Free cooling

Free cooling is an energy-efficient strategy in (HVAC) systems that utilizes ambient outdoor air or water at lower temperatures to provide cooling, thereby minimizing or eliminating the energy-intensive operation of mechanical compressors or chillers. This approach exploits natural temperature differentials between the environment and the conditioned space, enabling rejection through methods such as direct air economizers, indirect evaporative cooling towers, or glycol loops integrated with chillers. Implemented primarily in buildings, data centers, and industrial facilities, free cooling achieves substantial reductions in electricity consumption—often by 30-70% during favorable ambient conditions—by prioritizing passive or low-power over refrigeration cycles. Its adoption has grown with rising energy costs and mandates, though effectiveness depends on climate, system design, and controls to manage air quality, , and risks. Key variants include direct free cooling for milder climates and indirect systems for humid environments, with ongoing advancements focusing on integrations for year-round optimization.

Fundamental Principles

Thermodynamic Foundations

Free cooling operates on the principle of utilizing ambient environmental conditions, such as lower outdoor air or temperatures, to reject from a without the energy-intensive typical of cycles. This approach exploits natural temperature gradients where the ambient temperature falls below the system's return fluid temperature, enabling passive heat dissipation through conduction, , or evaporative processes driven solely by thermodynamic differentials. The causal arises from 's inherent tendency to flow from higher to lower states, minimizing destruction compared to active , which requires electrical input to invert this gradient via phase changes and . At its core, in free cooling follows the equation Q = \dot{m} C_p \Delta T, where Q is the rate, \dot{m} is the of the , C_p is the , and \Delta T is the difference between the system and ambient medium. For convective at surfaces, applies: q = h (T_s - T_\infty), with q as , h as the convective ( 10–100 W/m²K for air and higher for ), T_s the surface , and T_\infty the ambient . These relations hold empirically across lab validations and simulations, confirming that no compressor work is needed when \Delta T > 0, though auxiliary fans or pumps may consume minimal for circulation, yielding coefficients of () exceeding —often 5–10 or higher in favorable conditions—far surpassing standard COPs of 3–6. In air-side free cooling, psychrometric considerations incorporate both sensible and latent heat via enthalpy differences, where viable operation requires outdoor air enthalpy below return air enthalpy to avoid excess humidity introduction. Enthalpy h combines dry air sensible heat and vapor latent heat, calculated as h = C_p T + \omega (h_g + C_{pv} T), with \omega as humidity ratio, h_g latent heat of vaporization, and C_{pv} vapor specific heat; this ensures total heat rejection without mechanical dehumidification when ambient wet-bulb temperatures enable sufficient \Delta h. Empirical psychrometric charts and field data validate that such conditions, prevalent in temperate climates during cooler seasons, achieve heat rejection rates aligning with the above equations, underscoring the method's reliance on verifiable thermodynamic state properties rather than contrived energy inputs.

Key System Components

Free cooling systems incorporate specialized hardware to harness ambient air or water for heat rejection, bypassing compressor operation in mechanical chillers or air handlers. Essential components include economizers, which for air-side applications feature modular damper assemblies—typically comprising low-leakage outdoor air intake s, return air s, and exhaust s—to regulate the mixture of ambient and recirculated air based on outdoor conditions. These s, often constructed from galvanized steel with rubber seals for airtightness, integrate actuators driven by 24V signals from controllers to enable precise modulation, minimizing infiltration losses. Sensors form a critical layer, with sensors, relative humidity probes, and sensors mounted at outdoor intakes and mixed-air plenums to evaluate free cooling viability against indoor setpoints, typically triggering operation when outdoor falls below a 2-3 kJ/kg threshold relative to return air. Cooling coils, integral to both air- and water-side setups, utilize with aluminum fins for efficient ; in waterside configurations, these may include brazed-plate heat exchangers or tube-in-tube designs rated for glycol solutions to prevent freezing. Integration with chillers or air handlers employs bypass valves, such as three-way modulating butterfly valves, to divert flow from the to free cooling coils during suitable conditions, ensuring chilled water temperatures remain at 6-7°C without engagement. These valves, often with electric or pneumatic actuators, facilitate mode switching with minimal pressure drop, typically under 10 kPa. Durability is prioritized through corrosion-resistant materials, including epoxy-coated coils and stainless-steel exchanger plates compliant with standards, extending service life in variable ambient exposures up to 20-30 years under proper maintenance.

Historical Development

Origins in HVAC Engineering

The concept of free cooling originated in early 20th-century systems, where were employed to bypass mechanical chillers during winter months, utilizing ambient low temperatures for evaporative water chilling without compressor operation. This practice, rooted in advancements in design patented around 1910 by engineers Frederik van Iterson and Kuypers, allowed direct use of tower-cooled water for process needs when outdoor conditions sufficed, as seen in power generation and facilities by the 1920s and 1930s. Post-World War II expansion of into commercial buildings introduced air-side cycles, which drew cooler outdoor air to satisfy cooling loads and minimize mechanical refrigeration runtime. These systems, integrated into central HVAC setups for office towers and retail spaces during the 1950s building boom, prioritized operational reliability and capacity matching over , as costs remained low relative to installation expenses. The 1973 oil embargo and subsequent energy price spikes prompted widespread HVAC retrofits emphasizing free cooling for cost reduction, with Standard 90-1975 mandating economizers in new systems over 135,000 Btu/h capacity to leverage ambient conditions. field studies from the mid-1970s quantified benefits, reporting annual energy savings of 20-50% in chiller operation for temperate climates through extended bypass modes, based on monitored commercial installations where free cooling hours exceeded 2,000 per year.

Evolution in Data Center Applications

During the 1990s and early 2000s, the rapid expansion of server rooms and nascent data centers, driven by surging internet demand and IT equipment densities up to several kilowatts per rack, prompted engineers to adopt economizers for utilizing cooler outside air. This direct free cooling method bypassed mechanical chillers during favorable ambient conditions, reducing compressor runtime and achieving PUE values below 1.5 in early implementations where climates permitted. Such adaptations addressed the limitations of traditional raised-floor air distribution, which struggled with uneven cooling under high loads, by prioritizing airflow optimization over constant mechanical intervention. By the late 2000s, hyperscalers like pioneered chiller-less architectures in locations with moderate winters, exemplified by the 2009 Belgium facility that relied solely on air-side economizers and evaporative assist for cooling, eliminating traditional infrastructure to cut energy overhead. This engineering choice extended to the 2011 , site, where sub-zero ambient air enabled near-continuous free cooling, supplemented by heat exchange only during rare peaks, yielding quarterly PUEs around 1.14 through retrofitted controls. These cases highlighted pragmatic site selection for high-density IT, focusing on and to mitigate rather than universal applicability. In the , refinements targeted hyperscale operations with densities exceeding 10 kW per rack, incorporating automated dampers, variable-speed fans, and sensors aligned with TC 9.9 guidelines. The 2011 thermal envelope expansion to 18–27°C inlet air for Class A1 servers allowed extended hours without exceeding equipment tolerances, as validated in field tests showing no reliability degradation at higher averages. Predictive algorithms further optimized transitions, minimizing risks in transitional modes and enabling PUE reductions of 10–20% in compatible climates via longer free cooling windows. Location-specific performance data reveal stark viability contrasts. Nordic facilities, leveraging average winter temperatures below 0°C, sustain free cooling for over 90% of annual hours, attaining PUEs of 1.1–1.2 through direct air intake with minimal mechanical backup. In desert sites like , where daytime highs exceed 40°C for much of the year, direct methods limit to nocturnal or seasonal use, often hybridizing with glycol loops for indirect cooling to avoid dust ingress and maintain guidelines, resulting in average PUEs above 1.5 and underscoring the need for engineered redundancy over ambient reliance.

