Instrument transformer

An instrument transformer is a specialized electrical device designed to transform high voltages or currents from power transmission and distribution systems into lower, proportional values that can be safely measured and monitored using standard instruments or protective relays. These transformers operate on the principle of , providing electrical isolation between high-voltage circuits and metering equipment to ensure operator safety and accurate readings of quantities such as current, voltage, power, energy, , and . The two primary types of instrument transformers are current transformers (CTs) and voltage transformers (VTs), also known as potential transformers (PTs). Current transformers are connected in series with the load, stepping down high currents to standard secondary outputs like 1 A or 5 A, and their secondary windings must remain short-circuited during operation to avoid dangerous voltages. In contrast, voltage transformers are connected in parallel, reducing high voltages to levels such as 110–120 V, with secondary windings operated open-circuited for use with voltmeters or similar devices. Both types adhere to accuracy classes defined by standards like IEEE C57.13, with metering variants offering high (e.g., 0.3% ) for billing purposes and protection variants ensuring over wide ranges for fault detection. Instrument transformers play a critical role in electrical systems, enabling safe metering for billing, load surveys in industrial settings, and against faults, overvoltages, and disturbances through with relays and circuit breakers. Their advantages include cost-effective of measurements, minimal consumption, and enhanced safety via , though they require careful design to minimize errors from factors like burden and phase angles. Widely used in , substations, and systems, these devices ensure reliable operation and monitoring of networks up to levels.

Overview

Definition and Purpose

Instrument transformers are specialized electrical devices that reproduce high currents or voltages from primary power circuits in a scaled-down, proportional manner in their secondary circuits, enabling safe connection to metering equipment, relays, and instruments without interrupting the primary circuit's operation. These devices ensure that the secondary output remains at low, standardized levels, typically 5 A for currents or 100 V for voltages, facilitating accurate and monitoring in high-voltage environments. The primary purposes of instrument transformers include providing between the high-voltage primary side and low-voltage secondary side to protect personnel and equipment from electrical hazards, scaling electrical parameters to match the input requirements of standard instruments, and permitting non-intrusive, continuous measurements in systems. By isolating circuits, they prevent the propagation of faults, such as short-circuit currents or overvoltages, to sensitive secondary devices. Key benefits encompass minimized risk to operators through electrical separation, enhanced cost-efficiency relative to direct high-voltage sensing methods that would require specialized protective gear, and conformity to rigorous safety and performance criteria outlined in standards like IEC 61869, which specifies requirements for accuracy, error limits, and environmental resilience in applications above 1 kV or 1.5 kV . Instrument transformers originated in the late 19th century, coinciding with the expansion of distribution networks that necessitated safe, scaled measurement solutions for growing high-voltage infrastructure. The two principal types are current transformers, which handle current scaling, and voltage transformers, which manage voltage reduction.

Historical Development

The development of instrument transformers originated in the late amid the rapid adoption of (AC) systems for power distribution. The development of current transformers originated in the late 1880s, with early designs based on the closed-core invented by the ZBD team (Károly Zipernowsky, , and Miksa Déri) in 1885. These innovations were critical for isolating instruments from dangerous primary circuit voltages while providing accurate secondary signals. Key milestones in the early included the standardization of instrument transformers to ensure reliability and interoperability. In the , the (AIEE, predecessor to IEEE) issued the first dedicated standards, such as AIEE Standard No. 14 in 1925, defining requirements for performance and testing. Concurrently, the (IEC) began formulating analogous guidelines, promoting global consistency in design and accuracy classes. Post-World War II advancements focused on material improvements, with the widespread adoption of grain-oriented silicon steel cores enhancing efficiency by reducing magnetic losses and enabling compact, high-performance units for expanding efforts. During the 1960s and 1970s, instrument transformers played a vital role in the massive expansion of power systems, supporting increased generation capacity and transmission infrastructure in regions like North America and Europe, where aging assets from this era still form the backbone of many grids. The transition to the modern era accelerated in the 1980s with the introduction of electronic instrument transformers, which digitized signals for improved precision and reduced size, followed by optical variants in the 1990s and 2000s leveraging the Faraday effect for non-conductive current sensing in digital substations. These developments were driven by the demands of smart grid technologies, offering advantages in bandwidth, safety, and integration with communication networks. In the 2020s, ongoing updates to instrument transformers emphasize compatibility with integration, including low-power instrument transformers (LPITs) that facilitate precise monitoring of variable sources like and , enhancing grid stability and supporting decentralized energy systems. Market analyses project sustained growth, fueled by grid modernization initiatives worldwide.

Principles of Operation

Basic Electromagnetic Principles

Instrument transformers function based on the principle of , as described by Faraday's law, which states that an (EMF) is induced in a when it experiences a changing . In these devices, the primary winding—carrying the high current or voltage from the power system—produces an alternating in a ferromagnetic core, which links with the secondary winding. This flux change induces an EMF in the secondary proportional to the rate of flux variation and the number of secondary turns, enabling the transformation of electrical quantities to safer, measurable levels for instrumentation. The induced secondary EMF opposes the flux change per , ensuring energy conservation in the system. For an ideal transformer without losses, the relationships between primary and secondary quantities follow from the shared . In voltage transformers, the secondary voltage V_s relates to the primary voltage V_p by V_s = n V_p, where n = N_s / N_p is the turns ratio, with N_s and N_p denoting secondary and primary turns, respectively; this assumes uniform and no magnetizing current. Conversely, in current transformers, the secondary current I_s is given by I_s = I_p / n, where n = N_s / N_p, reflecting the balance that maintains equilibrium. These equations hold under the assumption of perfect and negligible core losses, providing exact proportional scaling. In practice, non-ideal behaviors arise due to the core's magnetic properties. Magnetization requires a small exciting current in the primary to establish the flux, but excessive flux can drive the core into saturation, where the magnetic flux density B no longer increases linearly with the magnetizing force H, distorting the output waveform and introducing errors. Qualitatively, the B-H curve illustrates this: in the linear region, flux rises steadily, but beyond the knee point, saturation flattens the curve, limiting induced EMF and causing nonlinear operation. Hysteresis, represented by the loop in the B-H curve, leads to energy losses as the core material's magnetization lags behind the applied field, while eddy currents—induced circulating currents in the core—generate additional heat and further reduce efficiency; these are minimized through laminated core construction. Polarity and phase relationships are critical for accurate measurements, ensured by the dot in winding design. Dots mark terminals of the same instantaneous : for instance, when enters the dotted primary , it induces a secondary leaving the dotted secondary , resulting in a 180° shift between primary and secondary currents or voltages. This guarantees in-phase summation in metering circuits, preventing errors in calculations or relays.

