Plenum space

A plenum space is a dedicated compartment or chamber within a building's structure that forms part of an air circulation system for (HVAC), excluding the occupied areas being conditioned. It typically consists of enclosed areas, such as the void above a suspended or below a , where air is supplied, returned, exhausted, or ventilated through connected ducts. These spaces are engineered to facilitate efficient airflow distribution while maintaining separation from habitable zones to ensure safety and system performance. In and , spaces play a critical role in modern commercial and institutional facilities, such as offices, schools, and hospitals, where they support centralized HVAC operations by channeling conditioned air throughout the structure. Unlike general cavities, plenums are explicitly integrated into the air distribution network, often featuring materials like metal or ducts to handle pressurized or environmental airflows. Their must comply with stringent building codes to prevent contamination of the and to mitigate risks during emergencies, emphasizing fire-resistant and low-smoke materials. Safety considerations are paramount in plenum spaces due to their proximity to air pathways, which could propagate , , or toxins into occupied areas if compromised. Installations within plenums, including , cabling, and equipment, require specialized plenum-rated components that undergo rigorous testing for flame propagation and smoke density, as outlined in standards like UL 2043 and NFPA 262. This is distinct from air-handling spaces, which refer to broader environmental air management areas (e.g., over hung ceilings) not directly tied to ducted systems, allowing for slightly less restrictive but still regulated installations per the (NEC) Article 300.22(C). Overall, proper space management enhances , , and occupant protection in compliance with international mechanical and codes.

Definition and Purpose

Definition

A plenum space is an enclosed portion of a building , other than an occupiable being conditioned, that is designed to allow air movement and that serves as part of an environmental air-conditioning system, typically located above suspended ceilings, below raised floors, or within vertical shafts to facilitate the circulation of air in (HVAC) systems. These spaces are integral to HVAC operations by providing pathways for supply or return air distribution. The term "plenum" derives from the Latin plenum, meaning "full," originally referring to a space filled with matter, such as air, in philosophical and scientific contexts before its adoption in architecture to describe areas occupied by moving air. Key characteristics of plenum spaces include their separation from occupied areas to minimize the risk of contaminants entering living or working environments, often achieved through barriers like fire-rated ceilings or floors. They are frequently pressurized for supply air distribution or utilized as return air paths to collect exhausted air. Unlike a duct, which is a specific conduit or tube for directed airflow conveyance, a plenum functions as a larger chamber or compartment where air can mix and distribute more diffusely before entering or exiting connected ducts.

Primary Purposes

Plenum spaces serve as critical components in by facilitating efficient air circulation within (HVAC) systems. They enable the even distribution of conditioned air from supply ducts to occupied areas while separating return air paths, which minimizes energy loss through leaks and enhances overall system efficiency. This separation allows for optimized airflow dynamics, reducing the workload on HVAC equipment and contributing to lower operational costs. Additionally, by maintaining consistent air delivery, plenum spaces improve through better and reduced recirculation of stale air in habitable zones. Another key function of spaces is , acting as a that potential pollutants from HVAC components, building materials, or maintenance activities away from occupied environments. This prevents the spread of airborne contaminants, such as , spores, or chemical residues, into living or working areas, thereby safeguarding occupant and complying with air quality standards. In designs where plenums house mechanical elements, their enclosed nature helps contain any emissions or particulates, reducing the risk of indoor . Plenum spaces also optimize space utilization in commercial and institutional buildings by providing concealed pathways for , allowing for more flexible and aesthetically pleasing floor plans without visible . This hidden integration frees up valuable in occupied areas, supporting efficient layouts in offices, hospitals, and schools where space is at a premium. By embedding utilities within these voids, buildings achieve higher functional density without compromising the integrity of habitable zones. In certain building designs, spaces contribute to pressure equalization by mixing and balancing airflows, which helps maintain uniform differentials to prevent the infiltration of unconditioned or outdoor air into the . This equalization mitigates drafts, enhances , and supports the overall stability of the HVAC system by avoiding imbalances that could lead to inefficiencies or equipment strain. Such functionality is particularly valuable in multi-story structures where maintaining balanced pressurization across floors is essential.

