends to other oil-filled electrical equipment, including bushings, circuit breakers, and cables, where it assesses health and identifies issues like arcing or thermal degradation in high-viscosity fluids. In emerging applications, DGA is increasingly used for transformers, which often exhibit elevated gas production due to variable loading and harmonics, supporting integration into . For instance, analysis of over 500 transformers has revealed patterns of stray gassing and partial discharges unique to these units. Implementation of DGA often involves integration with systems for real-time monitoring and alerting, such as tracking gas concentrations via protocols converted to for historical trending and rate-of-change alarms. This enables deferred maintenance strategies, yielding significant cost savings; for example, avoiding a single failure can prevent replacement costs that are 2-3 times the original installation expense, along with millions in outage-related losses. Case studies illustrate DGA's effectiveness in early fault detection. In one incident involving a 400 kVA grounding , elevated levels (288 ppm) signaled arcing at the off-load tap-changer shortly after energization, allowing timely repair and averting a prolonged outage. Similarly, in a 94 MVA gas-insulated in 2015, DGA identified up to 1735 ppm from low-energy discharges, leading to contact repairs that maintained reliability. These utility examples highlight DGA's role in preventing arcing-related disruptions through proactive intervention.

Relevant Standards and Guidelines

The interpretation and application of dissolved gas analysis (DGA) in oil-filled electrical equipment are governed by several international standards that establish procedures for sampling, analysis, interpretation, and maintenance actions. These standards ensure consistency and reliability in diagnosing faults in transformers and related apparatus. The IEEE Std C57.104-2019 provides a comprehensive guide for the interpretation of gases generated in mineral oil-immersed transformers, including detailed procedures for gas sampling, laboratory analysis, and trending of dissolved combustible gases. It defines gas concentration limits for individual key gases such as (H₂ ≤ 100 ppm), (CH₄ ≤ 120 ppm), (C₂H₂ ≤ 1 ppm), (C₂H₄ ≤ 50 ppm), (C₂H₆ ≤ 65 ppm), and (CO ≤ 350 ppm) under normal operating conditions (status 1, 90th percentile), along with trending procedures to monitor generation rates over time. Action levels based on total dissolved combustible gas (TDCG) are specified: Condition 1 (TDCG < 720 ppm, normal); Condition 2 (720–1920 ppm, increased monitoring and investigation); Condition 3 (>1920 ppm, potential severe faults necessitating immediate assessment). IEC 60599:2022 offers guidance on the of dissolved and free gases in oil-filled electrical equipment in service, focusing on fault for transformers, reactors, and similar devices insulated with cellulosic materials. It details the method, a graphical technique using the relative percentages of (CH₄), (C₂H₄), and (C₂H₂) to classify faults, with codes such as T1-T3 for thermal faults (T1: <300°C, T2: 300-700°C, T3: >700°C) and D1-D2 for electrical discharges (D1: low-energy, D2: high-energy). The standard also addresses partial discharges (PD) and mixture faults, recommending cautious application to non- oils. ASTM D3612-19 standardizes the sampling and gas chromatographic analysis of dissolved gases in electrical insulating liquids with viscosities up to 20 , specifying three primary extraction procedures: A (total gas vacuum extraction), B (individual component extraction), and C (stripper column method for individual gases). It includes precision requirements, such as repeatability limits of ±10-20% relative standard deviation for major gases like CO₂ and hydrocarbons, and reproducibility up to ±30% across laboratories, ensuring accurate quantification down to parts-per-million levels. IEC 60567:2023 complements these by outlining methods for sampling free gases from relays and analyzing both free and dissolved gases in mineral oils and other insulating liquids, using techniques like (Toepler and partial ), gas displacement by bubbling, and headspace sampling. Post-2020 updates in standards such as IEC 60599:2022 extend guidance to ester-based fluids (e.g., natural and synthetic esters) with adjusted thresholds, while IEEE Std C57.143-2024 addresses online DGA monitors, specifying , , and integration for real-time fault detection in transformers.

References

  1. [1]
    A Review of Dissolved Gas Analysis in Power Transformers
    Dissolved gas analysis (DGA) provides insights into thermal and electrical stresses in transformers, detects incipient faults, and helps prevent further damage.