Differences Between Current and Voltage Transformers

Current transformers (CTs) and voltage transformers (VTs), also known as potential transformers, differ fundamentally in their operational principles due to their connection methods and driving forces. CTs are connected in series with the primary circuit, where the primary current drives the secondary current through a low-impedance path, typically transforming high line currents (e.g., hundreds of amperes) to a standard secondary value like 5 A, with the secondary behaving as a largely independent of the connected burden within specified limits. In contrast, VTs are connected in parallel across the primary voltage, functioning like small power transformers with the primary voltage applied directly to the secondary through a high-impedance path, scaling high voltages (e.g., 11 kV) to low secondary values like 110 V, where the secondary acts as a proportional to the primary. This series connection in CTs introduces minimal impedance to the power circuit, while the shunt connection in VTs isolates measurement devices from high voltages. A critical safety distinction arises from these operational modes: the secondary of a CT must never be open-circuited while the primary is energized, as the induced (e.m.f.) can generate dangerously high voltages—potentially up to 3500 V—due to the buildup in the core, risking failure, equipment damage, or personnel injury. To mitigate this, CT secondaries are short-circuited or connected to low-impedance burdens during maintenance, often with protective devices like shorting blocks. VTs, however, can be safely disconnected from their burden without such risks, as their operation resembles that of power transformers where open-circuiting the secondary simply reduces the load without inducing hazardous voltages; instead, VTs require protection against secondary short circuits, which can cause excessive heating managed by fuses or miniature circuit breakers. In response to system faults, CTs and VTs exhibit contrasting behaviors tailored to their roles. Metering-class CTs are designed to saturate during high-magnitude fault currents (often up to 20-50 times the rated value for short durations) to limit secondary current and protect metering equipment from overload, while protection-class CTs aim to maintain linearity over these ranges for accurate relay operation; however, saturation can still occur in protection CTs under severe conditions, distorting the waveform and reducing accuracy during transients like asymmetric faults with DC offsets. VTs, conversely, prioritize linearity and maintain proportional output even under overvoltages up to 110-140% of rated value for extended periods, with low core flux density to avoid saturation and ensure accurate voltage monitoring during faults, though they may experience transient errors immediately following voltage changes. Equivalent circuit models further illustrate these differences, simplifying CTs as an ideal in with the magnetizing branch and in series with the secondary burden referred to the primary, emphasizing low leakage reactance and high excitation impedance to minimize phase errors. VTs are modeled as an ideal with the primary voltage divided across the turns ratio, featuring low through-impedance (winding resistances and leakage reactances) and high magnetizing impedance to replicate the primary voltage accurately across the secondary. These models highlight how CTs prioritize current fidelity under varying loads, while VTs focus on voltage constancy despite burden variations.

Current Transformers

Construction and Design

Current transformers (CTs) are designed for series connection with the high-current primary circuit, typically transforming line currents to standard secondary outputs of 1 A or 5 A for and . The primary winding often consists of a single turn or passing through a (window-type or bar-type CTs), minimizing turns to handle high currents with low , while the secondary winding features numerous turns of fine wire to achieve the step-down ratio. Wound-type CTs, used for lower currents, have a multi-turn primary wound on the core alongside the secondary. The is usually made of high-permeability laminations to reduce magnetizing current and losses, with designs optimized to avoid under fault conditions. Common insulation methods include for indoor or outdoor units up to medium voltages, providing cooling and , or gas insulation with (SF6) for high-voltage applications in gas-insulated (GIS). Dry-type CTs employ resin encapsulation, such as for indoor use or hydrophobic cycloaliphatic (HCEP) for outdoor environments, eliminating oil-related risks and complying with environmental regulations. CTs integrate the core and secondary directly into high-voltage bushings of circuit breakers or transformers, using or composite insulators for compactness. These designs incorporate stratified layers to prevent partial discharges and ensure reliability under high electric fields. Mounting options vary by application: pedestal-mounted for outdoor substations on bases, types for panels, or bushing-integrated for high-voltage . Modern advancements include low-energy and electronic CTs with Hall-effect or sensors for wide bandwidth and measurement, supporting substations as of the . Auxiliary features like suppression devices may be added to mitigate ferroresonance in certain configurations.

Transformation Ratio

The transformation ratio of a (CT) is fundamentally determined by the nominal ratio n = \frac{N_s}{N_p}, where N_s is the number of turns in the secondary winding and N_p is the number in the primary winding. This ratio defines the ideal scaling between primary current I_p and secondary current I_s, such that in a perfect CT, the actual k = \frac{I_p}{I_s} = n. However, real CTs exhibit deviations because the magnetizing current required to establish the in the core consumes a portion of the primary ampere-turns, resulting in I_s being slightly lower than the ideal value and thus k \approx n with a minor discrepancy. CTs are typically marked with their nominal ratio in the form of primary-to-secondary amperes, such as 1000:5 A, indicating that a primary of 1000 A produces a secondary of 5 A under rated conditions. These markings adhere to international standards like IEC 61869-2, which specify tolerance bands for the transformation ratio based on the accuracy class of the CT. For metering applications, classes such as 0.5 or 1.0 limit the percentage ratio error to ±0.5% or ±1.0% at rated and , respectively, ensuring reliable scaling for devices. Protection-class CTs, denoted as 5P or 10P, allow wider tolerances (e.g., ±1% to ±5%) but prioritize performance under fault conditions. Errors in the transformation arise from both and discrepancies, primarily due to the magnetizing and leakage between windings. The is calculated as \epsilon = \frac{k_n I_s - I_p}{I_p} \times 100\%, where k_n is the nominal ; this increases with higher magnetizing requirements or burden. Leakage introduces a \theta between I_p and I_s, typically small (in minutes or degrees), as it causes the secondary to slightly; minimizing inter-winding spacing reduces this effect. For a 200:5 CT (nominal k_n = 40), assuming a secondary burden of 2.5 at 50 Hz and a magnetizing of 0.5% of rated I_p, the might approximate 0.2%, with a of about 10 minutes—values that must stay within class limits for accurate operation. Selection of the transformation ratio depends on the system's maximum continuous levels and the requirements of connected instruments, such as relays or rated for standard secondary currents of 5 A or 1 A. The nominal primary should exceed the expected load by a margin (typically 20-50%) to avoid under overloads, while ensuring the secondary output matches instrument input capabilities for precise scaling. The connected burden influences the effective ratio, though detailed impacts on accuracy are addressed separately.