Types of Plenum Spaces

Ceiling Plenums

Ceiling plenums are the enclosed spaces formed between a suspended grid and the structural or slab above, typically measuring 12 to 36 inches (30 to 91 cm) in height to accommodate necessary while maintaining building efficiency. These areas are accessed through removable tiles or panels, allowing for non-invasive entry without disrupting the occupied space below. This has been a standard feature in commercial and institutional buildings since the mid-20th century, particularly following the widespread adoption of suspended acoustic ceilings in the to enhance sound control and hide mechanical systems. In terms of dynamics, plenums primarily serve as air pathways for heating, , and air-conditioning (HVAC) systems, leveraging the natural rise of warm air from occupied spaces to facilitate recirculation and maintain . They often integrate supply air diffusers that mix conditioned air into the plenum before distribution, promoting uniform and reducing drafts in environments like offices and hospitals. This setup contrasts with ducted returns by utilizing the plenum's volume for passive , though it requires careful sealing to prevent contaminants from entering the . Ceiling plenums also integrate horizontal runs of various utilities, including HVAC ducts, electrical conduits, low-voltage cabling for data and communications, lines, and systems, creating a centralized corridor for building services. These spaces support the distribution of , , and without penetrating the aesthetic ceiling surface excessively. The primary advantages of ceiling plenums lie in their ability to conceal building infrastructure while providing straightforward access for inspections, repairs, and upgrades, minimizing downtime in high-use facilities such as hospitals and office buildings. This design enhances both functionality and aesthetics, contributing to through optimized HVAC paths, though it necessitates compliance with measures like sealing to contain potential hazards.

Floor Plenums

Floor plenums are dedicated air-handling chambers formed beneath raised flooring systems, typically consisting of pedestal-supported slabs elevated 12 to 24 inches above the subfloor. These structures are prevalent in computer rooms and cleanrooms, where the elevated design creates a concealed void for integrated building services while maintaining a level walking surface. The primary function of floor plenums involves optimized airflow dynamics through underfloor supply air distribution, where conditioned cool air is pressurized into the plenum and directed upward via strategically placed perforated tiles. This setup delivers air directly to workstations or high-heat equipment, such as server racks, minimizing mixing with warmer room air and enhancing precise environmental control. In addition to airflow, floor plenums facilitate utility integration by accommodating dense bundles of power and data cabling routed beneath the floor, reducing surface clutter and enabling scalable infrastructure. Modular access panels, typically 24-inch square tiles, allow for straightforward removal and reconfiguration without disrupting operations. These plenums offer significant advantages in cooling efficiency, particularly for environments with high thermal loads from servers, by enabling targeted air delivery that lowers energy consumption compared to overhead systems. This approach originated in the 1960s with mainframe computing facilities, where raised floors were first engineered to manage cabling and airflow for early large-scale computers.

Riser Shafts

Vertical risers are enclosures within multi-story , typically integrated into stairwells, shafts, or dedicated utility shafts that span multiple floors, often constructed with fire-rated walls to compartmentalize potential . These structures serve as centralized pathways for the vertical of air and utilities, distinguishing them from horizontal types by their multi-floor extent and role in bridging building levels. Vertical risers may function as air shafts in HVAC systems, but unlike horizontal plenums, they typically use enclosed ducts to prevent and , per standards like NFPA 90A. In HVAC systems, vertical risers facilitate airflow between floors, enabling conditioned air to rise or descend through dedicated shafts while connecting to horizontal ceiling or floor plenums for distribution across zones. This design supports whole-building HVAC zoning by allowing takeoffs from a central vertical shaft to individual floor mechanical rooms, promoting efficient air movement and pressure balancing, as seen in retrofitted 1980s high-rise offices where outdoor air fans supply shafts with capacities up to 31,400 cfm per building. To preserve air integrity, penetrations for utilities must be sealed with fire-stopping materials, preventing unintended leakage or contamination of the airflow path. Vertical risers integrate stacks of utilities, including HVAC ducts, electrical conduits, plumbing pipes, and data cables, within the same enclosed space to streamline service delivery. Sealed penetrations at floor levels ensure that these utilities do not compromise the shaft's airtightness, maintaining both airflow efficiency and fire resistance. This integration is critical in high-rises, where central risers reduce installation complexity by halving thermal expansion movements in segmented sections, such as 250-foot runs. The advantages of vertical risers lie in their ability to centralize vertical distribution, minimizing clutter from scattered utility runs and enhancing overall building efficiency, a necessity evident since the early when like the 1906 Larkin Building employed vertical service ducts adjacent to staircases for . By consolidating air and utility transport in fire-rated enclosures, they support scalable designs in tall structures, reducing operational pressures on systems like water risers that face approximately 217 hydrostatic loads over 500 feet. Essential to modern high-rises, this approach originated with the advent of steel-frame construction over a century ago, evolving to incorporate innovations by the 1930s in buildings like the PSFS tower.