Operational Methods

Direct Free Cooling Techniques

Direct free cooling techniques utilize unconditioned outdoor air or water sources to reject heat directly from the conditioned space or chilled water loop, bypassing mechanical refrigeration components for energy savings when ambient conditions permit. These methods prioritize simplicity by avoiding intermediary heat exchangers, enabling higher coefficients of performance (COP) in cold climates through natural thermodynamic gradients. Air-side economizers represent a primary direct technique, where filtered outdoor air is drawn directly into the HVAC system to cool the space or over evaporator coils, modulating the mix of return and outdoor air based on or temperature differentials. This approach integrates dampers, filters, and fans to introduce cool ambient air when its falls below the return air temperature, often achieving full cooling without operation in sub-10°C ambients. In applications, direct air-side economizers can deliver up to 100% off-time by ventilating server halls with preconditioned outdoor air, provided prevents contaminant ingress. Water-side direct free cooling employs to produce chilled without activation, routing tower through the load side via minimal infrastructure. The strainer cycle variant directly connects the open cooling tower loop to the closed chilled circuit using a coarse strainer to capture , three-way valves, and pumps, allowing tower to circulate through building coils when its temperature suffices for load rejection. This method offers operational simplicity and values exceeding 10 in low wet-bulb conditions, as it leverages evaporative cooling directly without plate heat exchangers. Refrigerant migration provides another direct variant in chiller systems, where, upon compressor shutdown, refrigerant vapor naturally migrates from the warmer evaporator to the cooler condenser—chilled by tower water—while liquid refrigerant flows back, maintaining evaporation without auxiliary pumps. Effective in ambients below 7°C wet-bulb, this passive process can yield 100% free cooling hours annually in temperate zones, reducing energy use by eliminating compressor power draw. Limitations include dependency on refrigerant type and system design, with modern hydrofluoroolefins like R-32 enhancing migration efficiency due to favorable vapor pressures. These techniques excel in and peak , attaining compressor off-times approaching 100% during prolonged cold periods, as validated in analyses of systems operating below 10°C effective ambients. However, direct exposure necessitates robust and to mitigate or air quality risks, ensuring longevity without compromising performance.

Indirect Free Cooling Techniques

Indirect free cooling techniques utilize heat exchangers to transfer between isolated indoor and outdoor fluid or air streams, thereby avoiding direct mixing that could introduce contaminants, , or excess into the conditioned . This separation is achieved through devices such as plate-and-frame heat exchangers or closed-loop systems employing glycol as a medium, where outdoor ambient conditions cool the secondary loop before it preconditions the primary indoor cooling circuit. In plate-and-frame configurations, thin plates facilitate efficient counterflow heat exchange between water or glycol streams, maintaining isolation while enabling free cooling when outdoor temperatures fall below indoor requirements, typically by 5–10°C (9–18°F). Glycol-loop systems, often paired with dry coolers (air-cooled finned-tube s), circulate a glycol-water mixture exposed to ambient air on the outdoor side, which then rejects heat to the indoor chilled water loop via the exchanger. These setups provide advantages in humid climates by eliminating evaporative processes that could raise indoor relative , as dry coolers rely solely on transfer without addition, preserving tighter control over and preventing or microbial growth risks associated with moist outdoor air. Unlike direct methods, indirect approaches mitigate burdens and imbalances but incur drawbacks from added thermal resistance in the heat exchanger, which imposes an approach differential of 1–5°F (0.5–2.8°C), thereby limiting the effective utilization of cold outdoor conditions. Field evaluations indicate that indirect free cooling delivers lower than direct equivalents due to these intermediary losses and auxiliary pumping requirements for the secondary loop, often achieving 70–80% of the power savings potential in comparable installations, as derived from manufacturer performance data in applications. For instance, while direct systems can bypass compressors entirely in mild conditions, indirect variants may require partial mechanical supplementation sooner, increasing operational complexity and initial capital for the exchanger and circulation components. Despite these trade-offs, indirect techniques enhance reliability in polluted or variable environments by decoupling indoor conditions from outdoor fluctuations, supporting applications where air quality standards preclude direct economization.

Integrated and Hybrid Systems

Integrated free cooling systems incorporate water-side economizers into plants, allowing chilled water production via circulation when outdoor wet-bulb temperatures permit, typically switching automatically when the ambient wet-bulb drops below the chilled water setpoint plus a approach temperature margin. This integration bypasses operation, reducing energy use by leveraging evaporative cooling from towers, with controls monitoring wet-bulb conditions to enable partial or full free cooling modes as load decreases, such as entering free cooling at wet-bulb temperatures up to 10°F higher than full-load thresholds during off-peak seasons. However, causal trade-offs arise from added , valves, and requirements, which increase initial and potential needs, necessitating precise sizing to prevent over-circulation losses or insufficient heat rejection during transitions. Hybrid systems blend free cooling with mechanical alternatives like direct expansion (DX) or absorption chillers, employing dynamic controls to modulate between modes based on real-time ambient data, load demands, and metrics, with advancements in the 2020s incorporating predictive algorithms for preempting switchovers and minimizing cycling. For instance, DX hybrids integrate air-side free cooling coils ahead of evaporator stages, diverting outdoor air when viable to subcool refrigerant and reduce electrical input, while absorption hybrids pair lithium-bromide cycles with free cooling for heat rejection, offering in high-humidity climates where DX falters. These designs prioritize reliability by maintaining backup for extreme conditions, but introduce complexity in logic to avoid conflicts, such as humidity-induced coil freezing in DX paths or variable generator firing in absorption units, demanding empirical validation over models to account for site-specific variables like or part-load degradation. Real-world deployments of hybrid free cooling in data centers have demonstrated payback periods of 2 to 3 years in temperate climates with sufficient cooling hours, driven by 30-50% annual energy savings from optimized mode switching, though actual performance often trails modeled projections due to unaccounted factors like delays or ambient variability. Such systems underscore the need for causal realism in design, balancing free cooling's passive efficiency against mechanical reliability without assuming seamless integration, as evidenced by field studies showing 10-20% efficiency gains from retrofitted dynamic but requiring ongoing to sustain benefits.