Burden, Accuracy, and Classes

The burden of a () refers to the total load connected to its secondary circuit, typically expressed as the apparent power in () that the can deliver at its rated secondary current—usually 1 A or 5 A—while maintaining specified accuracy under a standard of 0.8 lagging. This includes the impedance from connected metering instruments, relays, cables, and other devices, with common ratings for metering s ranging from 1.5 to 30 , such as 15 for typical metering applications. Exceeding the rated burden increases secondary and can lead to core saturation, distorting the output waveform and reducing accuracy, particularly during high fault currents. Accuracy classes for CTs are standardized to ensure reliable performance for either metering or protection functions, with distinct requirements under the (IEC) 61869-2 guidelines. For metering CTs, classes such as 0.1, 0.2, 0.5, 1, 3, and 5 specify limits on ratio error and phase displacement at percentages of rated primary current (e.g., 5%, 25%, 50%, 100%), where class 0.5 allows a maximum ratio error of 0.5% at rated current and 1.5% at 5% of rated current. Protection CTs use classes 5P and 10P, which prioritize performance during overcurrents up to the accuracy limit factor (, often 5 to 20 times rated current), with class 5P limiting composite error to 1% at rated current and 5% at ALF times rated current. These classes ensure metering CTs provide precise energy measurements for billing, while protection CTs deliver faithful fault current reproduction to avoid relay maloperation. The primary measure of accuracy is the error, defined as the deviation between the actual and the nominal , calculated as: \epsilon = \frac{k_n I_s - I_p}{I_p} \times 100\% where k_n is the nominal transformation , I_s is the actual secondary , and I_p is the actual primary under rated burden and . displacement, the angular difference between primary and secondary currents (positive if secondary leads), is also limited, typically to 30 minutes for class 0.5 metering CTs at rated . For protection CTs, composite error assesses overall fidelity during faults, defined as the root-mean-square () difference between the primary and the reversed secondary scaled by the nominal , expressed as a : \epsilon_c = \frac{100}{I_p} \sqrt{\frac{1}{T} \int_0^T (i_p - k_n i_s)^2 \, dt} \% where i_p and i_s are instantaneous primary and secondary currents, and T is the period; limits are 5% for 5P and 10% for 10P at ALF (e.g., <10% error at 20 times rated current for class 10P). Testing CTs involves verifying compliance by applying burdens matching or less than the rated value to prevent saturation and ensure errors stay within class limits, often using primary injection or comparison methods at specified currents and power factors. Mismatched burdens during operation or testing can cause excessive heating or nonlinear response, necessitating selection of CTs with sufficient VA rating to accommodate the total secondary circuit impedance.

Multi-Ratio and Special Types

Multi-ratio current transformers (CTs) feature secondary windings with multiple taps, enabling selectable transformation ratios to accommodate varying primary currents in a single device. These taps allow users to configure ratios such as 600:5 or 1200:5 by connecting external links to specific points on the winding, providing flexibility without requiring multiple dedicated CTs. This design is particularly useful in substations where load conditions may change, but it introduces added complexity in manufacturing and installation compared to single-ratio CTs, potentially impacting overall cost and maintenance. The versatility gained supports broader application in dynamic systems, outweighing the complexity for installations needing adaptability. Special types of CTs address niche requirements beyond standard configurations. Bushing CTs, integrated into the insulation of power transformers or circuit breakers, utilize the high-voltage conductor as a single-turn primary while encasing a core and secondary winding within the bushing structure for compact, high-current measurement up to thousands of amperes. Linear couplers, an air-core variant, function as mutual reactors to detect both and components in fault currents, commonly employed in schemes where they produce an output proportional to the rate of change of primary current. Low-energy CTs, designed for IoT-enabled metering, harvest power directly from the measured circuit to operate wirelessly without batteries, enabling remote energy monitoring in smart grids with minimal power draw. In modern developments, Hall-effect sensor-based CTs have emerged for wide-range measurements, offering linear response to and currents across broad bandwidths and integrating seamlessly with 2020s digital substation systems for enhanced and protection. These sensors detect magnetic fields generated by currents without physical contact, providing and compatibility with relays.

Voltage Transformers

Construction and Design

Instrument voltage transformers, also known as potential transformers, feature a and winding configuration optimized for high-voltage and accurate voltage stepping down. The primary winding handles the high system voltage and consists of fewer turns made from large cross-section wire to minimize and , while the secondary winding provides a low-voltage output, typically 115-120 V, suitable for metering and protection devices. The is designed with low levels and a large cross-section to further reduce the number of turns required, enhancing and compactness. Stratified is employed between layers of the windings to prevent partial discharges, which could degrade the over time; this involves layering materials like or to distribute electric stress evenly and maintain integrity under high fields. The primary types of instrument voltage transformers are electromagnetic inductive designs, which use magnetic cores to transfer voltage. These are commonly insulated with for lower voltages or (SF6) gas for higher voltages, providing superior and compactness in gas-insulated units. However, owing to SF6's high , SF6-free alternatives such as clean air (nitrogen-oxygen mixtures) and fluoronitrile-based gases like are increasingly used in new installations to meet environmental regulations as of 2025. Oil-immersed versions feature or polymer bushings for outdoor applications, while SF6-filled transformers employ sealed housings to contain the gas under low pressure, enabling operation up to 800 kV or higher in extra-high-voltage systems. These designs prioritize mechanical robustness, with heavy-walled steel tanks in oil types to withstand internal pressures, and are rated for system voltages extending to 1000 kV in ultrahigh-voltage applications where capacitive variants may supplement inductive ones. Mounting configurations for these transformers include pedestal bases for outdoor substation installations, allowing stable support on foundations, and indoor designs for controlled environments like rooms. To mitigate ferroresonance—a potential in ungrounded systems—suppression coils or resistors, typically rated at 27-60 Ω and W, are integrated into the secondary windings or open-delta connections. Material advancements post-2000s have shifted toward epoxy-resin encapsulation in dry-type variants, using cycloaliphatic epoxy (CEP) or hydrophobic variants (HCEP) to eliminate oil and reduce environmental risks from leaks or disposal, aligning with regulations on hazardous substances and promoting in urban and ecologically sensitive deployments.