Applications in Building Systems

HVAC Systems

Plenum spaces serve as critical components in HVAC systems, facilitating the integration of air handlers, fans, and dampers to manage distribution. These spaces connect directly to air handlers, where fans draw in and propel air through the system, while dampers regulate the volume and direction of from supply and return paths. In particular, s function as mixing chambers that blend conditioned supply air with air from occupied spaces, ensuring uniform and levels throughout the building. This mixing process helps prevent short-circuiting, where unconditioned air bypasses the intended zones, thereby maintaining system efficiency and occupant comfort. Design considerations for plenum spaces in HVAC applications emphasize sizing based on required rates, typically measured in cubic feet per minute (CFM). Volume calculations derive from the formula (CFM) = (feet per minute) × cross-sectional area (square feet), ensuring the accommodates the system's total air without excessive loss or . For instance, extended systems are limited to approximately 24 feet in length to avoid uneven distribution, with adjustments made for branch takeoffs to sustain . Filters are commonly installed at entry points to , such as within air handlers or at return grilles, to capture and maintain air quality; these are sized for velocities not exceeding 150 feet per minute to minimize resistance. , often used as return air paths, exemplify this integration by channeling air back to the mixing chamber efficiently. The use of plenum spaces enhances HVAC efficiency by utilizing existing building voids as distribution pathways, thereby reducing the need for extensive dedicated ductwork. This approach can lower installation costs in large commercial buildings through minimized material and labor requirements for duct fabrication and routing. By shortening air paths and decreasing thermal losses, plenums contribute to overall energy savings, particularly in systems where conditioned air is maintained within the plenum environment. Historically, spaces became a standard feature in HVAC designs for commercial architecture following the widespread adoption of centralized systems in the post-1950s era. This shift was driven by post-World War II construction booms and evolving regulatory standards to improve occupant comfort and .

Electrical and Data Cabling

spaces serve as accessible pathways for routing electrical and data cabling in commercial buildings, particularly for low-voltage systems such as Ethernet and optic cables. These areas facilitate both from telecommunications rooms to workstations and vertical risers connecting multiple floors, often eliminating the need for additional conduits due to the open nature of the space. This approach is mandated by building codes to ensure that only plenum-rated cables, identified by the CMP (Communications Multipurpose ) designation, are used to maintain in air-handling environments. Safety considerations in plenum cabling installations prioritize preventing hazards associated with heat buildup and signal . The natural within spaces helps dissipate heat from bundled cables, reducing the risk of overheating that could occur in confined areas. Additionally, cables are typically separated from high-voltage lines by at least 12 inches to minimize (), which is more readily achievable in the expansive environment compared to wall cavities. -rated cables must meet stringent safety ratings, such as those specified in UL 910 for low flame spread and smoke production, to prevent rapid in oxygen-rich air-handling areas. Structured cabling practices in plenum spaces adhere to the ANSI/TIA-568 standards, which outline requirements for commercial telecommunications infrastructure, including performance parameters for horizontal and backbone cabling in air-handling areas. These standards ensure reliable data transmission while specifying compatible components like twisted-pair and optical fiber cables suitable for plenum use. The National Electrical Code (NEC) Article 800 further reinforces these by prohibiting non-plenum cables in such spaces unless installed in approved conduits. One key benefit of utilizing spaces for cabling is the simplification of retrofits in existing buildings, as the overhead or underfloor access allows for straightforward additions or modifications without extensive structural alterations. This method also supports higher cable density than traditional wall or conduit-based installations, accommodating greater volumes of wiring to meet evolving network demands while reducing material and labor costs associated with conduit requirements.