Environmental and Seasonal Factors

Climate Dependencies

Free cooling systems rely on ambient dry-bulb temperatures typically below 13–18°C for effective direct air-side operation, as higher outdoor temperatures necessitate supplemental mechanical cooling to maintain indoor supply air at safe levels for equipment, such as 18–27°C per ASHRAE guidelines for data centers. Humidity introduces additional constraints, requiring evaluation via psychrometric charts to ensure outdoor air enthalpy does not exceed indoor limits, preventing condensation risks and excessive dehumidification energy; for instance, wet-bulb temperatures under 13°C (55°F) for at least 3,000 hours annually enable substantial free cooling hours in suitable climates. These thresholds underscore that free cooling is not universally applicable, as claims of broad efficacy often overlook site-specific psychrometric viability, leading to overestimation in warmer regions. Geographic suitability varies markedly, with temperate zones like and offering extended free cooling potential due to prolonged sub-threshold conditions—often exceeding 5,000 annual hours—facilitating near-continuous operation without compressors. In contrast, tropical or subtropical areas exhibit minimal viability, with hot-humid conditions rarely meeting dry-bulb or criteria, resulting in free cooling hours below 1,000 annually and frequent reliance on energy-intensive alternatives. Empirical data from mixed-humid and marine climates show location-specific (PUE) reductions of 0.2–0.5 through free cooling integration, but such gains evaporate in persistently warm sites, where systems without robust backups face operational failures or efficiency penalties exceeding 20% in cooling load. Emerging climate models indicate that could shorten viable free cooling seasons by 5–10% per decade in mid-latitude facilities, as rising baseline temperatures push more hours beyond psychrometric thresholds, challenging long-term projections that assume static climatic envelopes. This trend highlights the need for hybrid designs in transitional zones, debunking assumptions of indefinite scalability without adaptive measures, as evidenced by reduced runtime in projections for even temperate locales.

Performance Across Seasons

In winter conditions, where ambient dry-bulb temperatures consistently fall below the data center's required chilled water supply temperature—typically around 7–12°C—free cooling systems achieve full operational dominance through direct or indirect economizer modes, bypassing mechanical chillers entirely and relying on outdoor air or water sources for heat rejection. This mode maximizes runtime for free cooling components, with systems like water-side economizers enabling near-continuous operation during periods of sub-zero or low single-digit Celsius outdoor temperatures. During transitional mid-seasons, such as and autumn, when ambient temperatures fluctuate around or slightly above the cooling setpoint, free cooling shifts to partial modes involving mixed : dampers partially open to introduce outdoor air blended with recirculated indoor air, or variable-speed pumps modulate flow to supplement mechanical cooling. Adaptive controls, including proportional-integral-derivative () algorithms, dynamically adjust mixing ratios to optimize sensible cooling while minimizing energy input from compressors. However, these periods often necessitate frequent mode switching—between full free cooling, partial economization, and mechanical fallback—as diurnal temperature swings trigger transitions, potentially accelerating wear on valves, actuators, and fans due to repeated analogous to HVAC system stresses. In summer, with ambient temperatures exceeding viable thresholds (e.g., wet-bulb temperatures above 18–20°C), free cooling contributes minimally or not at all, defaulting to full mechanical to maintain precise air conditions around 20–27°C. Across all seasons, management is critical: sensors monitor outdoor against coil or supply surface temperatures, closing economizers or activating dehumidification if the supply air risk falls below the to prevent on cold surfaces, which could lead to equipment or short circuits. Field data from optimized sites indicate free cooling can extend chiller-free by 30–40 percentage points during winter and mid-seasons, reducing overall annual mechanical accordingly in temperate climates. Yet, mid-season inefficiencies arise from suboptimal partial mixing, where frequent setpoint adjustments increase control complexity and potential for transient instabilities in or uniformity.

Primary Applications

Data Centers and Server Facilities

Free cooling systems are extensively deployed in data centers situated in cold climates, where external temperatures permit extended operation without mechanical , facilitating (PUE) ratings below 1.2 by reducing cooling energy to less than 20% of total power draw. Direct free cooling, which introduces outdoor air into halls, proves viable for centers in remote or pristine environments with low pollutant levels, enabling rapid deployment and minimal infrastructure. In contrast, indirect free cooling via heat exchangers or glycol loops predominates in urban facilities, isolating IT equipment from external air to maintain controlled conditions amid higher ambient dust and emissions. Field implementations demonstrate average cooling energy reductions of around 20% annually through direct air-side free cooling, particularly when outdoor conditions align with guidelines for server inlet temperatures. These gains, however, are offset by ancillary expenses, such as advanced to capture , which impose drops elevating power by up to 14% in unoptimized setups, alongside dehumidification or reheat processes to avert risks. Direct exposure in free cooling exacerbates risks from dust, hydrocarbons, and corrosive pollutants infiltrating servers, accelerating degradation and necessitating frequent or early replacements. To safeguard against such failures, operators incorporate redundant chillers or systems, incurring 20-50% higher than standard cooling alone, as uninterrupted operation remains paramount given hourly downtime valuations exceeding $300,000.

Industrial Processes and Buildings

In industrial processes such as and warehousing, free cooling is often implemented via water-side economizers in plants, where bypass allows chilled water production using ambient wet-bulb temperatures below the required supply temperature, bypassing mechanical compressors. This approach has demonstrated reductions of 20-50% in annual chiller consumption, depending on local ambient conditions and system design. For instance, a specialty chemical manufacturer achieved 42% annual savings by integrating a 360 kW free cooler with existing air-cooled s, primarily driven by reduced operational hours for equipment. Economic incentives, such as lowered utility costs, predominate as motivators, with environmental gains like reduced carbon emissions requiring post-implementation audits for verification rather than assumed benefits. Office buildings commonly employ air-side s for free cooling, modulating outdoor air intake to leverage cooler ambient conditions for space cooling, thereby minimizing reliance on mechanical refrigeration. These systems can yield 20-30% savings in cooling energy when properly controlled, though actual performance varies with climate and setpoint accuracy; economizer failures or suboptimal configurations have negated savings in up to 40% of installations. Integrated free cooling s in moderate climates further enhance efficiency for larger commercial structures by combining economizer modes with partial-load chiller operation. Retrofitting free cooling into legacy industrial buildings and processes presents scalability limits due to spatial constraints, incompatible piping in older chiller plants, and structural modifications needed for tower bypass or economizer dampers. While feasible in existing systems, such upgrades often require custom to address uneven or deficiencies, potentially offsetting short-term savings against upfront costs exceeding those of installations. In facilities with outdated HVAC, these challenges can limit applicability to 15-30% reductions without comprehensive overhauls.

Efficiency and Benefits

Quantifiable Energy Reductions

Free cooling techniques primarily reduce energy use by eliminating and operations, substituting ambient air or for when conditions permit, thereby targeting the 30-40% of total power typically allocated to cooling. In validated simulations of air-side economizers for 90 kW modular s, cooling dropped by 76% in and 86% in relative to baseline systems, reflecting favorable moderate climates with extended free cooling hours. Direct air-side free cooling optimizations have yielded over 46% reductions in cooling energy during winter weeks in modeled frameworks accounting for weather variability and , though fan power dominates (over 93%) during these periods, limiting net gains to about 5% overall in summer transitions. Water-side free cooling with cooling towers can achieve up to 70% cuts in energy demands by offloading mechanical loads, as evidenced in efficiency analyses comparing to traditional centrifugal systems. These savings translate to measurable kWh reductions in deployments; a 75 m² installation saved 100,000 kWh annually via integrated free cooling, primarily through reduced cycles. In cell sites, free cooling versus realized 24% energy savings in 2021 and 39% in 2022 under varying loads. Power Usage Effectiveness (PUE) improves with free cooling by shrinking non-IT overhead, contributing to industry-wide declines of 25% in average PUE from 2010-2020 through such non-mechanical strategies, though isolated retrofits show incremental drops like 1.22 to 1.14 in specific facilities. Real-world outcomes frequently underperform theoretical maxima, with 2020s audits highlighting 20-50% shortfalls from projections due to suboptimal controls, partial IT loads, and auxiliary fan/dehumidification needs that erode free cooling viability beyond ideal cold-dry seasons.