Transformation Ratio and Compensation

The transformation ratio of a voltage transformer is defined as n = \frac{N_p}{N_s}, where N_p is the number of turns in the primary winding and N_s is the number of turns in the secondary winding. Under no-load conditions, the primary voltage V_p relates to the secondary voltage V_s by the equation V_p = n V_s, assuming negligible magnetizing . This ratio provides the fundamental voltage scaling for and protection applications, with practical designs adjusting turns to minimize deviations from ideality. To address inherent errors from excitation current, which causes voltage drops across the windings, compensation techniques are integrated into designs. Auxiliary windings connected in parallel with the secondary can reduce leakage effects, while capacitive dividers in capacitive voltage transformers (CVTs) employ tuned compensation reactors to counteract phase shifts and ratio inaccuracies. These methods ensure the overall remains below 0.5%, aligning with accuracy requirements for precise metering. Voltage transformers are marked with their nominal ratios, such as 11000/110 V, denoting the primary-to-secondary voltage scaling, alongside the rated burden that specifies the accuracy class under defined load conditions. In long transmission lines, the —arising from distributed capacitance—elevates receiving-end voltage under light-load conditions, potentially distorting measurements; compensation in CVTs, via series inductors tuned to line frequency, mitigates this by stabilizing the effective ratio and .

Accuracy and Burden Considerations

In voltage transformers, the burden refers to the secondary load, typically expressed in volt-amperes (), which directly influences the transformer's output voltage and overall precision. A common rated secondary VA for metering applications is around 75 to 100 VA, though modern electronic instruments often impose much lower burdens, such as less than 10 VA total. Excessive burden causes voltage drops across the secondary winding impedance, leading to reduced secondary voltage under load compared to no-load conditions, thereby degrading measurement accuracy. This effect is quantified by the percentage voltage regulation, which measures the deviation in secondary voltage due to load: \% \text{ regulation} = \frac{V_{\text{no-load}} - V_{\text{full-load}}}{V_{\text{full-load}}} \times 100 Here, V_{\text{no-load}} is the secondary voltage with minimal burden, and V_{\text{full-load}} is the voltage at the rated burden; higher burdens increase this , potentially shifting the ratio error from positive (under light load) to negative values as the transformer's internal compensation is overwhelmed. To optimize performance, the rated burden is often selected as approximately 1.5 times the expected connected load, ensuring the transformer operates within its accuracy limits at typical secondary impedances. Accuracy classes for voltage transformers, as defined by IEC 61869-3, range from 0.1 to 3 for metering purposes, specifying maximum permissible and angle errors under rated frequency (50 Hz or 60 Hz) and burden conditions. For instance, class 0.1 allows a error of ±0.1% and displacement of ±5 minutes at 80-120% of rated voltage and full rated burden, while class 3 permits ±3% error and ±180 minutes displacement; these limits ensure reliable measurement when the connected burden does not exceed the rated and (typically 0.8 lagging). Errors are evaluated across a burden range from 0 to 100% of rated, with performance guaranteed down to 5% of rated voltage. Voltage transformers are designed to withstand continuous overvoltages of 1.2 (pu) and short-term overvoltages up to 1.5 pu for 30 seconds without or excessive error, accommodating system transients in effectively earthed or isolated configurations. This capability maintains accuracy within limits during such events, preventing ferroresonance or that could amplify errors. in the primary voltage, arising from nonlinear loads, further impacts accuracy by inducing nonlinear and losses in the core, which distort the secondary and increase both ratio errors and displacements. For a 0.2 under a distorted supply with up to 40% fifth content, voltage errors may reach -0.6% at higher orders (e.g., 100th ), and shifts can exceed 50 minutes, though typical network levels ( <5%) keep errors within limits; compensation techniques or low-distortion core materials are often employed to mitigate these effects.

Capacitive and Electronic Variants

Capacitive voltage transformers (CVTs) represent a non-inductive alternative to traditional voltage transformers, utilizing a capacitive voltage divider to step down high voltages. The construction typically involves a stack of series-connected capacitors forming the high-voltage arm of the divider, housed in a porcelain insulator filled with insulating oil or gas, which provides partial voltage division from the line potential. This divider feeds an intermediate voltage, typically 5-20 kV, to an electromagnetic unit (EMU) at the base, consisting of a step-down transformer, a compensating reactor to correct phase shifts, and a ferroresonance suppression circuit. The tuning reactor ensures resonance at the system frequency, enhancing accuracy and stability. CVTs are particularly advantageous for high-voltage applications, offering lower costs than inductive designs at voltages above 66 kV due to reduced material requirements, while providing a wide bandwidth suitable for both power frequency measurements and high-frequency power line carrier signals. They are commonly deployed on transmission lines from 69 kV to 765 kV for metering, protection, and coupling purposes. However, CVTs are susceptible to ferroresonance, a nonlinear oscillation that can lead to overvoltages and equipment damage, often mitigated by damping circuits but still posing risks during switching operations. Their transient response is inferior to inductive transformers, with voltage oscillations and decay times that can delay fault detection, such as up to several cycles in severe cases. Electronic instrument transformers, also known as low-power instrument transformers (LPITs) or non-conventional instrument transformers (NCITs), employ digital and optical technologies to measure voltage and current without relying on magnetic cores. These include optical voltage transformers (OVTs) based on the for electric field sensing and capacitive divider-based designs for voltage measurement combined with electronic processing. Fiber optic links transmit signals from the high-voltage sensor to a merging unit, providing inherent immunity to (EMI) and electrical isolation. Development of these technologies began in the 1970s with optical sensors but gained practical adoption in the 1990s, evolving into standards-compliant devices for digital substations. They align with , particularly through the Sampled Values protocol (IEC 61850-9-2), enabling direct digital outputs over Ethernet for seamless integration into systems. Advantages include compact size, lightweight construction (e.g., 25% weight reduction in gas-insulated ), no or ferroresonance risks, and a wide from steady-state to fault conditions. Despite these benefits, electronic variants often incur higher initial costs due to advanced electronics and calibration needs, and their performance can be sensitive to environmental factors like temperature. In comparison, CVTs excel in cost-effective transient response for power frequency applications but lag in speed and accuracy during faults compared to electronic transformers, which offer superior digital integration for smart grids with response times under 2 seconds for phasor measurements. Electronic designs provide direct network-compatible outputs, reducing wiring complexity, while CVTs require analog-to-digital conversion. Limitations such as CVT ferroresonance risks contrast with electronic higher upfront expenses, making the choice dependent on system voltage and digitalization level.