Plumbing and Other Utilities

Plenum spaces occasionally accommodate plumbing systems, including drain, waste, and vent (DWV) pipes as well as condensate drain lines from HVAC equipment, though such installations are subject to stringent material requirements to mitigate fire risks. These pipes must be constructed from noncombustible materials, such as cast iron, to comply with building codes that prohibit combustible plastics like PVC in air-handling spaces unless they meet specific low flame-spread criteria. For instance, condensate lines, which carry moisture from cooling coils, are routed through plenums to connect to building drainage but require materials that prevent contribution to fire propagation. Other utilities integrated into plenum spaces include fire sprinkler mains and, less commonly, gas lines, alongside penetrations for lighting fixtures. Fire sprinkler piping, typically steel for durability, is permitted in plenums provided it adheres to standards for exposure in air-handling areas; plastic variants are restricted to wet-pipe systems with verified low smoke and flame characteristics. Gas lines are rarely installed in plenums due to prohibitions against routing them through ventilating ducts or air-handling spaces, as outlined in fuel gas codes, to avoid explosion hazards in the event of leaks. Lighting fixtures that penetrate plenum ceilings must be sealed to maintain air integrity and use noncombustible enclosures where exposed. Design constraints for these utilities emphasize against environmental and structural threats. carrying or are insulated with materials exhibiting a flame spread index of 25 or less and of 50 or less to prevent from dripping into paths, which could foster microbial or . In seismic-prone regions, risers and sprinkler mains require bracing per standards like NFPA 13, using sway braces and flexible connections to accommodate building movement without rupture. The use of in plenum spaces is limited compared to HVAC or electrical systems primarily due to moisture contamination risks, where leaks could introduce or pathogens into circulated air, compromising . As of the International Mechanical Code 2024 edition (effective in many jurisdictions by 2025), restrictions on plastic piping in mandate rigorous testing for and often favor metallic alternatives to reduce emission during fires.

Data Centers and High-Density Applications

In modern s, plenum spaces are extensively used for underfloor and overhead configurations to support high-density server cooling and cabling. Raised floor plenums distribute conditioned air directly to equipment s, improving in environments with loads exceeding 20 kW per rack, while overhead plenums route fiber optic and power cabling to minimize and support scalable networking. These applications comply with standards like 90.4 for data center , emphasizing sealed plenums to prevent air leakage and optimize for hotspot mitigation.

Design and Construction

Materials and Specifications

Plenum spaces require durable, noncombustible structural materials to form enclosures that support air circulation and utility routing while minimizing risks. Walls are commonly constructed using board partitions, which are suitable for temperatures not exceeding 125°F (°C), or metal partitions for higher thermal demands and enhanced . Acoustic tiles, typically composed of mineral fiber, , , or metal with fire-rated backings, serve as the primary boundary for ceiling plenums, providing both acoustic and resistance. Non-porous surfaces, such as those found in certain metal or elastomeric insulations, are prioritized to resist growth by preventing in potentially humid conditions. Utility materials within plenum spaces must prioritize low flammability and minimal smoke production to protect air quality. Plenum-rated insulations, such as fiberglass variants designed for pipes and ducts, feature low smoke emission with a smoke-developed index of 50 or less, ensuring compliance in air-handling environments. For air paths, metallic ducts are favored over plastic alternatives due to their superior fire resistance, structural durability, and reduced risk of toxic fume release during combustion. Performance specifications for plenum materials emphasize resilience to operational stresses and environmental factors. These materials must endure positive and negative pressures ranging from 0.05 to 0.1 inches water gauge (12 to 25 ), common in low-velocity air distribution systems like underfloor s. Vapor barriers, often integrated into facings, help control levels and mitigate risks within the space. Testing standards ensure material integrity, with UL 181 serving as the primary benchmark for air leakage in ducts and plenums, evaluating durability under cyclic pressures and temperatures. These requirements became widespread following the energy conservation codes, which emphasized efficient and safe air-handling systems. Such testing aligns with broader needs, where materials achieve a flame-spread index of 25 or less.