Economic and Operational Advantages

Free cooling systems offer economic advantages primarily through reduced operational expenditures (OPEX), as they minimize reliance on energy-intensive mechanical refrigeration during favorable ambient conditions, leading to payback periods of approximately 2-3 years for installations in data centers and industrial facilities. This ROI is enhanced in regions with extended periods of low external temperatures, where free cooling can be utilized for thousands of additional hours annually compared to traditional thresholds, offsetting initial capital investments in ancillary equipment like heat exchangers or economizers. Business cases are particularly compelling in areas with elevated electricity tariffs, such as cold-climate locales with high energy costs, where the differential between free and mechanical cooling amplifies long-term capital expenditure (CAPEX) recovery without universal applicability across all sites. Operationally, free cooling simplifies system management by bypassing compressors and chillers in suitable seasons, thereby curtailing wear on these components and extending their , which lowers overall maintenance demands. Indirect configurations further reduce upkeep expenses by obviating the need for frequent filter replacements and associated labor, while dynamic controls enable seamless transitions without manual intervention, promoting reliability in variable loads. Compared to alternatives like liquid cooling, free cooling provides quieter during engagement—relying on fans and natural rather than constant mechanical cycling—and easier into existing air-handling , though it lacks the density-handling consistency of fluid-based methods in perpetual high-load scenarios. These attributes make it operationally preferable for facilities prioritizing seasonal simplicity over year-round uniformity, provided site-specific climate data supports frequent activation.

Limitations and Challenges

Technical Constraints

Indirect free cooling systems, which employ heat exchangers to transfer from process fluids to ambient air or without direct mixing, are constrained by inherent inefficiencies arising from finite approaches and conductive resistances. These exchangers typically require a minimum approach of 1-3°C between the ambient medium and the chilled fluid outlet, preventing the system from achieving the theoretical limit of ambient cooling and resulting in destruction due to irreversible flow across gradients, as dictated by the second law of thermodynamics. This leads to a reduced coefficient of performance () compared to direct methods, with indirect configurations exhibiting lower overall owing to the additional resistance layers. Under variable thermal loads, free cooling capacity experiences inherent drops because the system's rejection relies on fixed exchanger surfaces optimized for conditions, limiting without supplementary ; for instance, partial load operation often necessitates hybrid modes where staging incurs penalties from non-optimal rates and drops. Humidity management introduces further engineering limits, as ambient air introduction in air-side free cooling can elevate indoor , risking on surfaces maintained below the and necessitating integrated dehumidification via cooling coils or desiccants, which impose parasitic loads from fan power and removal that counteract sensible cooling gains. These processes add thermodynamic penalties, as dehumidification requires overcooling followed by reheating to maintain supply air conditions, amplifying dissipation in psychrometric cycles. Overall, such constraints manifest in practical efficiency reductions of 10-30% relative to idealized reversible processes, stemming from non-ideal heat and irreversibilities.

Real-World Implementation Issues

Implementation of free cooling systems in data centers is highly sensitive to geographic location, with performance deteriorating markedly in warmer or humid climates where ambient conditions rarely permit sufficient hours. For instance, facilities in cooler regions like the can leverage free cooling for extended periods, achieving substantial energy reductions, whereas those in subtropical areas such as face limited viability, often reverting to mechanical cooling and experiencing projected savings shortfalls of 20% or more due to mismatched site selection. This underperformance arises from fewer opportunities for , compelling hybrid operations that undermine the technology's promised efficiency gains and leading to criticisms that initial hype overlooks regional climatic constraints. Maintenance demands pose significant real-world hurdles, as introducing outdoor air exacerbates clogging from dust and pollutants, increasing drops and forcing fans to consume excess —potentially up to 15% more due to restricted . drift in and monitors further complicates reliable switching between free and modes, while inadequate accelerates , with clogged systems imposing an "energy tax" that erodes anticipated savings. Deployments have highlighted how neglected upkeep results in higher operational costs, as operators must frequently replace filters and recalibrate controls to mitigate these issues, often revealing overoptimistic projections that ignore such ancillary burdens. Reliability concerns amplify costs, as free cooling's dependence on variable necessitates robust mechanical backups, which inflate energy use when activated during unexpected warm spells or high humidity. Airborne contaminants introduced via economizers promote on servers and electrical components, particularly under lead-free regulations, contributing to unplanned outages with average downtime expenses reaching $5,600 per minute or $300,000 per hour. Empirical critiques note that auxiliary components like fans and pumps draw hidden power—scaling cubically with speed increases—offsetting 5-10% of touted savings and sparking debates over whether the approach's upfront economies justify the elevated risk and expenses in non-ideal deployments.

Recent Advances

Innovations Post-2020

Advancements in dynamic control systems have enabled real-time optimization of free cooling operations, particularly through AI-driven algorithms that predict thermal loads and switch between free cooling and mechanical modes based on ambient conditions and internal demands. These systems utilize to analyze data on , variations, and workload patterns, achieving up to 20% reductions in energy use for cooling in data centers by minimizing reliance on compressors during viable free cooling windows. Such controls have been implemented in pilots for medium-density facilities, where genetic algorithm-based frameworks optimize fan-wall systems for hybrid air-free cooling setups. Hybrid free cooling architectures integrating air or water-based free cooling with direct liquid cooling have emerged to address high-density AI workloads, allowing seamless transitions to handle rack densities exceeding 100 kW. In data center pilots from 2023 onward, these hybrids employ evaporative free cooling stages followed by liquid loops for residual heat rejection, reducing overall power usage effectiveness (PUE) by leveraging external cold sources when available. For instance, adiabatic fluid coolers in hybrid configurations have demonstrated halved energy consumption compared to traditional systems in AI-focused environments, though efficacy remains constrained by local humidity and temperature profiles. Material innovations, including microchannel and brazed plate heat exchangers, have enhanced free cooling by improving coefficients in indirect systems, enabling tighter approaches between external fluids and internal loops. These exchangers facilitate glycol-water separation in free cooling coils, boosting capacity without proportional increases in footprint or pressure drop. Empirical evaluations by organizations like NREL indicate that such advancements extend free cooling hours in psychrometric bin analyses, yet viability is fundamentally limited to climates with sufficient sub-wet-bulb , as quantified in envelope assessments. Integrations of surfaces with conventional free cooling have provided passive augmentation, particularly for daytime operations where solar loads previously curtailed viability. Sky-facing panels with high mid-infrared emissivity dissipate heat to space, supplementing evaporative or air-side free cooling in data centers and yielding net cooling even under partial , as demonstrated in field tests reducing loads by 10-15% in arid regions. However, depends on surface area and atmospheric transparency, with empirical data underscoring persistent climate dependencies that prevent universal adoption.