  2. [2]
    [PDF] IEEE DISSOLVED GAS ANALYSIS GUIDELINES | Facility Results
    A one to four condition DGA guide is used to classify risks to transformers with no previous problems has been developed by the IEEE [11]. The guide uses ...
  3. [3]
    DGA Test Standards: IEC vs IEEE – What You Need to Know - Megger
    Oct 7, 2025 · Emphasis on Trending: The IEEE standard places greater emphasis on gas generation rates and trending analysis rather than absolute concentration ...
  4. [4]
    IEEE C57.104-2019
    Nov 1, 2019 · Detailed procedures for analyzing gas from gas spaces or gas-collecting devices as well as gas dissolved in oil are described.
  5. [5]
    [PDF] Guide for Interpreting Dissolved Gases in Liquid-filled Transformers
    Jun 1, 2023 · This Guide is a tutorial and reference document whose purpose is to teach the reader how to do DGA interpretation, making use of several ...
  6. [6]
    None
    ### Summary of Dissolved Gas Analysis (DGA) from GE Vernova Document
  7. [7]
    None
    Summary of each segment:
  8. [8]
    [PDF] A CENTURY OF DISSOLVED GAS ANALYSIS - PART II
    transformers history facts relevant to gassing issues. 1836 - 1885 - transformer was invented in Europe and in the US. 1900 - Gas chromatography invented by ...
  9. [9]
    Conventional Dissolved Gases Analysis in Power Transformers - MDPI
    Oct 24, 2023 · From the 1960s onwards, gas chromatography (GC) saw its first applications in identifying dissolved gases in transformers from electrical faults ...
  10. [10]
    Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated ...
    However, this technique was not applied specifically to transformer mineral oil until the late 1960s/early 1970s and is now commonly called dissolved gas-in-oil ...
  11. [11]
    Dissolved gas analysis of transformers using fuzzy logic approach
    Apr 14, 2009 · Rogers method for dissolved gas-in-oil analysis (DGA). The Rogers ratio method was introduced for the first time in 1973 and was improved in ...
  12. [12]
    Machine learning based multi-method interpretation to enhance ...
    Feb 29, 2024 · The Duval triangle method was introduced for the first time in 1974, employing a combination of three hydrocarbon gases: CH4, C2H4, and C2H2, ...
  13. [13]
    DGA | PDF | Carbon Dioxide | Gases - Scribd
    The Duval Triangle method uses concentrations of methane, ethylene, and acetylene to plot results on a triangle diagram and identify fault types. It has been ...
  14. [14]
    IEEE/PES Transformers Committee
    Mar 26, 2020 · IEEE C57.104 "Guide for the Interpretation of Gases Generated in Mineral Oil-Immersed Transformers," originally introduced in 1978, is ...
  15. [15]
    [PDF] Chemical Sensing Strategies for Real-time Monitoring of ... - OSTI.GOV
    On-line dissolved gas analysis monitors were invented in the late 1990s. [9], which measured the concentrations of hydrogen and other combustible gas in ...
  16. [16]
    Integrating offline and online Dissolved Gas Analysis (DGA ...
    Nov 3, 2025 · The integration of offline and online Dissolved Gas Analysis (DGA) methodologies can be a framework for predictive transformer maintenance.
  17. [17]
    Experiences in Service with New Insulating Liquids - eCIGRE
    Experiences in Service with New Insulating Liquids · This publication is free only for CIGRE members · Price for non member: 180 €.
  18. [18]
    Learn about Polychlorinated Biphenyls | US EPA
    They have a range of toxicity and vary in consistency from thin, light-colored liquids to yellow or black waxy solids. Due to their non-flammability, chemical ...Missing: phased | Show results with:phased
  19. [19]
    Transformer Oil: Testing, Types & Properties - Electrical4U
    May 3, 2024 · Transformer oil (also known as insulating oil) is a special type of oil which has excellent electrical insulating properties and is stable at high temperatures.
  20. [20]
  21. [21]
    Influence of cellulose paper on gassing tendency of transformer oil ...
    The intent of this work is to evaluate the influence of cellulose insulation paper on gassing tendency of transformer oil under electrical discharge ...