Installation Considerations

Installing spaces requires meticulous preparation to ensure structural integrity and air handling efficiency. During or , the for ceilings or floors must be leveled to prevent uneven air distribution and potential sagging of components. Gaps at perimeters, such as those around walls or structural elements, should be sealed using approved materials like or mastic to maintain air integrity and prevent leakage, which can compromise HVAC performance. Prior to full assembly, the should be inspected for deficiencies, including or contaminants, to avoid issues during . Utility routing in spaces demands close coordination among HVAC, electrical, , and other trades to minimize conflicts and ensure compliance with building codes. Penetrations for ducts, conduits, pipes, and cables must be planned in advance, with all openings sealed using putty, , or tape to preserve plenum pressure and prevent air or contaminant migration. For instance, in underfloor plenums, seals at expansion joints, shafts, and perimeter walls are critical to limit leakage to specified thresholds, such as 0.05 cfm/ft² for high-performance systems. This interdisciplinary collaboration, often involving architects and engineers, helps integrate systems without compromising the space's functionality. Accessibility features are essential for safe and efficient and future . panels and hatches should be incorporated into the , featuring gasketing and latches to reduce air infiltration while allowing entry for inspections. During , temporary measures, such as fans or exhaust systems, are recommended to remove and , ensuring the remains clean before sealing. In open configurations, planned pathways facilitate technician access to equipment, enhancing overall build quality. Cost factors for plenum installation include upfront expenses for specialized sealing and coordination, which can range from $5 to $8 per for raised access floor systems before finishes. However, these are often offset by long-term savings, such as reduced ductwork needs and gains; for example, compact designs can yield annual reductions of around $116 through shorter duct runs and smaller equipment. In retrofit projects, a phased approach—installing sections sequentially—helps minimize occupant disruption while maintaining building operations.

Fire Safety and Regulations

Building Codes and Standards

Plenum spaces are regulated under the International Mechanical Code (IMC), which is integrated into the International Building Code (IBC) framework, defining a as an enclosed portion of the building structure, other than an occupiable space being conditioned, designed to allow air movement and serve as part of an air-conditioning or ventilating system. This definition emphasizes the role of plenums in air-handling, with requirements for construction that limits fire propagation, including the use of noncombustible materials where exposed to . In mixed-occupancy buildings, plenums must incorporate fire barriers to separate sprinklered areas from non-sprinklered ones, typically requiring a minimum one-hour to prevent smoke and fire spread. The NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, establishes requirements for construction in and institutional buildings, mandating dampers, detectors, and restrictions to control and within HVAC systems. As of November 2025, the 2024 edition of NFPA 90A is current, providing provisions for management through integration of detection and control systems to mitigate hazards in spaces. These standards apply broadly to buildings with centralized air-handling systems, ensuring plenums do not facilitate rapid fire extension. Adoption of the IBC and IMC varies by jurisdiction, with most U.S. states incorporating them as base codes with local amendments; for instance, as of 2025, amends them through Title 24 (2022 edition, effective until January 1, 2026), adding mandates that influence design and airflow optimization. In the , the equivalent framework is provided by EN 16798-3:2017, which sets performance requirements for and room-conditioning systems in non-residential buildings, addressing functionality for air distribution and . Compliance involves submission of detailed plans for review by Authorities Having Jurisdiction (AHJs), such as local building officials, who verify adherence to these codes before permitting construction. The evolution of plenum regulations traces back to the , spurred by major incidents that prompted stricter measures for air-handling spaces in subsequent code cycles.

Flame Spread and Smoke Development Ratings

The ASTM E84 test method, commonly referred to as the Steiner test, evaluates the surface burning characteristics of materials intended for use in spaces by measuring the flame spread index (FSI) and (SDI). This standardized procedure exposes a sample to a controlled in a 25-foot tunnel apparatus, simulating exposure on building interiors, with FSI values ranging from 0 (noncombustible reference like ) to 200 (highly combustible like red oak flooring at 100), and SDI quantifying smoke density relative to the same benchmarks. For plenum applications, materials must typically achieve an FSI of 25 or less and an SDI of 50 or less, corresponding to a stringent 25/50 rating under NFPA 90A to ensure limited contribution to growth in air-handling environments. Plenum space requirements mandate that exposed materials be noncombustible or limited-combustible, with low FSI and SDI values to comply with standards; for instance, ducts exhibit an FSI of 0 due to their noncombustible nature. Materials like PVC are generally prohibited in plenums unless specifically tested and rated to meet the 25/50 criteria, as unrated PVC fails to limit flame propagation and smoke release. These ratings are critical in plenum spaces, where high oxygen levels from air circulation can accelerate , making low FSI and SDI essential for containing spread and reducing obscuration that could hinder evacuation or efforts. Exceptions permit limited use of combustible materials, such as certain electrical cables or tubing, provided they are listed for installation and meet NFPA 90A definitions for limited-combustible , ensuring overall risk remains controlled.