Market Growth and Projections

The global free cooling systems market was valued at approximately USD 1.5 billion in 2024, reflecting adoption in s and facilities where ambient conditions permit reduced cooling reliance. Projections indicate growth to USD 3.2 billion by 2033, at a (CAGR) of 9.2%, primarily propelled by the expansion of hyperscale and edge s in cooler climates, such as parts of and , where free air economizers enable significant operational cost reductions. This trajectory aligns with broader cooling demands, estimated at USD 16.9 billion in 2023 and forecasted to reach USD 51.3 billion by 2030, though free cooling constitutes a niche segment limited by geographic viability. Longer-term forecasts for the overall cooling market, encompassing free cooling integrations, project expansion to USD 100.12 billion by 2035 from USD 25.77 billion in 2024, with a CAGR of 12.55%, driven by surging computational loads from and services. Free cooling's role within this is expected to grow modestly where energy prices incentivize passive methods—such as in regions with volatile costs exceeding USD 0.10 per kWh—yielding up to 40% savings compared to constant compressor operation, but universal scaling remains constrained by site-specific factors like and thresholds below 20°C dry bulb for optimal efficacy. Empirical data from hyperscale operators, including deployments in facilities, underscore this cost-energy nexus over regulatory mandates, as free cooling hours correlate more directly with local patterns than policy incentives. Emerging trends favor free cooling in distributed edge networks and retrofits for existing low-density farms, yet shifts toward high-density and alternatives—projected to capture over 20% of new installations by 2030—may erode its in warmer or urban locales, emphasizing inherent physical limits over optimistic policy-fueled narratives. Real-world data reveals that only 30-50% of annual operating hours in temperate zones support full free cooling, capping broader absent complementary systems.