Applications

Metering and Measurement

Instrument transformers, particularly current transformers (CTs) and voltage transformers (VTs), are essential for accurate energy metering in electrical power systems by stepping down high primary currents and voltages to safe, measurable levels suitable for watt-hour meters. These meters rely on the transformed signals to compute active power using the formula P = V I \cos \phi, where V represents the voltage, I the current, and \phi the phase angle difference, with energy consumption in kilowatt-hours (kWh) obtained by integrating power over time for precise billing. In revenue metering applications, high-accuracy class 0.1 instrument transformers are commonly deployed to minimize measurement deviations, ensuring with stringent requirements for and industrial billing. These devices are typically installed in tamper-proof enclosures to safeguard against manipulation and environmental factors, often positioned at service entrances or substations to capture total load data reliably. The overall billing accuracy in such setups is influenced by the accumulation of errors from both CTs and VTs, including and phase angle inaccuracies, which must be controlled to keep the combined system error within utility-specified limits, typically 0.3% to 0.5% under normal operating conditions per standards like ANSI C12.20 and IEEE C57.13. Proper burden matching and periodic verification help mitigate these effects, preventing revenue losses or disputes. Modern implementations increasingly integrate instrument transformers with Supervisory Control and Data Acquisition (SCADA) systems, allowing for real-time logging of metering data to support load forecasting, demand management, and grid optimization. This connectivity enhances monitoring capabilities while maintaining the focus on steady-state measurement for commercial purposes.

Protection and Control Systems

Instrument transformers play a critical role in power system protection by providing scaled-down electrical signals to protective relays, enabling the detection and isolation of faults to prevent equipment damage and maintain system stability. Current transformers (CTs) are primarily used for overcurrent protection, where they step down high fault currents to levels suitable for relay inputs, allowing relays to detect abnormal conditions such as short circuits and trigger circuit breaker operation. Voltage transformers (VTs), on the other hand, supply voltage signals for undervoltage protection, which safeguards against low voltage conditions that could harm motors and other loads, and for negative sequence protection, which identifies unbalanced faults like phase-to-phase errors by measuring symmetrical components. A key consideration in protection applications is the saturation behavior of CTs, which can distort secondary currents during high-magnitude faults and lead to misoperation. -class CTs, such as those designated under the IEC 5P accuracy , are specifically designed to limit composite errors to 5% or less when primary currents reach 20 to 100 times the rated value for short durations, ensuring reliable performance without excessive . For instance, a 5P20 CT maintains accuracy limits during fault currents up to 20 times rated, with the design incorporating low cores to recover quickly post-fault. In control systems, instrument transformers provide essential inputs for operational devices beyond basic fault clearing. CTs and VTs feed signals to circuit breakers for /close decisions based on and voltage thresholds, while VTs are integral to synchronizing equipment, where they measure bus and line voltages to ensure phase match, frequency alignment, and voltage equality before paralleling generators or closing breakers. A prominent example is protection for transformers and generators, which relies on matched CT ratios at both ends of the protected zone to compare incoming and outgoing s; any imbalance exceeding a set threshold indicates an internal fault, prompting rapid isolation. The evolution toward digital substations in the 2020s has driven the adoption of low-power instrument transformers (LPITs), such as Rogowski coil-based CTs and optical VTs, which deliver minimal output power (e.g., milliwatts) directly compatible with microprocessor-based relays, reducing wiring burdens and enabling digital communications for faster, more integrated schemes. These LPITs eliminate traditional magnetic issues and support advanced algorithms in numerical relays for enhanced fault discrimination in modern grid environments.

Standards and Testing

International Standards

The (IEC) 61869 series establishes the foundational global standards for instrument transformers, applicable to newly manufactured devices with nominal voltages above 1 kV AC or 1.5 kV , operating at frequencies from 15 Hz to 400 Hz or in DC applications. IEC 61869-1:2023 specifies general requirements, including error limits for analogue and digital secondary signals, bandwidth specifications, filters, and accuracy classes that define permissible and errors for metering and functions. It also mandates tests, such as type tests for impulse withstand and routine measurements, to ensure integrity under high-voltage conditions. IEC 61869-2:2012 provides additional requirements for current transformers (CTs), focusing on inductive types used with measuring instruments and protective devices, including specific accuracy classes like 0.1 to 5P for precise metering and applications. IEC 61869-3:2011 addresses inductive voltage transformers (VTs), detailing transformation s, burden capabilities, and performance tailored to electrical and needs. In , the IEEE C57.13-2016 standard outlines requirements for instrument transformers in systems, emphasizing electrical, dimensional, and mechanical characteristics with integrated safety features. It defines standard transformation ratios, such as 600:5 for CTs, and burden ratings (e.g., 0.1 Ω at 2.5 ) to ensure compatibility with metering and relaying equipment. markings and test procedures for ratio, phase angle, and demagnetization are also specified to facilitate accurate installation and performance verification. The (ANSI) C12.11-2024 governs instrument transformers for revenue metering in the United States, covering current and inductively coupled voltage transformers with basic insulation levels from 10 to 350 . It prioritizes high metering accuracy (e.g., 0.3% error limits), thermal ratings for continuous operation, and standardized dimensions to support reliable energy billing systems. CIGRE, through its technical brochures, offers supplementary guidelines for high-voltage instrument transformer applications, particularly in transmission networks above 60 kV. Brochure 512 (2010) analyzes global reliability data and failure modes for high-voltage CTs and VTs, recommending design enhancements for transient withstand and maintenance practices. Brochure 301 (2010) addresses the use of optical instrument transformers in high-voltage testing, providing performance criteria for non-conventional sensors in severe electromagnetic environments. Revisions to the IEC 61869 series in the 2010s, starting with core parts published between 2011 and 2016, replaced the older IEC 60044 standards and incorporated provisions for instrument transformers to align with substations. IEC 61869-6:2016 introduced requirements for low-power instrument transformers (LPITs), including and voltage sensors with rated outputs below 1 , emphasizing interfaces and reduced size for integration. Subsequent parts like IEC 61869-9:2016 and IEC 61869-10:2017 extended support for outputs and passive LPITs, with accuracy specifications under conditions to ensure reliable performance amid non-sinusoidal waveforms from . These updates also enhanced withstand criteria within and accuracy tests, mandating evaluation of transformer response to up to 15% for protection and metering integrity. IEC 61869-20:2025 addresses requirements for instrument transformers in high-voltage applications, including protections against mechanical and environmental stresses.