  22. [22]
  23. [23]
    Online dissolved gas analysis used for transformers – possibilities ...
    Feb 16, 2022 · The solubility of the investigated hydrocarbons (C2H2, C2H4, C2H6 and CH4) increases with rising temperature, whereas the solubility of ...Missing: law | Show results with:law
  24. [24]
    (PDF) Solubility study of different gases in mineral and ester-based transformer oils
    ### Solubility of H₂ and CH₄ in Mineral Oil and Esters
  25. [25]
    D923 Standard Practices for Sampling Electrical Insulating Liquids
    Dec 27, 2023 · These practices cover sampling of new electrical insulating liquids including oils, askarels, silicones, synthetic liquids, and natural ester insulating ...
  26. [26]
    [PDF] sample container selection for insulating liquids - Doble Engineering
    ASTM D923, Standard Practice for Sampling. Electrical Insulating Liquids provides a list of sample containers and the advantages and disadvantages of each and ...<|separator|>
  27. [27]
    The Right Way to Sample a Transformer - Southwest Electric Co
    Mar 1, 2024 · How Much Oil Should I Pull? ASTM D- 923 states that whenever you sample a transformer you should flush 2 liters of oil. This can be a lot of ...
  28. [28]
    [PDF] LIQUID SAMPLING INSTRUCTIONS - SDMyers
    Flush the valve as follows: 50 oz. for a ... These instructions are intended to provide some basic guidance on drawing your own transformer liquid samples.
  29. [29]
    [PDF] Method 9079: Screening Test Method for Polychlorinated Biphenyls ...
    6.0 SAMPLE COLLECTION, PRESERVATION, AND HANDLING. 6.1 See the introductory material to this chapter, Organic Analytes, Section 4.1. 6.2 Oil samples may be ...
  30. [30]
    [PDF] Headspace-GC Analysis of Dissolved Gases in Transformer Oil ...
    ASTM D-3612 offers three methods for the DGA analysis1: • Method A: Vacuum extraction. Dissolved gases from the transformer oil are extracted by vacuum using a ...Missing: dynamics | Show results with:dynamics
  31. [31]
    [PDF] Transformer Oil Gas Analyser According to ASTM D 3612c Small ...
    ASTM D 3612 describes three procedures for the extraction and determination of gases in transformer oil. This application note is based on part C, using head ...
  32. [32]
    [PDF] The world of DGA – and its uncertainties - Vaisala
    DGA and its utilization in transformer diagnostics is not exact science, but rather an evaluation method based on statistics and empirical data.
  33. [33]
    Dissolved gas analysis - Academic Dictionaries and Encyclopedias
    The collection and analysis of gases in an oil-insulated transformer was discussed as early as 1928. Many years of empirical and theoretical study have gone ...
  34. [34]
    Transformer Oil Gas Analysis via Headspace Sampling (ASTM D3612)
    Headspace sampling involves transferring dissolved gases from oil to a headspace in a closed vessel, then using a GC to analyze the gases.
  35. [35]
    Standard Test Method for Analysis of Gases Dissolved in Electrical ...
    Dec 13, 2017 · ASTM D3612 is a test method for analyzing gases in electrical insulating oil using gas chromatography, covering extraction and measurement of  ...
  36. [36]
  37. [37]
    [PDF] Automated GC sample prep of dissolved gas-in-oil - PAL System
    In combination with a PAL RTC and a GC-MS system, Oleo allows the automated analysis of 30 samples of oil by headspace, to quantify permanent gases, methane, ...<|control11|><|separator|>
  38. [38]
    Dissolved Gas Analysis Limits | ELSCO Transformers
    May 16, 2024 · DGA gives you valuable insight into a transformer's condition through concentration and trend analysis of dissolved gases in transformer oil.
  39. [39]
    [PDF] Dissolved Gas Analysis is an Art of Testing and ... - CPRI Journal
    In DGA testing and Analysis first aim should be to get the correct amount of gas content in oil using the latest gas extraction methodology and sensitive gas.
  40. [40]
    Static headspace gas chromatographic determination of fault gases ...