References

  1. [1]
    Free Cooling Fundamentals in Modular HVAC Chillers
    Apr 19, 2018 · Free Cooling, simply put, is using colder ambient air (colder than the supply chilled water set point) to perform cooling rather than the refrigeration cycle ...
  2. [2]
    What Is Free Cooling In Chiller Operation - Tower Water
    May 1, 2023 · Free cooling is a type of cooling operation that utilizes low-temperature outside air to cool water or other fluids without mechanical refrigeration.<|separator|>
  3. [3]
    What Is Free Cooling? Free Cooling HVAC Chillers Guide
    Jan 20, 2023 · Free cooling is a type of cooling system design. It uses ambient temperatures to reduce or eliminate the need for a chiller or compressor operation.
  4. [4]
    [PDF] A Next-Generation Passive Cooling Design for Data Centers - OSTI
    Jul 20, 2011 · The benefits are many: The “free-cooling” system design drastically reduces energy consumption; chiller-less, free-cooling technology eliminates ...
  5. [5]
    Towards energy-efficient data centers: A comprehensive review of ...
    Sep 1, 2024 · This study reveals that free cooling is widely employed, with Artificial Neural Networks emerging as the most popular algorithm for managing ...
  6. [6]
    (PDF) Free cooling technologies for data centers: energy saving ...
    Aug 6, 2025 · In this paper, four typical free cooling systems are analyzed and compared, to show their mechanisms, main features, energy saving effects and ...
  7. [7]
    MAXIMIZING EFFICIENCY WITH FREE COOLING - Process Cooling
    A free cooling system reduces energy use by using a fluid cooler or cooling tower to cool the process fluid in place of a chiller.
  8. [8]
    Free cooling or compressor cooling? | www.swegon.com
    Free cooling is the process of using external ambient temperature to enable cooling and by that reduce, or possibly avoid, the use of a chiller.Cold Outdoor Air Provides... · Cooling By Compressor -- The... · Is Free Cooling Possible...
  9. [9]
    A closer look at free cooling - DATA4
    Sep 20, 2021 · Key Principles of Free Cooling. Free cooling is optimal when the outdoor temperature is lower than that anticipated within the IT rooms. In ...
  10. [10]
    [PDF] Free Cooling
    to avoid the energy costs associated with operating the chiller. Obviously, some other means of producing the ...
  11. [11]
    Understanding Convective Heat Transfer: Coefficients, Formulas ...
    Free Convection - water and liquids: 50 - 3000 (W/(m2K)) · Forced Convection - air, gases and dry vapors: 10 - 1000 (W/(m2K)) · Forced Convection - water and ...
  12. [12]
    Free Cooling is Available - Metasys - Johnson Controls
    Free Cooling Available is True when: the supply fan is running. the calculated outside air enthalpy is less than the calculated return air enthalpy. the outside ...
  13. [13]
    [PDF] Air Water Vapor Mixtures: Psychrometrics - MIT OpenCourseWare
    The total enthalpy is the sum of the enthalpy of the air and water vapor, ... In a way this could be termed free cooling, but the price is water consumption.
  14. [14]
    The Importance of Enthalpy in Free Cooling for AHUs - Andivi
    By measuring enthalpy, sensors provide a comprehensive understanding of the total heat content, ensuring that free cooling is applied under the most favorable ...
  15. [15]
    Use an Air-Side Economizer | ENERGY STAR
    An air-side economizer (see Figure 1 below) brings cool air from outdoors into a building and distributes it to the servers.
  16. [16]
  17. [17]
  18. [18]
    [PDF] Automated Free Cooling | Field Controls
    Indoor/outdoor temperature sensors automatically signal ultra-quiet, positive seal dampers and engage the central fan to bring in cool air while exhausting warm ...
  19. [19]
    The Pros and Cons: Integrated Water-Side Economizer Systems
    Similar in concept to a dry cooler, integrated free cooling uses glycol to air coils, but unlike dry coolers, these coils are typically attached to the chiller ...
  20. [20]
    The Effectiveness of Butterfly Valves and Sensors in a Hybrid Free ...
    Nov 5, 2021 · The 3-way change-over butterfly valve handles the change-over between free cooling and cooling with the chiller. Two 3-way control butterfly ...
  21. [21]
    [PDF] Free Cooling Using WaterEconomizers - Trane
    economizer system "must satisfy 100% of the expected system cooling load at. 45°F dry bulb/40°F (4ºC) wet bulb." Table 6.5.1 Minimum system size for which an.
  22. [22]
    History of Cooling Towers
    Aug 15, 2023 · In the early 20th century, two Dutch engineers, Frederik van Iterson and Gerard Kuypers, patented a new type of cooling tower design called the ...
  23. [23]
    Cooling Tower Technology: An Historical Perspective | ACHR News
    Apr 26, 2001 · By the early 20th century, advances in cooling towers were fueled by the rapidly growing electric power industry. The cooling loads created ...Missing: engineering chiller bypass
  24. [24]
    The 1940s: World War II And The Postwar Boom | ACHR News
    Nov 6, 2001 · The balance of the 1940s saw massive production increases brought on by a booming housing market and the increased use of the automobile.
  25. [25]
    [PDF] Our Seminar Goal!!
    Sep 26, 2016 · Standard 90.1 originated in 1975 in response to the energy crisis of the early 1970s. It was revised in 1980, but became more prominent in ...
  26. [26]
    [PDF] Emergence and Expansion of Liquid Cooling in Mainstream Data ...
    During the. 1990s and early 2000s, IT equipment power draw increased regularly. ... Existing large- scale data centers expecting significant future adoption of ...
  27. [27]
    Free cooling of data centers: A review - ScienceDirect.com
    This paper reviews the advancements of data center free cooling mainly focusing on configuration features and performances.Free Cooling Of Data Centers... · Airside Free Cooling · Heat Pipe System<|separator|>
  28. [28]
    The Evolution of Data Center Cooling - Schneider Electric Blog
    Jun 3, 2021 · For the past few years, the data centres used pressurised air from a raised floor for cooling. The air that is moved by the constant speed of a ...
  29. [29]
    Google's Chiller-less Data Center
    Jul 15, 2009 · Google has begun operating data center in Belgium that has no chillers to support its cooling systems, which will improve energy efficiency.
  30. [30]
    Power usage effectiveness - Google Data Centers
    Cooling system retrofits at data centers D and E reduced quarterly PUEs from 1.22 and 1.19 last year to 1.14 in Q1 2012. Data Center A reported a higher than ...Missing: implementations | Show results with:implementations
  31. [31]
    Google opens energy-efficient data center in chilly Finland
    Sep 13, 2011 · The new server station in Hamina will use cool air temperatures and the Gulf of Finland's chilly waters to make the center energy-efficient.
  32. [32]
    [PDF] ASHRAE TC9.9 Data Center Power Equipment Thermal Guidelines ...
    The original ASHRAE air temperature recommended envelope for data centers was 20-25°C (68-77°F).
  33. [33]
    Evolving Data Center Cooling Environmental Ranges and Standards
    Mar 8, 2016 · The majority of data centers cooling practices have been based on ASHRAE's Technical Committee 9.9 (TC 9.9) Mission Critical Facilities, ...
  34. [34]
    The Arctic Advantage: How cold climates boost data center ... - Vaisala
    Cold climates offer long periods of free cooling · Nordic locations reduce water use · Heat recovery and reuse minimizes data center carbon footprints · The ...
  35. [35]
    Cooling Solutions for Bitcoin Mining in Desert vs. Arctic Climates
    Apr 29, 2025 · This report compares various cooling solutions – natural ventilation, air cooling, water cooling, immersion cooling, and oil-based cooling – and ...
  36. [36]
    [PDF] Keeping Cool with Outdoor Air: Airside Economizers - Trane
    Airside economizers use outdoor air to cool spaces, especially when it's colder outside, by adjusting the mix of outdoor and return air, sometimes without ...
  37. [37]
    Energy savings in direct air-side free cooling data centers
    Apr 1, 2024 · In data centers utilizing direct air-side economizers (DASEs)—a free cooling technology that introduces cool outdoor air directly into the data ...
  38. [38]
    Economizer in HVAC: Ain't No Fooling With Free Cooling
    Nov 18, 2017 · Remember that while the concept of “free cooling” sounds simple, the integration of sensors, dampers, and controls requires careful attention to ...
  39. [39]
    [PDF] Energy Conservation through Filtration and Hydronic Free Cooling
    A strainer cycle is a method of free cooling directly connecting the cooling tower (open system) to the building loop through a strainer that in theory would ...
  40. [40]
    Free Cooling and HVAC Optimization - tekWorx
    Free cooling is an economical method of using low external air temperatures chill water without mechanical cooling, greatly reducing energy cost.
  41. [41]
    How Waterside Economizers Work - MEP Academy
    Mar 29, 2023 · A 100% free cooling allows for the chiller to be shutoff and the cooling tower along with a heat exchanger to do all the cooling. We will show ...Integrated Waterside... · Adding a Waterside... · Non-Integrated Waterside...
  42. [42]
    about-r-32-free-cooling-and-natural-migration - News Center
    Nov 18, 2020 · R-32 is an ideal refrigerant for natural migration, namely the free circulation of refrigerant within the unit's circuit, with no need for additional pumps.
  43. [43]
    Waterside Economizer (WiSE) Free Cooling - Nortek Air Solutions
    WiSE uses a cooling tower, condenser, water piping, control valves, and water coils to provide cooling without compressor operation, called "free cooling".
  44. [44]
    Free Cooling - Chiller Designs
    Free cooling is only of significant value when the ambient wet bulb temperature is lower than the design return chilled water by about 10°F.
  45. [45]