Testing Procedures and Calibration

Testing procedures for instrument transformers, including current transformers (CTs) and voltage transformers (VTs), are essential to verify their performance, accuracy, and safety in metering and applications. These procedures are governed by international standards such as IEEE Std C57.13-2016 and the IEC 61869 series, which categorize tests into routine (performed on each unit), type (for design validation), and special (as required). Routine tests ensure compliance with accuracy classes, while type tests evaluate long-term reliability under operational stresses. focuses on verifying , , and limits with traceable measurements to national institutes, minimizing uncertainties in revenue metering and relay operations. Accuracy verification begins with ratio and phase angle measurements, conducted at rated frequency and specified burdens. For CTs, tests occur at 5% to 120% of rated current, using methods like the voltmeter-ammeter or comparator bridge to determine correction factor (RCF) and transformer correction factor (TCF), with limits such as ±0.15% for 0.15 accuracy class metering CTs. VTs are tested at 80% to 120% of rated voltage, ensuring phase displacement below 20 minutes for 0.3 class units. These measurements require equipment calibrated to uncertainties of ±0.075% in and ±0.75 milliradians in for high-precision applications, with demagnetization of the core prior to testing to ensure reproducibility. Dielectric and insulation tests assess withstand capabilities. Induced voltage tests apply a voltage of approximately twice the rated secondary voltage induced in the secondary winding at approximately twice the rated frequency for 150 seconds or until a temperature rise of 10 °C, whichever occurs first, to check inter-turn insulation; this test is not required if sinusoidal induction at 400 Hz causes core saturation. Applied voltage tests use 2-4 kV on secondary windings for one minute. Partial discharge measurements, routine for units above 5 kV per IEC standards, limit discharges to ≤10 pC at 1.2 times rated voltage for applicable designs. Temperature rise tests, as type tests, monitor windings under rated burden until steady-state, ensuring rises below 65°C for indoor CTs. Calibration procedures emphasize and evaluation per IEEE/IEC 61869-21, using standards like those from NIST for CTs, where errors are calibrated at 60 Hz with uncertainties as low as 20 . For electronic variants, output calibration follows IEC 61869-10, verifying and accuracy. Burdens are calibrated separately using three-voltmeter methods to simulate service conditions, ensuring total secondary burden does not exceed rated . Post-calibration, certificates provide correction factors for field adjustments, with recalibration intervals of 1-5 years depending on usage.