    The method of choice for the determination of fault gases in transformer oils is the so-called dissolved gas analysis (DGA). Dissolved gas analysis is a common ...
  41. [41]
    Dissolved Gas Analysis Procedure Based on IEEE C57.104-2019
    May 31, 2025 · This article outlines the suggested Dissolved Gas Analysis interpretation procedure from the IEEE Std C57.104-2019, offering a structured ...
  42. [42]
    Traditional fault diagnosis methods for mineral oil‐immersed power ...
    Apr 22, 2024 · The authors present a detailed and comprehensive literature review of the traditional DGA-based methods for mineral oil-immersed power transformer faults ...
  43. [43]
    IEEE Guide for the Interpretation of Gases Generated in Mineral Oil ...
    Nov 1, 2019 · The purpose of this document is to provide a guide for evaluating dissolved gases analysis results from mineral oil-immersed transformers.
  44. [44]
  45. [45]
    Diagnostic Simplexes for Dissolved-Gas Analysis - MDPI
    A Duval triangle is a diagram used for fault type identification in dissolved-gas analysis of oil-filled high-voltage transformers and other electrical ...
  46. [46]
    The Duval Triangle for Load Tap Changers, Non-Mineral Oils and ...
    Aug 7, 2025 · The present paper reviews these DGA results in a more user-friendly graphical form. It also reviews the DGA results of laboratory models ...
  47. [47]
    A Reviewed Turn at of Methods for Determining the Type of Fault in ...
    May 12, 2024 · The Doernenburg Ratio Method. This method was proposed in 1974 and used for the recognition of incipient faults using the technique of key gas ...<|separator|>
  48. [48]
    [PDF] IEEE Guide for the Interpretation of Gases Generated in Mineral Oil ...
    Nov 1, 2019 · This guide describes procedures for interpreting Dissolved Gas Analysis (DGA) results in mineral oil-immersed transformers, including gas ...
  49. [49]
  50. [50]
    Fuzzy Logic Approach to Dissolved Gas Analysis for Power ... - MDPI
    This paper proposed a fuzzy logic system for power transformer fault assessment based on the three DGA methods; key gas, IEC ratio, and Duval triangle method ...
  51. [51]
    Multiclass Fault Diagnosis in Power Transformers Using Dissolved ...
    Studies have indicated that approximately 70–80% of transformer faults are incipient, highlighting the importance of early detection to prevent fault escalation ...
  52. [52]
    Dissolved Gas Analysis (DGA) by EPRI Disposable Oil Sampling ...
    Fluid-filled equipment -- which includes transformers, cables, bushings, terminations, and circuit breakers -- is an integral part of the electrical system.
  53. [53]
    Gassing in Wind Turbine Transformers - TJ|H2b Analytical Services
    Feb 2, 2023 · Local transformers, those directly linked to the turbine of a wind farm, generate abnormally high amounts of dissolved gases.
  54. [54]
    Dissolved Gas Analysis - integratedSCADA
    Integrating DGA data into the SCADA system allows historical trending, alarming and real-time monitoring. In this case the rate of change of values over ...
  55. [55]
    Cut Costs with Transformer Monitoring - Dynamic Ratings
    Jul 8, 2025 · Condition-based monitoring provides a cost-effective solution, empowering utilities to adopt a proactive approach to monitoring their assets.Missing: savings deferred
  56. [56]
    Experiences with transformer diagnosis by DGA: case studies
    Nov 7, 2019 · In this study, after reviewing the significant points in the DGA procedure, five real cases are reported which explain the transformer diagnosis by DGA.
  57. [57]
    IEC 60599:2022
    May 25, 2022 · IEC 60599:2022 describes how the concentrations of dissolved gases or free gases can be interpreted to diagnose the condition of oil-filled electrical ...
  58. [58]
    [PDF] INTERNATIONAL STANDARD NORME INTERNATIONALE IEC 60599
    This document describes how the concentrations of dissolved gases or free gases can be interpreted to diagnose the condition of oil-filled electrical equipment ...
  59. [59]
    IEC 60567:2023
    Dec 8, 2023 · Three basic methods are described, one using extraction by vacuum (Toepler and partial degassing), another by displacement of the dissolved ...