    Free Cooling – Direct and Indirect - Stulz
    Free Cooling. Free Cooling means that the power consumption of the air conditioning system at the site is reduced to the necessary minimum by suitable means, ...
  46. [46]
    Free cooling with water - Alfa Laval
    Plus, with a compact plate heat exchanger in your system, you can isolate the chilled water loop from all your sensitive equipment and confidently eliminate any ...Missing: humid | Show results with:humid
  47. [47]
    [PDF] A New Era of Free Cooling - Trane
    The element of common piping is a section of return main located between the two tees. The primary system is unaffected by exchanger pump operation. Likewise, ...
  48. [48]
    Cooling for data centres | www.swegon.com
    With indirect free cooling, the outdoor air cools a heat transfer medium, which then in turn cools the computer equipment. This provides far better control of ...Missing: techniques | Show results with:techniques
  49. [49]
    Free Cooling: reducing energy costs in Data Centers - ARANER
    Two key considerations when designing a free cooling system · Expected thermal load · Expected demand and demand fluctuations · Energy efficiency goals ...Missing: HVAC | Show results with:HVAC
  50. [50]
    What is Indirect Free Cooling and what are the differences with ...
    Obviously, the investment costs for a direct free cooling system will also be much lower than for an indirect one.Missing: efficiency | Show results with:efficiency
  51. [51]
    Combining direct and indirect free cooling for data centers via ...
    Aug 15, 2025 · To address these limitations, indirect free cooling involves first transferring heat from the racks to a primary coolant, which is then ...Missing: HVAC | Show results with:HVAC
  52. [52]
    Hybrid cooling systems - Condair
    The system's advanced controls continuously monitor ambient conditions such as temperature, humidity, and air pressure to make real-time decisions. This ...
  53. [53]
    Comparative energy analysis of cooling energy performance ...
    In this study, the performance of an air source hybrid cooling system under dynamic operating conditions is investigated. Using a simulation model created ...
  54. [54]
    DX free cooling | HYSAVE Net
    Feb 13, 2024 · DX free cooling uses lower outdoor temperatures to minimize mechanical refrigeration by transferring heat outside, bypassing the vapor ...Missing: hybrid absorption dynamic controls
  55. [55]
    Hybrid CHW & DX Cooling Systems Part 1 - YouTube
    Sep 10, 2020 · Air Change Precise Control Units can incorporate chilled water coils alongside DX refrigeration systems to form a hybrid cooling system.Missing: absorption dynamic
  56. [56]
    Free cooling in data centers: More cost efficiency through dynamic ...
    The payback period for such a free cooling system was around two to three years. However, development has not stopped here.Missing: hybrid real-
  57. [57]
    Energy Performance Study of a Data Center Combined Cooling ...
    Depending on the working fluids used in the cooling cycle, the system's payback period varies between 2.04 and 2.46 years. Thirdly, for data centers, the ...
  58. [58]
    Determining the Outdoor Air Intake Dry-Bulb Temperature Range for ...
    The study found that a 14°C outdoor air intake dry-bulb temperature threshold provided the most favorable balance between energy efficiency and environmental ...
  59. [59]
    [PDF] Best Practices Guide for Energy-Efficient Data Center Design
    Free cooling is usually best suited for climates that have wet bulb temperatures lower than 55°F for 3,000 or more hours per year. It most effectively ...
  60. [60]
    Top 10 sustainable locations for data centres
    Jul 26, 2023 · Data Centre Magazine rounds up the top 10 sustainable data centre locations from around the world.
  61. [61]
    [PDF] Is Data Center Free Cooling Feasible in the Middle East?
    The ambient dry-bulb temperature will have to be calculated for dry operations instead of the wet-bulb temperature during wet operations. Figure 3 shows the ...Missing: viability thresholds
  62. [62]
    Analysis of energy saving potential of air-side free cooling for data ...
    The results showed that significant free cooling potential was achieved in data centers located in mixed-humid, warm-marine, and mixed-marine climate zones.Missing: thresholds | Show results with:thresholds
  63. [63]
    How Climate Change Affects Data Centers
    Aug 25, 2022 · “Climate change is having an impact on data centers broadly in the sense that it is limiting the potential for providing free cooling ...
  64. [64]
    How will extreme weather conditions influence cooling operations?
    Jul 28, 2023 · When temperatures reach 40C, the amount of energy required to cool a data centre increases as the ambient temperature goes up. This poses a ...
  65. [65]
    Energy performance evaluation in a data center with water-side free ...
    Sep 15, 2023 · In full-free cooling mode, a reduction in cooling energy consumption of 8322 kWh could be achieved. However, the decrease in PUE was only about ...
  66. [66]
    [PDF] Enhancing Cooling Energy Reduction in Data Centers throu
    As a result, the free cooling operation rate was increased by 39.7 percentage points during intermediate and winter seasons, achieving reductions of 34% in ...
  67. [67]
    Can Frequent Heat and Cooling Switches Damage Your HVAC?
    Generally, switching to and from your heating and cooling settings will not cause any issues. Nonetheless, often changing back and forth can cause your system ...
  68. [68]
    Is It Bad to Switch Between Heat and AC in the Fall? - Platinum HVAC
    Sep 12, 2025 · 1. Increased Wear and Tear on Your HVAC System ... Switching between heat and AC too often can cause undue strain on your system. HVAC systems are ...
  69. [69]
    Free Cooling for Data Centers: Strategies and Advantages
    Dec 9, 2024 · In data centers, free cooling is the practice of dissipating heat without artificially cooling air or water. Typically, free cooling systems ...Missing: definition engineering
  70. [70]
    Why Data Centers Sweat: Dew Point Management and Its Role in ...
    Apr 6, 2025 · Facilities relying on economizers or free cooling must include dew point logic to avoid disaster.
  71. [71]
    Data Center Humidity Control Via Advanced Sensor Technology
    Oct 21, 2024 · For data centers, knowing the dew point is critical for avoiding condensation on servers and sensitive equipment. High data center air ...
  72. [72]
    Feasibility investigation on a novel data center cooling system ...
    Sep 20, 2024 · A novel data center cooling system based on cross-seasonal soil cold storage is proposed,which makes full use of the cold stored in the soil across the seasons ...
  73. [73]
    Optimizing PUE to Enhance Data Center Efficiency - AKCP
    Dec 19, 2024 · Free Cooling: Leveraging free cooling in colder regions can reduce reliance on energy-hungry cooling systems and contribute to substantial ...Missing: empirical | Show results with:empirical
  74. [74]
    Free Cooling & Beyond – Data Center Efficiency at the Edge
    Aug 17, 2016 · Traditional air-side free cooling is effective in some edge locations, but in many locations – where it gets too hot and/or too humid – free ...Missing: urban | Show results with:urban
  75. [75]
    Radiative free cooling for energy and water saving in data centers
    Apr 1, 2024 · In the meantime, the average PUE of data centers decreased by 25% [13], implying the portion of energy used for cooling decreased substantially.
  76. [76]
    [PDF] The hidden cost of free cooling and what you can do | ABB
    Hidden costs of free cooling include increased fan motor power, as fan motor power draw increases with the cube of fan RPMs, and leakage power in computing ...
  77. [77]
    Have filters in Data Centers become surplus to requirements?
    Feb 26, 2024 · Our calculations suggest a possible 14% increase in energy expenditure when comparing a like-for-like set up of cooling equipment inside a data center.
  78. [78]
    Free Cooling: Is It Costing Data Centers Their Equipment Reliability?
    ### Summary of Real-World Issues with Free Cooling in Data Centers
  79. [79]
    What You Need to Know About Air Quality in Data Centers
    Jul 15, 2018 · Data centers face contaminants like particulate matter, humidity, and ozone, which can cause equipment failure, increase cooling costs, and ...Missing: pollutants | Show results with:pollutants
  80. [80]
    A Practical Guide to Sustainable Cooling Practices for Data Centers
    Proper cooling water treatment can effectively help data centers support sustainability initiatives by reducing water and electrical use.
  81. [81]
    [PDF] Free Cooling - EVAPCO
    Apr 16, 2010 · COOLING TOWER BYPASS DURING FREE COOLING OPERATION! Reduced flow over the tower can result in uneven water flow over the heat transfer media ...
  82. [82]
    Improve Chiller Efficiency - The Engineering Mindset
    May 3, 2018 · Using a free cooling cycle could reduce the chillers annual energy consumption by 20-50% again this really depends on the local ambient ...
  83. [83]
    Free cooling – the cheapest and greenest way to provide cooling
    Feb 28, 2023 · Three air cooled chillers and a 360kW free cooler system resulting in 42% annual energy savings for a chemical manufacturer. —–. NEW CHILLER AND ...
  84. [84]
    [PDF] Free Cooling: At What Cost? - ACEEE
    Free cooling can provide 20-30% savings, but failures and incorrect setpoints can cause 30-40% of economizers to not provide savings.Missing: office | Show results with:office
  85. [85]
    Free Cooling in Buildings: Opportunities to Drive Significant Savings ...
    Figure 5 shows how an integrated free cooling chiller can offer energy savings for an office building application when applied in moderate and cold climates.
  86. [86]
    [PDF] Minimizing Energy Costs with Free Cooling