References

  1. [1]
    [PDF] Instrument Transformers - ABB
    Instrument transformers (ITs) are designed to transform voltage or current from the high values in the transmission and distribu-.
  2. [2]
    Instrument Transformers: What is it? (and their Advantages)
    Feb 24, 2012 · An instrument transformer is used in AC systems to measurement of electrical quantities such as voltage, current, power, energy, power factor, and frequency.What is Instrument Transformer? · Types of Instrument... · Current Transformer (C.T.)
  3. [3]
    What is an Instrument Transformer : Types and Their Differences
    A transformer that is used to measure electrical quantities like current, voltage, power, frequency and power factor is known as an instrument transformer.
  4. [4]
    None
    ### Summary of Instrument Transformers from ABB Instruction Manual (1VLM000610 Rev.24)
  5. [5]
    IEC 61869-1:2023
    Jun 14, 2023 · IEC 61869-1:2023 is applicable to newly manufactured instrument transformers intended for applications where the nominal voltage is higher than 1 kV AC or 1,5 ...
  6. [6]
    (PDF) Historical Development of the Transformer - ResearchGate
    Historical Development of the Transformer is the IEE Sri Lanka Centre 2000/01 Chairman's Lecture. It presents the outcome of a research done on how the ...
  7. [7]
    Archives:Transformers at Pittsfield, part 1
    Feb 11, 2019 · William Stanley designed and built a great deal of two-phase equipment during the 1890's, partly because of a belief in its superiority over ...
  8. [8]
    AIEE 14-1925 - IEEE Standards Association
    The Standards in this section apply to transformers designed for use with measuring or control devices. Status: Superseded Standard; Board Approval ...Missing: historical | Show results with:historical
  9. [9]
    [PDF] Advanced Transmission Technologies - Department of Energy
    Along with aged assets, primarily from the 1960s and 1970s, the electric power system is evolving, from consisting of predominantly reliable, dependable, and ...
  10. [10]
    [PDF] Optical current transducers for electrical power systems
    A literature survey of Optical Current Transducers (OCTs) with particular emphasis on electric power systems measurements has been performed.
  11. [11]
  12. [12]
    Expanding the Role of Low-Power Instrument Transformers in Grid ...
    Oct 6, 2025 · For renewable integration, LPITs ensure that variable generation sources are measured precisely, supporting algorithms for balancing and ...
  13. [13]
    [PDF] Instrument Transformer Basic Technical Information and Application
    Instrument transformers can be simplified with basic magnetic circuits. Figure 2 depicts the most basic magnetic circuit of an ideal instrument transformer.Missing: electromagnetic | Show results with:electromagnetic
  14. [14]
    [PDF] B2 Current and Voltage Transformers - Schneider Electric
    A CVT is a series resonant circuit. The introduction of the electromagnetic transformer between the intermediate voltage and the output makes possible further ...<|control11|><|separator|>
  15. [15]
    [PDF] Current and Voltage Transformers Lecture 5 : Introduction to CT
    However, a fundamental difference is that while regular power transformers are excited by a voltage source, a current transformer has current source excitation.
  16. [16]
    None
    ### Summary of Construction and Design of Instrument Voltage Transformers (Potential Transformers)
  17. [17]
    Voltage Transformer TVI (72.5 - 420 kV) | Hitachi Energy
    TVI is a SF6 gas-insulated Inductive Voltage Transformer built for revenue metering and protection in high voltage networks.
  18. [18]
    Siemens SF6 Insulated Voltage Transformers Air-insulated switchgear
    SF 6 insulated voltage transformers are used to convert high transmission line voltages (up to 800kV) to standardized low and easily measurable values.<|separator|>
  19. [19]
    Specifying current transformers for protection purposes - LinkedIn
    May 16, 2017 · The IEC 61869-2 provides the following definitions for the parameters which we have considered in this paper. • The rated transformation ...<|control11|><|separator|>
  20. [20]
    Current Transformer - Electrical Notes & Articles
    Apr 16, 2011 · Kn = rated transformation ratio, Ip = actual primary current, Is = actual secondary current ... Formula : Ip/Is = Ns/Np; Ip = Primary ...
  21. [21]
    Why Current Transformers Have Errors: Understanding the Basics
    Mar 13, 2025 · However, in practice, the magnetizing current consumes a portion of the primary current, leading to a reduced secondary current and causing ...
  22. [22]
  23. [23]
    Understanding Current Transformer Accuracy Classes Under IEC ...
    Mar 13, 2024 · This blog will delve deep into the IEC 61869-2 standard and focus specifically on accuracy classes defined by CTs and their significance.Missing: nominal actual
  24. [24]
    What is the error in % on class 0.5s and class 1? - Schneider Electric
    May 23, 2016 · For Current transformers the tolerance for each class is as follows: For class 0.5s, if: I < 0.01 x In - Percentage ratio error 1.5%
  25. [25]
    Current Transformer Accuracy Classes: What Do They Mean?
    Mathematically, it is calculated as [(Kn × Is) – Ip] / Ip × 100%, where Kn is the nominal ratio, Is is the secondary current, and Ip is the primary current. A ...
  26. [26]
    Errors , Characteristics & Methods to reduce errors in Current ...
    Apr 6, 2017 · Leakage reactance tends to increase ratio error. Therefore, the two windings, primary and secondary should be close together to reduce the ...
  27. [27]
  28. [28]
    The right choice of current transformers – ratio, nominal current ...
    Consider ratio, nominal current, rated power, and accuracy class when choosing a current transformer. The ratio should be directly above the measured current.<|control11|><|separator|>
  29. [29]
    [PDF] Sizing Current Transformers for Line Protection Applications
    n /n n. = = = (2) where: n is the CT turns ratio, n = nS/nP. Equation (2) can be expressed in per-unit (pu) values as: ( ). ( ). S. P. I pu. I pu. = (3). 2) ...Missing: actual | Show results with:actual
  30. [30]
    None
    ### Summary of Current Transformers (https://www.cedengineering.com/userfiles/Current%20Transformers%20R1.pdf)
  31. [31]
    [PDF] Current Transformer Accuracy Ratings
    Current transformer accuracy is specified by a percent ratio error. IEEE standard is 10%, while IEC has 5% (preferred) and 10% ratings.
  32. [32]
    [PDF] IS/IEC 60044-1 (2003): Instrument Transformers, Part 1
    The current error expressed in per cent is given by the formula: ... error for current transformers having rated transformation ratios differing from unity.
  33. [33]
    How to select taps for multi ratio current transformer?
    Jan 2, 2021 · Various winding taps are provided allowing user to pick and choose the desired ratio. Many models allow up to ten different ratios and these CTs ...Missing: design | Show results with:design
  34. [34]
    TechTopics No. 91 - Siemens US
    Outside North America, the most common standards for current transformers are the IEC 61869-1 and 61869-2 standards (replacement for the old IEC 60044-series), ...
  35. [35]
    [PDF] CTs
    6.4.2 Tapped-secondary or multi-ratio current transformer. The relay accuracy class applies only to the full winding, unless otherwise specified. If ...
  36. [36]
    Transformer bushing CTs - Megger
    A bushing type CT consists only of a toroidal-shaped core with a secondary winding. The bushing's centre conductor forms the single turn primary of the BCT.
  37. [37]
    Bushing-Type Current Transformer - Camille Bauer Metrawatt AG
    In stockBushing-type current transformers are used wherever high currents are to be acquired and processed. hey are directly placed on the primary conductor.
  38. [38]
    LC-1 linear coupler relays - ABB
    These relays are used for bus differential protection in conjunction with Linear Couplers, which are air coil mutual reactors.
  39. [39]
  40. [40]
    Smart Current Transformer - Milesight
    The CT10x is designed to derive power directly from the measured circuit, eliminating the constraints of batteries while ensuring seamless operation.
  41. [41]
    Current Transformer - MultiTech