Maintenance and Inspection

Routine Procedures

Routine procedures for spaces in building HVAC systems emphasize preventive measures to maintain air quality, structural integrity, and efficient , preventing the accumulation of contaminants that could compromise indoor environments. These tasks are typically performed by qualified HVAC technicians and follow established industry standards to ensure compliance with requirements. Access to plenum areas is gained through designated panels or hatches, minimizing disruption to occupied spaces. Cleaning protocols form a core component of maintenance, focusing on and removal to mitigate risks of microbial and reduced . Vacuuming using high-efficiency particulate air ()-filtered equipment is recommended, with technicians accessing the plenum via panels to extract accumulated from surfaces and air paths without dispersing particles. This process incorporates contact vacuuming or negative air machines to capture fine , complemented by filtration systems in adjacent air handling units to inhibit microbial growth in pathways. For open plenums, may be used sparingly to dislodge stubborn residues, followed by thorough vacuuming to avoid re-entrainment of contaminants. Frequency should be determined by environmental factors and contamination assessments. Inspection schedules ensure early detection of potential issues, preserving the plenum's role in safe air distribution. Regular visual inspections are standard, involving checks for signs of water leaks, corrosion on metal components, and pest infestations that could introduce allergens or damage insulation. In hard-to-reach areas, borescopes or endoscopic cameras are employed to visually assess internal conditions, such as insulation integrity and foreign object accumulation, without full disassembly. These inspections align with broader fire safety regulations by verifying no combustible materials have accumulated, tying into periodic compliance checks. Documentation is integral to routine procedures, providing a record for performance tracking and regulatory audits. Technicians log key metrics, including pressure differentials across boundaries and airflow rates measured at access points using manometers and anemometers, to confirm system balance. These records integrate with systems (BMS) for automated monitoring and , enabling alerts for deviations that could indicate needs. Frequency guidelines for these procedures are informed by ANSI/ Standard 62.1 (2022), which outlines minimum activities and component-specific frequencies for ventilation systems to sustain acceptable . Cleaning may occur more frequently in environments with high dust loads, such as industrial settings, while inspections remain regular unless operational data from BMS logs suggests otherwise. Adherence to these schedules supports long-term system reliability and energy efficiency.

Common Problems and Solutions

One common issue in spaces is dust accumulation, which clogs HVAC filters and ducts, thereby reducing airflow and system efficiency. This buildup often results from inadequate filtration or environmental contaminants entering through ventilation openings. To address this, installing pre-filters at air returns captures before they settle in the plenum, preserving air circulation. Professional cleanings scheduled every 3-5 years or more frequently based on conditions, using methods like vacuuming and brushing, remove accumulated debris and restore performance, as recommended by NADCA for HVAC systems. Moisture intrusion represents another frequent problem in plenum spaces, often stemming from roof leaks, , or HVAC drains, leading to growth on surfaces and . proliferation not only degrades air quality but also damages structural elements over time. Effective remedies involve installing dehumidifiers to maintain relative below 60%, preventing , and sealing all potential leak points such as pipe penetrations and duct joints with appropriate caulks or tapes. These measures align with EPA guidelines for control in building envelopes and HVAC systems. Fire hazards arise from the use of unauthorized materials, such as non-plenum-rated cables, which can ignite rapidly and propagate flames through the air-handling space, exacerbating smoke distribution. For instance, standard PVC-jacketed cables release toxic fumes when burned, violating standards in plenums. Solutions include conducting regular audits by certified to identify non-compliant installations and retrofitting with CMP-rated cables, which feature low-smoke, flame-retardant jackets tested to UL 910 standards. This approach ensures compliance and minimizes retrofit costs from failed inspections or fines. Structural failures, such as sagging ceilings, commonly occur in spaces due to overloaded , of supports, or inadequate initial fastening, potentially leading to collapses or disruptions. These issues are often detected during routine visual inspections revealing bowed tiles or loose components. Remediation entails reinforcing the with additional metal hangers anchored to the building's structural , spaced no more than 4 feet apart, to restore load-bearing capacity. Such reinforcements should be performed during comprehensive inspections to prevent progressive failure.