    The cooling tower and heat exchanger begin to shave the load at a predetermined wet-bulb temperature by handling a portion of the chilled water load. As the wet ...<|separator|>
  87. [87]
    [PDF] Energy Efficiency in Industrial Process Cooling Systems - ACEEE
    This case study examines process cooling systems at a Utah manufacturing facility making large blow molded plastic products. The study was performed as part of ...
  88. [88]
    5 Data Center Energy Efficiency Best Practices That Cut Costs
    Aug 15, 2025 · Most cooling efficiency improvements pay for themselves within 18-36 months through reduced energy costs. Hot/cold aisle containment often ...
  89. [89]
    Optimizing Cooling Efficiency in Modern Data Centers
    Sep 8, 2025 · Cooling systems in data centers account for roughly 30% to 40% of total energy consumption. As rack densities grow and sustainability targets ...Missing: 2020s | Show results with:2020s
  90. [90]
    The Energy-Saving Potential of Air-Side Economisers in Modular ...
    This study examines the feasibility of utilising outside air for 'free cooling' in modular data centres through the implementation of an air-side economiser.<|separator|>
  91. [91]
    Data Center Energy Efficiency: Which Metrics Matter Most? - AIRSYS
    Jul 3, 2025 · Replacing mechanical chillers with cooling towers for chilled water supply can cut cooling costs by as much as 70%. ... free cooling, their CUE ...
  92. [92]
    Gesis Project - Energy-Efficient Cooling - Stulz
    Explore how STULZ's cooling solutions saved 100000 kWh per year in a 75 m² data center at Gesis.
  93. [93]
    (PDF) Technoeconomic Evaluation of Cell Site Power Consumption ...
    May 19, 2024 · Site Power Consumption Reduction Using Free Cooling Technique. ESI Preprints. ... and 24% for FC in 2021, and 61% for AC and 39% for FC in 2022.
  94. [94]
    [PDF] A Method for Estimating Potential Energy and Cost Savings for ...
    The best savings are usually in cool or dry climates where “free” economizer or evaporative cooling can provide most of the cooling; locations with a high cost ...Missing: regions | Show results with:regions
  95. [95]
    Can data centers lower Alaska's high energy costs? | From the Grid
    Mar 25, 2025 · Utilizing the ambient cooling and cold water will reduce energy consumption ... A key advantage for Alaska could be the free cooling Arctic sites ...
  96. [96]
    Customized data center cooling system operating at significant ...
    Jan 15, 2022 · The freecooling mode is more energy-efficient compared to the compressor mode. •. In freecooling mode, a single chiller works more effectively ...
  97. [97]
    Free Cooling vs Mechanical Cooling: Why Chillers Make the ... - Lneya
    Extended Equipment Life – Fewer compressor run hours mean less wear. • Consistent Product Quality – Seamless switching keeps process temperatures stable. • ...Missing: drawbacks frequent
  98. [98]
    Free cooling, what it is and when the ROI is advantageous
    Jul 5, 2024 · A free cooling system in process cooling using refrigeration units allows significant energy savings if the system is located in a country ...
  99. [99]
    Water Side Economizers Part 8: The Heat Exchanger Approach
    Jul 10, 2023 · The heat exchanger approach is the temperature difference between the cold cooling tower supply water and the heat exchanger chilled water outlet temperature.Missing: losses | Show results with:losses
  100. [100]
    [PDF] Waterside Economizers - Keeping the Free in Free-Cooling - Trane
    Condenser bypass is the preferred method for waterside economizer mode, as it allows the tower flow rate to remain high, which provides adequate fill coverage ...<|separator|>
  101. [101]
    [PDF] Is Free Cooling Right for My Application? | Daikin Applied
    Dec 15, 2020 · In this mode, all the cooling of the glycol is achieved through the use of the coils and the compressors are turned off.Missing: disadvantages | Show results with:disadvantages
  102. [102]
    Design requirements for condensation-free operation of high ...
    HTC system's cooling capacity is limited by risk of condensation in humid climates. •. Low temperature lift required by the HTC system permits the use of ...
  103. [103]
    [PDF] Humidity Control in Data Centers.03242017_0.pdf
    Mar 24, 2017 · First, the cooling coil surface temperature should be higher than the room dew point. This ensures that no moisture is removed from the data ...
  104. [104]
    [PDF] Moisture Control Guidance for Building Design, Construction ... - EPA
    During the cooling season, humidity loads from outdoor air are far larger ... dehumidification loads and determining component performance, it is very ...
  105. [105]
    Why Free Cooling in Data Centers Is Harder Than It Sounds — And ...
    Free cooling sounds easy, until you try it. Real world execution requires careful coordination between environmental inputs and system behavior. DCIM ...
  106. [106]
    Correlation between the local climate and the free-cooling potential ...
    Aug 5, 2025 · In this article, studies of the free-cooling potential for different climatic locations are presented. Six cities from around Europe with a wide ...
  107. [107]
    HVAC Predictive Maintenance: Slash Energy Costs - LLumin
    Jul 28, 2025 · If your HVAC system is just 15% less efficient than it should be and that's common when filters clog, coils dirty, or sensors drift out of spec, ...
  108. [108]
  109. [109]
    AI & Automation: The Next Frontier in Cooling Efficiency - Airedale
    Jun 12, 2025 · AI algorithms can use real-time sensor data combined with historical operating patterns to predict and dynamically optimize cooling in data ...<|separator|>
  110. [110]
    AI-Powered Efficiency: Optimizing Data Center Cooling Systems
    Mar 22, 2024 · Dynamic Cooling Control: Based on factors like workload, temperature variations and airflow patterns, AI driven control systems can adjust the ...
  111. [111]
    AI-driven optimization of fan-wall cooling system in a medium ...
    This study introduces an optimization framework for fan-wall cooling systems in medium-density data centers, combining a genetic algorithm (GA) with a surrogate ...
  112. [112]
    How Hybrid Cooling Is Future-Proofing Data Centers For AI
    May 13, 2025 · A hybrid data center will utilize direct-to-chip liquid cooling along with some form of traditional air cooling to keep facilities running.
  113. [113]
    Dynamic cooling solutions: How hybrid systems meet AI's ever ...
    Jul 1, 2025 · High-density AI workloads are pushing data centers toward adaptive hybrid cooling to address thermal management demands.
  114. [114]
    Data Center Cooling Trends for 2025 - Upsite Technologies
    May 29, 2025 · Shumate Engineering has designed a Hybrid Abiatic Fluid Cooler that uses half the energy and 97% less water than traditional AI data centers ...
  115. [115]
    Free Cooling - Kaltra
    Kaltra offers a comprehensive range of free cooling chillers with different types of compressors and optimized for various applications.
  116. [116]
    Brazed plate heat exchangers for free cooling - SWEP
    High thermal efficiency and a tight temperature approach make SWEP BPHEs the ideal loop-breaker to separate the external brine circuit from the inside water ...
  117. [117]
    [PDF] Psychrometric Bin Analysis for Alternative Cooling Strategies in Data ...
    Psychrometric bin analysis uses ASHRAE envelopes to divide a chart into bins, categorizing cooling strategies based on technology combinations.
  118. [118]
    NREL Joins $40 Million Effort To Advance Data Center Cooling ...
    Jan 9, 2025 · The group will develop standardized testing to evaluate the cooling technologies developed by COOLERCHIPS projects in real data center operating ...
  119. [119]
    Radiative free cooling for energy and water saving in data centers
    All-day passive radiative cooling is a free cooling technique, in which sky-facing surfaces with high solar reflectivity and midinfrared emissivity ...
  120. [120]
    Radiative cooling applications toward enhanced energy efficiency
    Jun 16, 2025 · Radiative cooling applications include cooling, energy harvesting, and resource collection, such as building cooling, personal thermal ...
  121. [121]
    Radiative cooling drives the integration and application of thermal ...
    Oct 10, 2025 · Radiative cooling modulates temperature through radiative heat exchange between object surfaces and the cold universe. Its physical mechanism ...
  122. [122]
    Free Cooling System Market Size, SWOT, Market Trends ...
    Rating 4.4 (65) Free Cooling System Market size is estimated to be USD 1.5 Billion in 2024 and is expected to reach USD 3.2 Billion by 2033 at a CAGR of 9.2% from 2026 to 2033.
  123. [123]
    Data Center Cooling Global Strategic Industry Report 2023-2030
    Aug 27, 2024 · The global market for Data Center Cooling was estimated at US$16.9 Billion in 2023 and is projected to reach US$51.3 Billion by 2030, growing at ...
  124. [124]
    Data Center Cooling Market - A Global and Regional Analysis
    Rating 4.6 (38) The data center cooling market is projected to reach $100.12 billion by 2035 from $25.77 billion in 2024, growing at a CAGR of 12.55% during the forecast period ...
  125. [125]
    Data Center Cooling Market, Industry Size Forecast [Latest]
    Jul 21, 2025 · The global data center cooling market is projected to grow from USD 11.08 billion in 2025 to USD 24.19 billion by 2032, at 11.8% cagr from 2025 ...
  126. [126]
    Data Center Cooling Market Size, Share | Forecast Report [2032]
    Oct 16, 2025 · The global data center cooling market size was valued at $16.84 billion in 2024 & is projected to grow from $18.78 billion in 2025 to $42.48 ...<|separator|>
  127. [127]
    Data Center Liquid Cooling Market | Industry Report, 2030
    The data center liquid cooling market in the U.S. is expected to grow at a significantly CAGR of 21.6% over the forecast period. By component, the solution ...