    The MultiTech Current Transformer (MTCT) is a wireless, self-powered energy monitor designed for precise amperage and amp-hour measurements.
  42. [42]
    [PDF] Use of Hall Effect Sensors for Protection and Monitoring Applications
    A Hall Effect sensor is a transducer that outputs a voltage in response to the magnetic field generated by the current flow. The sensor is used to accurately ...
  43. [43]
    IEEE C57.13-2016 - IEEE Standards Association
    IEEE C57.13-2016 defines requirements for instrument transformers, covering electrical, dimensional, and mechanical characteristics, and safety features.
  44. [44]
    What is Ferranti Effect in Power Transmission Lines?
    Ferranti Effect causes the receiving voltage to be greater than the sending voltage in a long-distance transmission line that has a very light load or no load ...
  45. [45]
    [PDF] Burden Rating of Voltage Transformers And the Impact on Accuracy ...
    The conclusion can be made that for almost any modern application, improved accuracy performance can be gained by purchasing VTs with lower full rated burdens, ...
  46. [46]
    The Essentials Of Voltage Transformers (Advanced Theory and ...
    Dec 20, 2018 · This technical article will explain all important aspects of voltage transformers in MV and HV measurement and protection applications.
  47. [47]
    Potential transformer accuracy class - Voltage Disturbance
    Feb 17, 2019 · The maximum ratio deviation over a specified range of burden defines the accuracy class of the transformer. If the maximum ratio error is +/-0.3 ...
  48. [48]
    3D Electromagnetic Field Analysis Applied to Evaluate the Accuracy ...
    The article concerns the phenomenon of the influence of voltage higher harmonics of supply voltage on the accuracy (up to the 100th harmonic) of the measuring ...
  49. [49]
    [PDF] IEC Capacitive & Coupling Capacitor Voltage Transformers (CVT ...
    The capacitor divider will provide between 5kV and 20kV to the intermediate step down transformer which has a low voltage output as requuired. 1000kV Capacitive ...
  50. [50]
    [PDF] Distribution Automation Handbook: Elements of Power Systems
    Figure 3.93: Capacitive voltage transformer's principal construction. The figure above shows the principle of a capacitive voltage divider on which the CVT is.
  51. [51]
    [PDF] CVT Transients Revisited – Distance, Directional Overcurrent, and ...
    Abstract—Several classic papers explain the fundamentals of capacitive voltage transformer (CVT) design, operation, and transient response. Distance elements ...
  52. [52]
    [PDF] INTRODUCTION - SUST Repository
    ... immunity to EMI ... Electronic current transformers (ECTs) with a Rogowski coil have been ... Optical fiber instrument transformers with digital output signals.
  53. [53]
    [PDF] How Low-Power Instrument Transformers and Digital Secondary ...
    The IEC 61869 series standards further consolidated analog and digital interface requirements, enabling industry-wide acceptance and LPIT integration with ...
  54. [54]
    Electronic transformer performance evaluation and its impact on PMU
    Nov 7, 2019 · The electronic transformer performs well and can output digital signals via network. ... transient response problem of the CVT. The performance of ...Missing: Comparison | Show results with:Comparison
  55. [55]
    [PDF] METERING PROTOCOL APPENDICES A-G
    • the voltage transformer (VT) ratio. • the current transformer (CT) ratio. • the number of meter elements. The following data from a transformer test report ...<|separator|>
  56. [56]
    C57.13.6-2005 - IEEE Standard for High Accuracy Instrument ...
    Dec 9, 2005 · This standard defines one new 0.15 V transformer accuracy class, two new 0.15 current transformer accuracy classes, two new current transformer burdens.
  57. [57]
    [PDF] AN-136: Metering System Accuracy
    Apr 14, 2017 · When combining a meter with external CTs, it seems intuitive that combining a 0.2% meter with 0.3%. CTs should yield a 0.5% system accuracy ...
  58. [58]
    [PDF] Metering Application Requirements STD-DC-000005 REVISION 06
    Sep 24, 2024 · Instrument Transformers (current and voltage): A transformer used to reduce the actual line currents and voltage to levels appropriate for ...<|control11|><|separator|>
  59. [59]
    Metering for Utility Applications | EIG - Electro Industries/GaugeTech
    Accurate real time data from metering of utility transformers, breakers, and other plant equipment and the ability to communicate the metering data to SCADA ...
  60. [60]
    Negative Sequence Overvoltage Protection - Voltage Disturbance
    Apr 3, 2024 · Negative sequence overvoltage protection is used for protection of service main, motor circuits, sensitive loads for conditions such as reverse phase rotation.
  61. [61]
    What Do the 5P10 and 5P20 Mean in a Current Transformer?
    The 5P20 marking on a current transformer indicates that if the primary fault current is 20 times the rated current, the error will be 5%.
  62. [62]
    Voltage transformer selection scheme in complex substations | EEP
    Dec 2, 2024 · Synchronization, a critical operation, relies on VTs to provide voltage signals from both the line and busbar sides of a circuit breaker.
  63. [63]
    Four Special Differential Protections And Their Respective CT ...
    A differential protection monitors an area limited by CTs which measure incoming and outgoing currents.
  64. [64]
    [PDF] Low-Power Instrument Transformers
    Oct 30, 2025 · This problem is well known and has been described for linear coupler applications for more than 50 years. A select group of sensor ...<|control11|><|separator|>
  65. [65]
    IEC 61869-2:2012
    Sep 18, 2012 · IEC 61869-2:2012 is applicable to newly manufactured inductive current transformers for use with electrical measuring instruments and/or electrical protective ...
  66. [66]
    IEC 61869-3:2011
    Jul 13, 2011 · IEC 61869-3:2011 applies to new inductive voltage transformers for use with electrical measuring instruments and electrical protective devices.
  67. [67]
    ANSI C12.11-2006 (R2019) - Instrument Transformers for Revenue Metering 10kV BIL through 350 kV BIL
    ### Summary of ANSI C12.11-2006 (R2019) - Instrument Transformers for Revenue Metering
  68. [68]
    Final Report of the 2004 - Part 4: Instrument Transformers | eCIGRE
    €300.00Summary. Results from a world wide utility survey of failures and service experience with instrument transformers rated for 60 kV and above are presented.
  69. [69]
    Use of optical instrument transformers for high-voltage testing - e-Cigre
    Use of optical instrument transformers for high-voltage testing · This publication is free only for CIGRE members · Price for non member: 30 €.
  70. [70]
    Instrument transformers according to new IEC standards available
    Mar 19, 2015 · IEC 61869-3 Instrument transformers - Part 3: Additional requirements for inductive voltage transformers. New standards IEC 61869-1, IEC 61869-2 ...Missing: details | Show results with:details
  71. [71]
    IEC 61869-6:2016
    Apr 27, 2016 · IEC 61869-6:2016(E) is a product family standard and covers only additional general requirements for low-power instrument transformers (LPIT)
  72. [72]
    [PDF] IEC 61869-9:2016 - iTeh Standards
    This International Standard contains specific requirements for electronic low power instrument transformers (LPIT) having a digital output. This Part 9 is to be ...
  73. [73]
    Instrument transformers influence on harmonic measurements for ...
    Apr 15, 2020 · Inductive instrument transformers play a fundamental role in monitoring power network current and voltage. Inductive current transformers ...
  74. [74]
    [PDF] IEEE Std C57.13
    Jun 29, 2016 · This standard was prepared by the Instrument Transformer Subcommittee of the Transformers Committee of the IEEE Power and Energy Society. The ...
  75. [75]
    IEEE/IEC P61869-21 - IEEE SA
    Jun 6, 2024 · This standard provides requirements, methods, and guidelines to be applied to the evaluation of uncertainty in testing the accuracy of Instrument Transformers ...
  76. [76]
    [PDF] A Calibration Service for Current Transformers
    The Guide provides essential technical details of NIST calibration and related measurement services, such as levels of accuracy provided by NIST and the ...